CG-D-62-77
Randall Eberly
Merchant Marine Technical Division
0
Office of Merchant Marine Safety
U.S. Coast Guard Headquarters
Washington, DC 20590
October 1977
Final Report
•s
NOTICE
!R:.:
-ad:l/be.ý1 CCA-'23/7
16. Abstract
VkDuring the week of 19 July 1976, a full-scale fire test series was performed at
the U. S. Coast Guard Fire and Safety Test Detachment to examine the potential
fire hazards of intermodal shipping containers. The three-part test series was
conducted on Little Sand Island in Mobile Bay, Alabama. The first sequence of
tests were planned to evaluate whether a fire originating within a sealed
intermodal container could burn through the container shell. The second task
of the test series was to determine the effects of an exterior pool fire exposure
on a single level of containers, and the final task was to evaluate the effects
of an exterior pool fire exposure on a stack of containers."
(Standard 8 foot by 8 foot by 20 foot steel, aluminum and fiberglass-reinforced
plywood shipping containers were tested.
(The interior fire tests utilized two 30-pound wood cribs constructed of white
fir and 2 gallons of naptha as a fuel source. For the exterior fire tests, a
29 x 24 foot steel test pan containing JP-5 was constructed beneath the container
stack. Standard container stacking and lashing arrangements were used for all
tests.
Fern DOT F 17M-7 (1-7) Reproduction of form and -completed page is authorized
S730 J I
O 7i.. .
0.
0
--
0
- 00
U '" I i 0
010
ai ,
Im
FA ""' 111r
11
111'
111
1.r1
1.1r.1.
oil"
"1""
02 1 31 I0 ,0
6IE I2 _ I
= 0 0 0
I
ato
go.; o
N 'U W• °
ACKNOWLEDGEMENTS
This test series is one facet of an on-going research and development program
conducted by the United States Coast Guard. The ultimate mission of this
program is to implement newly developed technology and progressive engineering
techniques into the Commercial Vessel Safety Program, thereby providing an
riptimum means to insure the safety of life at sea.
0,
gITII whireto
UNIANNtOUNtlCED 13
. ....... ... ., .
JUJSTIFIC:AT153 ...
I. .........-
11LI/M
Coo.at
TABLE OF CONTENTS
Page
1.0 INTRODUCTION 1
1.1 Background 1
1.2 Purpose 2
3.0 CONTAINERS 7
4.1 Theory 10
4.2 Thermocouple Locations 10
4.3 Discussion 10
6.0 CONCLUSIONS 24
7.0 SUMMARY 25
REFERENCES 26
LIST OF ILLUSTRATIONS
Figure Page
3 Instrumentation Lead-Ins 5
v -o
Figure Page
16 Collapse of Container #5 23
LIST OF TABLES
Table Page
vi
vi.
1.0 INTRODUCTION
1.1 Background
1
1.2 Purpose
"4A:54"P-
2.0 TEST PROCEDURE
The container test series was conducted at the Coast Guard Fire and
Safety Test Detachment in Mobile, Alabama. Because gantry cranes or other
appropriate container-lifting apparatus could not be practically erected, the
tests were not conducted aboard one of the Test Detachment vessels. A gravel
test pad of approximately 3600 square feet was constructed on Little Sand
Island, adjacent to the T/V ALBERT E. WATTS. A 29 by 25 foot simulated hatch
cover was constructed on the test pad consisting of welded steel plates. Steel
coamings were also welded along the perimeter of the mock-up hatch cover to
form a ten-inch deep fuel pan for use during the pool fires. Two steel I-beams
with six-inch flanges were fitted with bottom-stacking fittings and pad eyes
(Figure 1) and centered in the fuel pan to act as a base for the container
stack.
b. External Fire Tests - JP-5 was used as a fuel source for all
external exposure tests. Several gallons of naptha were used to prime the JP-5
for easier ignition.
For the internal tests, sufficient lengths of fuse cord were run from
the naptha pan at the base of the wood crib to the exterior of the container.
The fuse cord was then manually ignited from a safe distance.
2.4 Instrumentation
The Fire and Safety Test Detachment instrumentation van was used for
this test series. To facilitate the connection of all necessary wiring and
electrical power supply circuits, the van was loaded on one of the Test Detach-
ment LCM's which was then moored on the island adjacent to the test site.
