Kalyani Steels Limited Chapter 2.5.

3
Koppal, India 2 46 47 100
BOF Steel Making Shop February 2015, Rev.2

2.5.3 Electrical Conditions Page 1

2.5.3 Electrical Conditions


confidential

Document1
Kalyani Steels Limited Chapter 2.5.3
Koppal, India 2 46 47 100
BOF Steel Making Shop February 2015, Rev.2

2.5.3 Electrical Conditions Page 2

Standards and Rules .................................................................................. 3


Ambient Conditions..................................................................................... 3
Engineering conditions for voltage levels .................................................... 4
confidential

Document1
Kalyani Steels Limited Chapter 2.5.3
Koppal, India 2 46 47 100
BOF Steel Making Shop February 2015, Rev.2

2.5.3 Electrical Conditions Page 3

Standards and Rules

The electrical and instrumentation equipment, its accessories and its application cor-
respond with the following standards and regulations:
 EN/IEC - Rules and regulations
 IS Standards and Indian Electricity Rules for local supplied equipment
 RAL – code for painting colours (the colour will be selected during Basic
Engineering)
Standards of the customer / other standards are not applied.

Ambient Conditions

Ambient Conditions*

Altitude above sea level < 1000 m


Max. ambient temperature + xx°C
Min. ambient temperature + xx°C
Relative humidity (max) xx%
Relative humidity in control rooms for 10% …85 %,
PLC / Computer, non- condensing, dust
free, air-conditioned

Ambient temperature for electrical equipment in:

Electrical room +5°C to +45° C


Electrical rooms for VVVF +5°C to +45° C
Electrical rooms for PLC and electronic +5°C to +25° C
equipment
Control rooms +20°C to +25° C
Computer rooms +20°C to +25° C
Offices (equipped with computer) +20°C to +25° C
confidential

Document1
Kalyani Steels Limited Chapter 2.5.3
Koppal, India 2 46 47 100
BOF Steel Making Shop February 2015, Rev.2

2.5.3 Electrical Conditions Page 4

Engineering conditions for voltage levels

Engineering conditions for voltage levels*


1st medium voltage level: 33 kV AC, +/- 10% (max 36 kV)
3 phase, 3 wire
50 Hz, +/- 1, 5 Hz
31.5 kA for 3s
2nd medium voltage level: 6,6 kV AC, +/- 10% (max 7.2 kV)
3 phase, 3 wire
50 Hz, +/- 1,5 Hz
40 kA for 3s
Low voltage level: 415 V AC, +/- 10%
3 phase, 4 wire
50 Hz, +/- 1,5 Hz
50 kA for 1s
Control voltage level: 240 V AC, +/- 10%
1 Phase, PE
50 Hz, +/- 1,5 Hz
and 24 V DC

Main Incoming Power Data*


Frequency 50 Hz, ± 0,5 Hz

Medium voltage, 3 ph, AC 6,6 kV, ± 5%

Low voltage level, 3 ph, AC 415 V, ± 5%

Maximum short circuit current 50 kA (min. recommended)

Network configuration grounded

For motors < 200 kW 415 V


For motors  200 kW 6,6 kV
confidential

Document1
Kalyani Steels Limited Chapter 2.5.3
Koppal, India 2 46 47 100
BOF Steel Making Shop February 2015, Rev.2

2.5.3 Electrical Conditions Page 5

Auxiliary Voltages*
Control voltage 415 V switchgear 230 V AC, 1ph
Control voltage for other power distribution sys- 230 V AC, 1ph
tems
Supply voltage for sensors, operation stations 230 V AC, 24 V DC
and devices
Analog signals 4-20 mA, potential isolated,
if not specified differently
Digital signals 24 V DC, potential isolated con-
tacts
Solenoid valves 24 V DC
Lighting 415 V / 230 V AC
Power plugs 415 V AC
AC plugs 230 V AC

* Assumptions; to be clarified further.