Sie sind auf Seite 1von 17

Edition:V15.

03
Date:2015.9

No.:

Mains complementary off-grid PV power


generation systems
Technical specification
Model:NK-GP15000

Attention:

As the upgrade of the product version or other reasons, the content of this document will
not be updated regularly. Unless otherwise agreed, the document is only used as a guide,
and all statements, information and recommendations made in this document do not
constitute any express or implied warranties.
1. Technical characteristic

Function introduction

(1) This product is a solar photo-voltaic inverter power,using CPU intelligent control,
making solar controller and inverter in one. With pure sine wave output, low loss, high
conversion efficiency and reliability.

(2) Automatic identification and selection of solar, mains and battery reverse mode.

◆ W hen solar and battery voltage is high, the inverter mode will be selected
intelligently, using solar energy supply power to the load directly and charging
the battery at the same time.

◆ When the solar energy is not enough, the machine automatically switch to
solar common with battery to supply power to load;

◆ W hen solar existing and battery voltage down to low voltage protection value,
mains supply power to load (but mains don’t charge the battery), solar on the
battery charging.

◆ W hen the battery voltage is lower than the low voltage protection value, the
machine switch to mains supply power to load intelligently and charging the
battery at the same time to ensure the service life of the battery;

◆ This machine with automatic recognition function:during the day, it


automatically switch to solar priority status,the battery charging and load power
supplying; at night it automatically switching to the mains power priority mode,
mains priority for power supply and automatically monitoring battery state to
decide whether to charge the battery or not.

(3) Inverter DC under voltage, over voltage protection, temperature protection, AC


input under voltage protection, AC input over voltage protection, inverter output
short-circuit protection, inverter output overload protection

(4) Inverter monitoring through Wifi (software is updating).

(5) Touch screen real-time view of the inverter working condition

(6) With intelligent BMS system for management and protection:

◆ High precision voltage and current sampling.

◆ Auto protection function. The battery pack has the perfect and reliable
protection function: the battery pack over voltage, under voltage protection, the
battery single cell over voltage, under voltage protection, charge and discharge
over current protection, charge and discharge temperature protection(high
temperature, low temperature), short circuit protection,

◆The smart battery balance management. Passive balance method,


automatically balance control according to the battery voltage of each node to
ensure the consistency of the battery pack;
2. Technical specifications

Input Features of inverter

Index
NO. item Remark
Min. Rated value Max.

1 DC Voltage Range 180Vdc 216Vdc 288Vdc

2 Over Voltage Protection 284 Vdc 290Vdc 312Vdc

3 Over voltage recovery 270 Vdc 274Vdc 278Vdc

4 Low voltage protection 176Vdc 180Vdc 184Vdc

5 Low voltage recovery 227Vdc 230Vdc 233Vdc

6 AC input voltage range 220Vac

7 AC input frequency 50HZ

8 AC Charging voltage 247V

9 AC Charging current 15A

Output features of Inverter

Index
NO. item Remark
Min. Rated value Max.
1 Rated power 15000W 16500W
2 Rated output current 68A
3 198Vac 220Vac 242Vac In AC mode
Output Voltage
4 205Vac 220Vac 235Vac In inverting mode
Automatically tracking and
5 55HZ 60HZ 65HZ
Output Frequency adaptive in AC mode
6 59HZ 60HZ 61HZ In inverting mode
7 Output Waveform Pure sine wave
9 Waveform Distortion 5% linear load
10 Phase Deviation 2°
11 Switching Time 4ms
12 Efficiency 90
Dynamic Response 25%~50%~25% or 50%~
13 60ms
Recovery Time 75%~50% of load。

Dynamic Response 25%~50%~25% or 50%~


14 ±5%
Overshoot 75%~50% of load。
Peak Output Current
15 3:1
Coefficient
16 Battery Backup Time Continuous discharge

