Beruflich Dokumente
Kultur Dokumente
BASIC STEAM
HEATING
SYSTEMS
■ One-Pipe
■ Two-Pipe
Basic Steam
Heating
Systems
WET STEAM
BOILER LOOP RISER RETURN
CONDENSATE
DRAIN
BOILER STEAM
2
Parallel Flow
Dry Return
Applications—
VENT VALVE One-Pipe
SUPPLY Systems
VALVE
DRIP CONNECTION
BOILER
WATER LINE
Down-Feed
MAIN VENT
SUPPLY
STEAM MAIN
VENT VALVE
DOWN-FEED RISER
SUPPLY
SUPPLY VALVE
RISER
VENT
Mechanical Return
VENT VALVE
SUPPLY
VALVE
F&T TRAP
“Y” STRAINER
STEAM SUPPLY MAIN
DRIP
BOILER CONNECTION
BOILER WATER LINE
“Y” STRAINER
3
Parallel Flow
Wet Return
Applications—
One-Pipe VENT VALVE
Systems SUPPLY
VALVE MAIN
VENT
WATER LINE
BOILER HARTFORD LOOP
WET RETURN
Up-Feed
VENT VALVE
SUPPLY VALVE
UP-FEED RISER
MAIN
VENT
SUPPLY MAIN
RISER DRIPPED
Counter Flow
VENT VALVE
SUPPLY
VALVE MAIN
VENT
4
Gravity
DOWN-FEED
RETURN RISER THERMOSTATIC
TRAP
5
Vacuum
Vacuum
Applications—
Two-Pipe
Systems SUPPLY VALVE
THERMOSTATIC
TRAP
STEAM SUPPLY
MAIN
PITCH 1" IN
20FEET
F&T TRAP
TO
DRAIN VACUUM
BREAKER
VACUUM CONTROL
BOILER SWITCH LINE
WATER
LINE
F & T TRAP
GATE VALVE “Y” STRAINER
CHECK VALVE
VACUUM PUMP
PITCH 1" IN
20FEET
VACUUM PUMP OPEN
EQUALIZER VENT
“Y”
STRAINER
F&T TRAP
TO DRAIN
CONTROL LINE
BOILER
WATER F & T TRAP
LINE
GATE VALVE
VACUUM BREAKER
CHECK VALVE
LIFT GATE VALVE
VACUUM PUMP FITTING “Y” STRAINER
ACCUMULATOR TANK
6
Steam Mains
Typical
Installations
Correct pitch for
45¡ horizontal supply mains
and dry returns must be
1/4" min. in 10' in the
direction of steam and
ACCEPTABLE PREFERRED condensate flow.
BRANCH
ECCENTRIC
REDUCER
RISER
RISER
MAIN
45° ELL
DRIP PIPE
DIRT
WET POCKET
RETURN
Drop riser branched from Drop riser branched Riser branched from main bottom
main top at 45° angle from main bottom and dripped into wet return
7
Steam Mains
Typical
Installations
B Constant
B 11 1⁄4° 5.126
22 1⁄2° 2.613
C
30° 2.000
45° 1.414
60° 1.155
A
To find C—
multiply A by
constant for angle B
DRY
RETURN
45¡ ELBOWS MAIN
SUPPLY MAIN
RADIATOR
BRANCH
RISER
RISER
ANCHOR
Double radiator branch from riser Pipe expansion joint for riser
8
Typical
FULL SIZE
Installations
AT
LEAST 1"
AT
LEAST
1"
PLUG FOR
CLEANOUT
OPEN
VENT
RETURN
MAIN BOILER
WATER
LINE
CONDENSATE
PUMP
BOILER RETURN
PUMP DISCHARGE HEADER
BOILER HEADER
DRIP CONNECTION—MIN 1" DIA.
EQUALIZES PRESSURE BETWEEN
SUPPLY HEADER AND THE RETURN
HEADER AT THE BOILER
9
Typical
Installations
MAIN VENT
3/4" PIPE
HIGH PRESSURE VENT
3/4" ELBOW
WET
RETURN
TRAP
DRY RETURN
Drop riser or end of main dripping into Supply main end dripping into dry return
dry return (two-pipe system) (two-pipe system)
10
Accumulator Tank—Where returns in a vacuum Flash Steam—Re-evaporation of condensate
pump heating system are below inlet connection back into steam. It occurs when condensate flows
Glossary
of vacuum pump receiver, an accumulator tank into a reduced pressure area where the
needs to be installed. Its location should be such condensate’s temperature is above boiling point
that condensate flows by gravity to accumulator, for reduced pressure. For example: if hot
and is lifted to vacuum pump receiver. condensate is discharged by a trap into a low
pressure return or into atmosphere, a certain
Boiler-Header Drip Connection—Piping percentage of water will be immediately
arrangement that drips steam header to return transformed into steam. Flash steam usually has a
header and equalizes pressure between the two. white, puffy appearance.