I 3
Nam
. ---
-,-.--
PAR
a II.R
Figure 3 ~~~~InsrmnainLa-n
Oxygen concentrations were measured using a thermomagnetic oxygen
analyzer with a range of 0 to 25 percent 02 ± 0.4 percent. Carbon monoxide con-
centrations were measured with a Luft-type infrared analyzer with a range of 0
to 10 percent CO + 0.2 percent. Carbon dioxide concentrations were also measured
with a Luft-type infrared analyzer with a range of 0 to 50 percent C02 + 1.0
percent. All instrumentation was fed into an analog-to-digital converter. The
output of this machine was recorded on both printed paper tape and paper punch
tape. The punch tape was used as input for a computer which plotted all data
as engineering units versus time.
r1
Vt
'i
,6 V
4 -!
3.0 CONTAINERS
All joints formed by the connection of a frame member to a panel are sealed
by caulking or a gasket to provide water tightness and corrosion resistance.
I
ro
Roof FlorBord
1. Ed FrmeFitting
* - - ~ IS
Fiberglass
Sandwich
S*FRP
ZPlywood Core
Aluminum
Sheet
S]Aluminum -
Exterior Post
Plywood Liner.
Aluminum
Sheet
GapAluminum
/ //Air -
Interior Post
Plywood Linerl--ý
IV
~ ~ 9
4.0 INTERIOR FIRE TESTS
4.1 Theory
The containers used for the interior fire tests were containers which
were removed from service because of their overall deteriorated condition; how-
ever, they were determined to be structurally adequate for these tests. Minor
defects such as broken hinges, torn door gaskets, and dented frame rails were
noted on the containers. No special repairs or sealing materials were employed
to render the containers overly airtight. In fact, because of their condition,
these containers were probably less airtight than containers in normal service.
Table 1 is a summary of data for the interior fire tests.
10
.0
CnA
U uJLL)
U UL)L U)CL) U ()U U UQ)Q
E 0 0 000 0 (0 0 00 0 0 0 00 0 000 0
d) I- to IL~OM COO
; C tn ~ c" D4Tf~ 0 OO)clic)U3
C)C
I-- CM
C3C
() (i0 0LflU
%D o.0 - - C'l4D Ln r- IL'* P- . MLO tD
WMW~ C..)Cir-r- CJC% -r - Mr -r
w Co
- ~0 C.) 0 0 Q CJCQJa\I)
Q a 0 C) C 0JC~~
C) COLA 0
0 4J 4- A.
44 4J
C-)I- hv n c
4) c
Figure 6 - Natural Venting on Steel Container
The FRP container used for Test 2 was not vented. In the test, a
weight loss of 25 pounds occurred. It is felt that warped floorboards allowed
the leakage of sufficient quantities of air to permit glowing or deep-seated
combustion of the wood crib. Additionally, it was noted that the FRP panel
joints were sealed with a caulking material which decomposed from the heat of
"the fire. The deterioration of this material may have allowed additional air
leakage. There were two noted effects of the test fire on the FRP container.
As in Test 1, a slight darkening of the ceiling occurred directly above the
wood crib, and secondly, the heat of the fire caused styrene boil-out from the
M woven roving on the container roof panel during the test.
T!hBLE 2
13
7 N
2
In a report dated April 1973,2 the Netherlands Ship Research Centre
reported on a similar test series conducted in the Netherlands. In those tests,
almost identical results to those produced in this study were obtained for a
ventilated steel container and an FRP container. In the Netherlands Ship
Research Centre tests, wood crib weight loss of approximately 12 pounds were
recorded in all cases. A second report dated November 19743 discusses the
results of tests conducted on aluminum containers. As a result of both test
series, the Netherlands Ship Research Centre concluded that, "a fire inside a
container (regardless of the cause) will not inflict very much harm on the
container in question and certainly not on adjacent containers."
I.
14
4 'g-'. '4____________________________
A
- 7
5.0 EXTERIOR FIRE TESTS
In Section 1.1 it was stated that the two credible fire scenarios
developed for intermodal container transport included exposure from an exterior
fire source, either a flammable liquid leak or possibly another source such as a
fire in the container vessel's superstructure. Tests 4 and 5 were designed to
simulate the exposure of the top level of a container stack in such a manner that
the underside of the containers would have no effect on the test results. This
was accomplished by flooding the test fuel pan with water to raise the fuel level
above the container floors. Originally, several tests of varying duration were
planned. The burning time could be regulated by the amount of fuel floated on
the water surface. Previous test experience has shown that the JP-5 will burn
off at a rate of approximately one-tenth of an inch per minute.
Since little damage was incurred in the internal fire tests, the
original three containers used for Tests 1 through 3a were stacked as shown in
Figure 8 and used for Tests 4 and 5.
