GE Multilin 1
SBC Static Breaker Backup
Fig. 1. SBC221A functional block diagram Fig. 2. SBC221B functional block diagram
A (+)
PROTECTED B CC1
BREAKER SW1
A ØA
C CC4
PROTECTED B SW4
3Ø
BREAKER (+) 1
2 IA
C
CC1 CC2
SW1 SW2
1 ØA ØB
2 IA
TS 1
50BF 1 2 B
OTHER 3 2 TS 50BF
CC2 A2 RELAYS O
SW2 4 IB A2
OTHER 3 ØB CURRENT A TS
RELAYS IB DETECTOR O 50BF CC3 SW3
4 50BF
A1 ØC OR
A1
CC3 TS A/O
SW3 TS
5 ØC IT 5
LEVEL A IT
6 IC 6 IC O OUT
DETECTOR
10 10
TO SURGE TO SURGE
GROUND GROUND
(+) (+)
BFI BFI BFI BFI BFI BFI BFI BFI
ØA ØB ØC 3Ø 11 13 15 19 ØA ØB ØC 3Ø
7 8 9 17 7 8 9 17
T2 T1 T3
(-) 18 (-) 18
2 www.GEindustrial.com/Multilin
SBC Static Breaker Backup
www.GEindustrial.com/Multilin 3
SBC Static Breaker Backup
technical specifications
RATINGS BURDEN
Current: (maximum) for 10 A at 60 Hz
Nominal: 5 A at 60 Hz with continuous Phase Pickup Setting Burden (VA)
capability of 10 A. 1-2 2.3
1 Sec: 210 A 2-4 1.5
DC Power Supply: Single rated, 48, 125, or 250 VDC 4-10 1.3
AMBIENT TEMPERATURES 31O Pickup Setting Burden (VA)
0.5-1 4.5
These relays have been designed for continuous operation
1-2 2.3
between -20°C and +55°C per ANSI standard C37.90. In addition,
2-50 1.6
these relays will operate within published characteristics, and not
malfunction nor be damaged if operated in an ambient up to +65°C
CURRENT DETECTOR FOR SBC200 / 53
BFT CONTACT RATINGS Dropout level: 95 percent of pickup.
3 A continuous, 30 A for tripping duty. Dropout time: Adjustable from less than 5 ms to 10 ms when
current reduced to 90 percent of pickup.
Specifications subject to change without notice.
Fig. 5 SBC223C functional block diagram Fig. 6 SBC231A functional block diagram
+DC ED6 ED4 ED2 EB2 EB4 EB6
A
PROTECTED
B
62X A T1
BREAKER 62Y
C BFI IT-3 IT-2 IT-1 BFT1 BFT1 BFT1
1 EB9 -1 -2 -3
2 IA
+IOV TP10
Power
3
IB
TS 50BF supply OV TP1 ED7 ED5 ED3 EB3 EB5 EB7
4 A2
LEVEL A
EB10
-IOV TP2
5 DETECTOR O 1 TS
50BF TP3 TP6
6 IC EA2 TP4 BFT1
A1
IA Level A TS
7
LD IA O 1
8 3IO CC
TS det. TP5 1/4~
LD EA3 TP7
10 OUT IT
EA4 PU
TO SURGE OUT IB IB Level IT
GROUND (+)
CC
det. BFT2
TS
EA5 2
EA6
(+)
1 B
O
IC IC
*J1 LOCATED ON BACKPLANE EA7 Out EC2 EC4 EC6
EXTERNAL
CONTACT EA8
11 9 11 13 15 19 3I0 3I0
1 2 3
62X 62Y BFI
EA9 T2
J1 CC T2 T1 T3 Surge EA1,EB1,EC1,ED1
IT 1
(SEAL-IN)
BFT BFT BFT ground BFT2 BFT2 BFT2
IT A1 A1 A2
17 -1 -2 -3
POWER 12 14 16 20
SUPPLY
- DC EC3 EC5 EC7
(-) 18 Note: Connect surge ground to ground bus on panel
Fig. 7 Typical external conn. and logic for SBC53A Fig. 8 Typical external conn. and logic for SBC53C
4 www.GEindustrial.com/Multilin
SBC Static Breaker Backup
Features
■ Added security is provided since
the SBC relay is not connected to
DC control until a fault occurs
and the power supply is ener-
gized by contact initiation.
■ Each relay has its own regulated
power supply with a low voltage
cut-off of approximately 60
percent and, thus, the relay will
not operate from accidental
grounding.
■ The current detector has an LED
to indicate pickup, for ease in
calibration and testing.
■ Fast reset current detectors,
which may be adjusted to less
than 5 ms.
■ The SBC200 relays have three
“BFT” contact outputs (two with
targets) and one or two “IT”
instantaneous trip contacts. The
SBC53 relays have six electroni-
cally separate “BFT” contact 5
outouts, two with targets, and
three “IT” instantaneous trip
contacts.
■ Surge suppression on all AC and
DC input circuits. All relavs will
pass the ANSl-IEEE SWC test and
the GE Fast Transient and RFI
test.