Protection Features of Inverter

NO. item Min. Rated Value Max. Remark


1 DC low voltage protection 176V 180V 184V Output circuit should have fuse
2 DC over voltage protection 284V 288V 312V
Automatic recovery after
3 Over-heat protection 85℃ 90℃ 100℃
temperature return to normal
4 AC input voltage range 220
5 Short-circuit protection Flashing and shut down after 1S
6 reverse polarity protection NO
120% of rated power, restart after
30S; 150% of rated power, shut
7 Over-load protection
down after 10S; 200% of rated
power,shut down after 1S

Features of Solar Controller Input

Index
NO. Item Note
Min. Rate Value Max.

1 Solar panel input range 250Vdc 330Vdc 450Vdc

2 Battery Voltage - 216Vdc

Input over voltage


3 470Vdc
protection
Input Over voltage
4 437Vdc
recovery
Input reverse connection Testing without output connection
5 Yes
protection (Beeper warning)

6 Solar Input Power 11KW

Features of Solar Controller Output

Index Remark
NO Item Min. Rate Value Max.

1. Output Voltage 250Vdc Adjust according the battery


voltage

2. Output Current 50A


Output Voltage Regulated
3. Accuracy -1.5% +1.5%
When Input Rated Voltage is
4. Effiency 97% 330Vdc,Load >60%
Solar Energy Utilization
5. Ratio 99%

6. Over-voltage Protection `264Vdc Lock

7. Over-current Protection 54A

8. Shortcircuit Protection Yes

9. Output Fuse Protection Yes Output with fuse protector


Reverse Polarity
10. Protection Yes
from the starting time to the DC
output voltage rise to the rated
11. Starting Time 3S 30S time(normal temperature test)

Operating Ambient:

NO. Item Specification Remark


1 Working temperature -5+40℃
2 Storage temperature -15+50℃
3 Relative humidity 0%90% no condensation
4 Atmospheric pressure 70106kPa
0-3,000m(If the altitude >1000M, when the
5 Elevation range altitude increases by100M, the available Power
will be decreased by 1%)
6 Storage elevation 0-15,000 Meter

Safety Requirement:

NO. Item Standard(Or test condition) Remark

1 Dielectric AC Input—Ground 2000VAC/10mA/ 1min No breakdown, flash over


strength phenomenon
DC Input—Ground 500VDC/10mA/1min
AC Output—Ground 2000VAC/10mA/ 1min

Insulation Input-Ground ≥20MΩ@500Vdc


2
resistance Output-Ground ≥20MΩ@500Vdc

3 Leakage current(input- ground) ≤20mA Input 220Vac

Other Requirement:

NO. Item Requirement Note

1 Placement
horizontal
Making the shell, the front panel, the fastening screw and
Grounding
2 the cabinet in good conductive contact.
Connection

The appearance and sensory requirements:

1、No fly line, device loosening;


2、Converter shell surface should be smooth, no impurities, no scratches, warping
degree is less than 2%;
3、Screen printing is clear to meet the safety requirements;
4、Shell color: light gray sand grain.

Process Requirements:

Neat, Firm connection, suitable length


3. Appearance

4. Product size(mm):
Product Size: 640mm×570mm×1200mm
Max. Product size: 640mm×570mm×1275mm (including wheels)
Shell Material: Iron
Shell Color: Cream-Coloured

5. Product components:
1. LCD Display 2. Air Vents
3. Control switch of Solar input 1 4.Control switch of Solar input 2
5. Control switch of battery input 6. Control switch of AC input
7. Control switch of AC output 8. Ground Wires
9. Solar Input 1 10. Solar input 2
11. Battery Input 12. AC Input
13. AC Output 14. RS485 Port
15. Cooling fan

6. Packing(720*645*1435mm)
Accessories:User’s Manual 1 set, Warranty Card 1pc, Quality Certificate 1pc
Packing material:Wooden case
Packing quantity:1pcs
Product N.W.:180Kg
Product G.W.:210Kg

7. Touch Screen Introduction


■Touch Screen Operation & Content Introduction

1. Touch Icon “SOLAR” as show below, it shows solar input voltage, solar input current,
solar output current and solar output power.