15
4-
Figure 8 - Single Level Array of Containers
16
'. "Pj,
<T-
ai _ a4 0
cci 0 .0
0L
E EC.
cv
E0. E
~Iio 0
C'E Oc E
0 C a0E
Cc &. Cw
E E0
~E
ha0U. E
0 1c
.54a CI C 9
6U.
if L
CIE ~iE 18
7-;. aC C
5.4 Discussion of Tests 4, 5, and 6
19
*1
C. EC
.10
wII J
cri
~,0
EI E F:
U
I= I- V 9.N-yl o 0
<
~ C C cl Cj C enC
Lai
02
Ir-
Jr - -
t *.
4 '" 'L
k
U . '.. ;%'-x'nfl;t' .4.
1.
a - - .. -.
-- 4 4
Figure 15- Containers Held in Place
by Bridge Fittings
r24
-WAVTNMW-
7.0 SUMMARY
25
APPENDIX A
A-1
* *2' - ý .
REFERENCES
Ii
II
26
-7-
pil 77
- - ~ -
-Wood Crib
415 FWD Tree 6 ft. Ht.
FWD Tree- Coiling
FWD Tree - 4 ft. Mit.
FWD Tree- 2ft.Ht.
&332 FWD Tree -Floor Level
S249
1883
0 4 8 12 16 20 24 28 32 36
I. Elapsedl Time InMinutes
A-2
- _4ur .4
20
16
x
0
~12
*8
0 4 8 12 16 20 24 28 32 36
Elapsed Time In Minutes
A-3 L~
Interior Fire Test of Steel Container
119 July 1976 Test: 1
10
8-
4-
0 4 8 12 16 20 24 28 32 36
A.OPON0--7
;• A-4
'I w"
Interior Fire Test of Steel Container
19 July 1976 Test: 1
6
14
-I 0I .
0 4 8 12 16 20 24 28 32 36
Elapsed Time In Minutes
A-5
03
Interior Fire Test: Fiberglass Reinforced Plywood Container
19 July 1976 Test: 2
600
-Wood Crib
------------------------
FWD Tree.- Floor Level
-FWD Tree - 2ft. Ht.
5re004f. 6NF1 t
S300
100
0
0 9 18 27 38 45 54 63 72 81
Elapsed Time In Minutes
- A-6
interior Fire Teat: Fiberglass Reinforced Plywood Container
20
2
0
12
0.
8
' S
4
0 I I I
0 9 18 27 36 45 54 63 72 81
ElaPsed Tim. In Minuteb
A-7
'I
-
II
!4 36
II
C
2_
0 9 18 27 38 45 54 63 72 81
Elapsed Time In Minutes
AA-8
1!
Interior Fire Test: Fiberglass Reinforced Plywood Container
19 July 1976 Test: 2
6 I I
5-
4-
0 18 27 I36 45 54 63 72 81
Elapsed Time In Minutes
A-9
S. ..
Interior Fire Test of Aluminum Container
19 July 1976 Test: 3
582
-- Wood Crib
485 FWD Tree - Floor Level
FWD Tree. 2 ft. Ht.
FWD Tree- 6 ft. Ht.
FWD Tree - Ceiling
3118 FWD Tre - 4 ft. HIt.
291
~194
97 //
0 I I I ,, I
0 4 a 12 16 20 24 28 32 36
A-1O
T T-
Interior Fire Test of Aluminum Container
19 July 1976 Test: 3
24
20
16
x
0
o 12
0 I I I ,
S0 4 8 12 16 20 24 28 32 36
Elapsed Time In Minutes
A-11*
ENV •• u •. •.. • °. . .. •' " "' • " -••'- ;,.-• _ . '• '& ''r _••-
.•o_. • '"
Interior Fire Test of Aluminum Container
1219 July 1976 Test: 3
12I
10
I8 U
i~i.•4.
2
0 I I I IIIIII
0 4 a 12 16 20 24 28 32 36
Elapsed Time In Minutes
A-12
Yt
Interior Fire Test of Aluminum Container
619 July1978 Test: 3
5
¶
3 r
9 uy 9'6Tst -
- -- -- - - - - - -- - - - - - - - - - - - - - - - - - -
*0 4 8 12 16 20 24 *28 32 36
Elapsed Time In Minutes
A-13
-- .,-JjfN -- ---..-
,
P77 1 ! ....
600I
Wood Crib
0
0 101 I , I ... III I
0 4 $ 12 16 20 24 28 32 36
A-14
Interior Fire Test of Aluminum Container
24 19
,, July 1976 Test: 3a,
20
16
12
10
0 4 8 12 16 20 24 28 32 36
"ElapsedTime In Minutes
A-15
.. ..
. . . . . ... . ..