Selection Guide
19 Inch Rack 3φ + Ground
www.GEindustrial.com/Multilin 5
SBC Static Breaker Backup
Selection Guide
Drawout Case 3φ + Ground
1 Pole Freq. RatedCT Contin. DC Phase Residual BFT Inst. Trip No. Targets Functional A/O B/O Model Case Approx. Wt. in
or (Hz) Current Current Voltage Pickup Current Contacts Contacts @ 0.15A Block Timer Timer Number Size lbs (kg)
3 Pole (A) (A) (A) (31O)(A) Pickup Diagram 10-1590 ms 10-1590 ms Net Ship
SBC221A - 1 POLE, 1 TIMER(A/O), PLUS CONTACT CONVERTERS(CC) FOR PHASE SELECTION, WITH BFT & INSTANTANEOUS TRIP(IT)
1 Pole 60 5 10 38-280 1-8.5 3 N.O. 1 N.O. 3 Fig. 1 Yes No SBC221A1A M2 22 27
(0.5 A steps) (10) (12.3)
1 Pole 50 1 2 38-280 0.2-1.7 3 N.O. 1 N.O. 3 Fig. 1 Yes No SBC221A2A M2 22 27
(0.1 A steps) (10) (12.3)
1 Pole 50 5 10 38-280 1-8.5 3 N.O. 1 N.O. 3 Fig. 1 Yes No SBC221A3A M2 22 27
(0.5 A steps) (10) (12.3)
SBC221B-1POLE,2TIMERS(A/O,B/O),PLUS CONTACTCONVERTERS(CC) FORPHASESELECTION&LOGIC,WITHBFT&INSTANTANEOUSTRIP(IT)
1 Pole 60 5 10 38-280 1-8.5 3 N.O. 1 N.O. 3 Fig. 2 Yes Yes SBC221B1A M2 22 27
(0.5 A steps) (10) (12.3)
1 Pole 50 1 2 38-280 0.2-1.7 3 N.O. 1 N.O. 3 Fig. 2 Yes Yes SBC221B2A M2 22 27
(0.1 A steps) (10) (12.3)
1 Pole 50 5 10 38-280 1-8.5 3 N.O. 1 N.O. 3 Fig. 2 Yes Yes SBC221B3A M2 22 27
(0.5 A steps) (10) (12.3)
SBC223A - 3 POLE, 1 TIMER(A/O), WITH BFT AND 3 SCHEME INSTANTANEOUS TRIP(IT)
3 Pole 60 5 10 38-280 1-8.5 0.5-4.25 3 N.O. 1 N.O. 3 Fig. 3 Yes No SBC223A1A M2 22 27
(0.5 A steps) (0.25 A steps) (10) (12.3)
3 Pole 50 1 2 38-280 0.2-1.7 0.1-0.85 3 N.O. 1 N.O. 3 Fig. 3 Yes No SBC223A2A M2 22 27
(0.1 A steps) (0.05 A steps) (10) (12.3)
3 Pole 50 5 10 38-280 1-8.5 0.5-4.25 3 N.O. 1 N.O. 3 Fig. 3 Yes No SBC223A3A M2 22 27
(0.5 A steps) (0.25 A steps) (10) (12.3)
SBC223B - 3 POLE, 1 TIMER(A/O), PLUS CONTACTCONVERTER LOGIC WITH BFT AND 3 SCHEME INSTANTANEOUS TRIP(IT)
3 Pole 60 5 10 38-280 1-8.5 0.5-4.25 3 N.O. 1 N.O. 3 Fig. 4 Yes No SBC223B1A M2 22 27
(0.5 A steps) (0.25 A steps) (10) (12.3)
3 Pole 50 1 2 38-280 0.2-1.7 0.1-0.85 3 N.O. 1 N.O. 3 Fig. 4 Yes No SBC223B2A M2 22 27
(0.1 A steps) (0.05 A steps) (10) (12.3)
3 Pole 50 5 10 38-280 1-8.5 0.5-4.25 3 N.O. 1 N.O. 3 Fig. 4 Yes No SBC223B3A M2 22 27
(0.5 A steps) (0.25 A steps) (10) (12.3)
SBC231C - 3 POLE, 2 TIMERS(A/O,B/O), PLUS CONTACTCONVERTER LOGIC WITH BFT AND 3 SCHEME INSTANTANEOUS TRIP(IT)
3 Pole 60 5 10 38-280 1-8.5 0.5-4.25 3 N.O. 1 N.O. 3 Fig. 5 Yes Yes SBC223C1A M2 22 27
(0.5 A steps) (0.25 A steps) (10) (12.3)
3 Pole 50 1 2 38-280 0.2-1.7 0.1-0.85 3 N.O. 1 N.O. 3 Fig. 5 Yes Yes SBC223C2A M2 22 27
(0.1 A steps) (0.05 A steps) (10) (12.3)
3 Pole 50 5 10 38-280 1-8.5 0.5-4.25 3 N.O. 1 N.O. 3 Fig. 5 Yes Yes SBC223C3A M2 22 27
(0.5 A steps) (0.25 A steps) (10) (12.3)
1 Pole Freq. Rated CT Contin. DC Phase Residual Output No. Targets Functional Model Case Approx. Wt.
or (Hz) Current Current Voltage Pickup Current Contacts @ 0.15 A Block Number Size in lbs (kg)
3 Pole (A) (A) (A) (31O)(A) Pickup Diagram Net Ship
SBC221A - 3 INSTANTANEOUS OVERCURRENT FUNCTIONS
3 Pole 60 5 10 38-280 1-8.5 0.5-4.25 5 N.O. 2 Fig. 6 SBC231A1A M2 22 27
(0.5 A steps) (0.25 A steps) 1 N.O.or N.C. (10) (12.3)
3 Pole 50 1 2 38-280 0.2-1.7 0.1-0.85 5 N.O. 2 Fig. 6 SBC231A2A M2 22 27
(0.1 A steps) (0.05 A steps) 1 N.O.or N.C. (10) (12.3)
3 Pole 60 5 10 38-280 1-8.5 0.5-4.25 5 N.O. 2 Fig. 6 SBC231A3A M2 22 27
(0.5 A steps) (0.25 A steps) 1 N.O.or N.C. (10) (12.3)
Order online –
save time
www.GEindustrial.com/pm
6 www.GEindustrial.com/Multilin