Check Valve—Valve that controls water flow Float and Thermostatic Trap—Stops steam flow
between pump and boiler inlet, so that water and continuously discharges condensate and air
cannot flow back from boiler to pump. accumulations into returns. Install trap far enough
Condensate—The water formed when steam from condensate pump receiver so flash steam
cools, as in a radiator or other heating unit. The does not affect the pump operation.
capacity of traps, pumps, etc., is sometimes Gate Valve—Valve that completely closes off the
expressed in lbs. of condensate they will handle flow of water out of boiler inlet valve, usually open,
per hour. To convert lbs. of condensate or steam can be closed tightly if pump needs repair or
per hour, to sq. ft., EDR, multiply by 4. servicing.
Condensate Pump—Used to return condensate Hartford Loop—Actually two loops, this system of
to the boiler where it cannot be done by gravity. piping acts as a safety device to prevent the water
Pump must be located so that condensate flows from draining out of the boiler if a leak develops in
into receiver by gravity. return piping. First loop surrounds boiler; second
Cooling Leg—A length of uninsulated pipe with is the balance of the system.
sufficient cooling surface to dissipate enough heat Heating Unit—Convectors, cast iron radiators,
so that steam condenses and the trap can open to wall-fin radiation units, and similar heating
discharge condensate from unit. devices.
Counter-Flow System—Steam and condensate Loop Riser—Vertical portion of the wet return that
flow in the opposite direction within the same brings water into the equalizer 2" below water line.
piping. Piping should be one size larger than in a
parallel-flow system to allow sufficient space for Main Vent Valve—Lets air escape from supply
free flow of steam and condensate. main quickly so steam can circulate and reach
heating units for fast warmup. Main Vent should
Differential Pressure—Difference in pressure be located at least 15" from the last fitting of the
measured between inlet and outlet of trap or supply main.
similar equipment.
Mechanical Return—Steam heating systems in
Down Feed Riser—Piping that carries steam which the height between the end of the main and
from supply main above to heating units below. the boiler water line (drip connection) is
This piping also carries condensate from heating insufficient for gravity return of condensate back to
units to the return. the boiler A condensate pump provides the
Down-Feed System—Steam system for more mechanical means for condensation return.
than one floor in which steam supply main is near No Pressure Return—Actually a dry return below
top of structure and down-feed risers carry steam the boiler water line. Condensate flows by gravity
to heating units, as well as condensate to wet through this return and enters the condensate
return. Condensate flows to boiler via the Hartford pump above the high water line of the pump’s
Loop. receiver. Air in this return is at atmospheric
Drip Connection—This section of piping, at least pressure because the receiver has an open air
18" long, is the minimum distance the end of the vent that extends above the boiler water line.
supply main must be above boiler water line for Open Air Vent—Open length of piping extending
gravity flow of condensate back to the boiler. up from the pump receiver to above the boiler
Dry Return—Return piping above the boiler water water line. The vent keeps air pressure in both the
line that carries condensate back to the boiler. pump receiver tank and the no pressure return
equal to atmospheric pressure outside the system.
Equalizer—Piping from top of boiler to maintain
pressure balance on water in boiler return Parallel-Flow System—Piping arrangement of
connection. steam system in which both steam and
condensate flow together in the same direction in
the supply main and return.
11
Glossary Pitch of Mains—Pitch is the amount of slope
given to a pipe. Correct pitch for horizontal supply
Thermostatic Steam Trap—Located at the
bottom outlet connection of the heating unit,
mains and dry returns must be 1/4" min. in 10' in thermostatic trap stops flow-out of live steam, but
the direction of steam and condensate flow. opens to drain condensate and air into the return.
Pressure Drop—Difference between steam Two-Pipe Vacuum System—An ordinary two-
pressure at top of boiler and pressure at the end pipe vacuum system uses a vacuum pump to
of the steam supply main. It is caused from friction create a subatmospheric pressure, usually
within piping and the condensing process in mains 3" to 8" Hg (Mercury), in the return piping.
and heating units. Vacuum removes air from system piping and
heating units to provide quick heating and efficient
Safety Factor—Additional static head needed to steam distribution. Condensate flows to the pump
compensate for higher pressures and greater receiver by gravity.
steam consumption during warm-up periods.
Up-Feed System—Steam system for more than
Static Head—Amount of water needed in returns one floor in which the steam supply main is in the
to build up necessary pressure to force water back basement above the boiler. Risers carry steam to
into the boiler in a gravity feed system. heating units. Condensate from each up-feed riser
Steam Boiler—A closed vessel for conversion of is dripped by gravity into wet return and then flows
water into steam. It should be equipped with via Hartford Loop to boiler. Supply main is kept
automatic controls to maintain water level and free of condensate accumulation for free flow of
sufficient safety devices for proper burning of fuel. steam.
Supply Main—Primary piping that carries steam Vacuum Pump Equalizer—Piping arrangement
from boiler to heating units, and, in a one-pipe that equalizes induced vacuum between the
system, condensate from heating units to return supply header and vacuum pump receiver.
main.
Vent Valve—Installed on a tapping at the
Supply Riser—Vertical piping that carries steam opposite end of the supply valve, float and
under pressure from boiler up to supply main. A thermostatic vent valves let air escape from the
riser carries steam up from supply main to heating heating unit under pressure, but closes against
unit. the passage of steam and condensate.