Interior Fire Test of Aluminum Container
19 July 1976 Test: 3a
12 , , ,
10
Io
0
6-
°1
S
a.
0 i . ,i I i ,i . I
0
0 4 8 12 16 20 24 28 32 36
A-16
Interior Fire Test of Aluminum Container
619 July 1976 Test: 3a
5-
4.
00 4 a 12 16 20 24 28 32 36
Elapsed Time In Minutes
A1
B-1
~ ~ i
Approdl.
Container Conotructlon Data - Three Level Array
Container side 4 End Pe-.le I End Free.. Front Fnd Fro Rear
e, Too
lal,
I6-tor66-T
Notton
Rete Roof Doors rloors Lining
".*od~r .06" Polyester fiber- or 6S)a62 •646 Nail .06" N/A N/A N/A
1,
1466 Vintagae
uIoneandwich-3S/"
nlwod core
Alusnm Alloy I polyastor
l.sfiberlyis
1 5/8" ply-
Wood Mors
poT .063" Al "n-o Sheet ;Htth Tensile Strength Sme 6061-S teel Stee"P la-
"-tenror Post
I
1 3/1n" Poet. on JA" Stte AiI3-H14
a1 . 'ntal 1 1/4"
1o66 violate Core. I Alloy Alo•nee fhard°ood
W/A
5
Interiorn !ontSt ren" I Shet
'3th 10010.
l"'T
riT
nI/A" & 7
6. Aluminm .051" Aluminum Shoot ih Tonsil. StrengthN/A /A .0= 1/4" plywood
Bxtorfor ot Steol Aluminum tal hardwood 48" height
1066 Vnatia
5. PR? 0.6" Polyester fibargloonAlumino. Alloy
I -
hhigh Tensile NIA N/A
Sheet
.01"
I
ply" tIN/
eaodwich-3/4" olood Stool oStrnAth
polyester Type 8;2 N/A
core. fiberglass
aantlch-
5/8" ply-
wood Mor.
6. Aluminus .063" Al~inum Sheet High Tensile Strength Sam A O" /
ply 8 N/A,
Steel 2 Al mlnr' oetal hardwood
Sheet tongue
a Too &
7.. M SEE Ifm elt OKo, -------- -----.-.---.----------.I.--------.-.-.-.-..-.-.-.-.-----
--.-------- ------.-.-..
:B-2
7
Exterior Exposure Fire Test on Containers
19 July 1976 Test: 4
366
244 I \
II
~183
S ~ I'lot
E
ij- 122
61
!0 0IO I i I I I,,
0 4 8 12 16 20 24 28 32 36
Elapsed Time In Minutes
B-3
A.Ri
two
&80 /I
6 ..
20
20
0I , I | , tI . i
0 4 8 12 16 20 24 28 32 36
"ElapsedTime In Minutes
B-4 I
l'1__-
Exterior Exposure Fire Test on Containers
19 July 1976 Test: 4
252 , ,I
126
42
0 , I I i I I
0 4 8 12 16 20 24 28 32 36
Elapsed Time In MInuies
B-5
7--5-7
Exterior Exposure Fire Test on Containers
20 July 1976 Test: 5
570
S285
,190
95
0 , p ,
0 4 8 12 16 20 24 28 32 36
-6
I4
Exterior Exposure Fire Test on Containers
20 July 1976 Test: 5
342 , ,
__228
I%%
e171 %% -
E 114 //
1-
/
57
0 4 8 12 16 20 24 28 32 36
Elapsed Time in Minutes
B-
Exterior Exposure Fire Test on Containers
20 July 1976 Test: 5
1026 ,r
6I 1
6513
I ~ IU
& I
I .. 342 U
171 I
0 4 a 12 16 20 24 28 32 36
Elapsed Time In Minutes
B-8
77I7
External Exposure Fire Test on Array of Containers
22 July 1976 Test: 6
846
Contain -I
-Container -4
705 --- ContaIner.-
& 6 I '\
JI ..-"'ý . ..
0 .,
0V I IiI , I
141/
141 10 15 20 25 30 35 40 45
B-9
External Exposure Fire Test on Array of Containers
22 July 1976 Test: 6
1.06 E + 03
4 -Container
..---- Container- 2
-5
0II LL x!t Ii
35 10 i 20 25 30 35 40 45
B-10
Elapsed Time In Minutes
External Exposure Fire Test on Array of Containers
22 July 1976 Test: 6
1.03E+03
-5 .. Container - 6
855 ------- (io.rI3
--- Container - 9
& 684
S513
/ 44 X
E / \
34
342
171
171 I IaJ I
0 5 10 15 20 25 30 35 40 45
B-1l