2. Touch Icon “BATTERY” as show below, it shows battery voltage, battery capacity and

discharge current.

3. Touch Icon “INPUT” as show below, it shows AC grid input voltage, AC gird input
current, and AC input frequency.
4. Touch Icon “OUTPUT” as show below, it shows inverter output voltage, output
frequency, output current, and loads’ power.

5. touch picture icon “inverter” as show bellow, it shows the inverter output voltage,

inverter output frequency, inverter temperature, and inverter bus voltage.

6. Touch picture icon “horn” on the right bottom to set the alarm or no-alarm.
7. Touch picture icon “house” on the left bottom as show bellow, there will be setting

menu.

Setting menu options as show below:

(1). touch “Operation mode”,user can set the following information.

Operation mode setting explanation:

a. Touch “AC priority Bypass”, in this mode, the inverter will have AC grid output, use AC

bypass function, not charge the battery. The inverter goes to the standby status; its

output follows with the AC grid. In this mode, if the AC grid cut off or the voltage is

beyond AC grid normal voltage, the inverter will be change to the battery inverting

mode automatically.
b. Touch “AC priority AVR”, in this mode, the inverter will automatic stabilize the AC grid

output voltage, send the power to the load and charge the battery. In this mode, if the

AC grid cut off or the voltage is beyond AC grid normal voltage, the inverter will be

change to the battery inverting mode automatically.

c. Touch ”AC priority ECO”, in this mode, the inverter will have AC grid output, use AC

bypass function to charge the battery. The inverter not working. its output follows with

the AC grid. In this mode, if the AC grid cut off or the voltage is beyond AC grid normal

voltage, the inverter will be change to the battery inverting mode automatically in 12

seconds.

d. Touch ”Solar priority ”, in this mode, the inverter will be working like this:
① when there is sufficient solar energy, and the battery voltage is relatively high. The
solar will provide power to the load directly and charge to the battery meantime.

② If the solar energy is insufficient, both the solar energy and battery will supply power
to the loads automatically.

③ When the solar energy is insufficient, the battery voltage drops to the protection
voltage, the AC grid power will automatically supply power to the load directly but not
charge for the battery, while the solar energy will charge the battery instead.

④ when the battery voltage is lower than the protection voltage, this product will switch
to AC mode intelligently: AC will supply power to loads and charge for the battery at
the same time, to ensure the service life of the battery

⑤ When there is no solar energy, the product will use AC grid supply power to the
load or battery supply power to the load automatically.

⑥ When there is no solar energy or AC grid, the product will use battery supply power to
the load automatically.

e. Touch ”On/Off Inverter”, in this mode, will be block other modes, the inverter will be

always have output, or always off working.


f. Touch ”Oil machine mode”, in this mode, the inverter check if have oil input, the oil

machine will be use AC pass function to charge the battery. The inverter not working.

its output follows with the oil machine. In this mode, if the oil machine cut off or the

voltage is beyond oil machine normal voltage, the inverter will be change to the battery

inverting mode automatically in 12 seconds.

(2). “Language” is to set the language

(3). “Communication” is to set the address code to communicate with the inverter

(4). “Event Log” is to record the inverter running status

(5). “Setting” is to set the display parameters and output parameters; the password is

“654321”

(6). ”Time setting” is to set the time.


(7). ”Infomat” is to set the system information

(8) ”Running State” is to track the running status of the inverter

(9) “Controller” is MPPT PV controller


a. User can check the “Current power generation”, “Daily Generation”, and “Total power

generation” of solar power.

b. Touch “Module 1” or “Module 2”, user can check the parameters of each module.

(10) “Alarm” is to show the fault message of the inverter.