Sie sind auf Seite 1von 12

HS-901(A)

BASIC STEAM
HEATING
SYSTEMS
■ One-Pipe
■ Two-Pipe
Basic Steam
Heating
Systems

One-pipe steam heating system


In a one-pipe, gravity-flow
system, each heating unit has a
SUPPLY
single pipe connection through
HEATING
VALVE UNIT VENT which it receives steam and
VALVE
releases condensate at the
STEAM same time.
SUPPLY MAIN
All heating units and the end of
15" MAIN the supply main are sufficiently
EQUALIZER VENT
SAFETY
FACTOR
above the boiler water line so
STATIC HEAD DRIP CONNECTION that condensate flows back to
STEAM PRESSURE DROP
the boiler by gravity.
2"
WATER LINE

WET STEAM
BOILER LOOP RISER RETURN

CONDENSATE
DRAIN

1ST LOOP 2ND LOOP


HARTFORD LOOP

Two-pipe steam heating system


In a two-pipe system, steam
supply to the heating units and
HEATING UNITS
condensate return from heating
SUPPLY units are through separate pipes.
VALVE
Air accumulation in piping and
STEAM
SUPPLY MAIN THERMOSTATIC
heating units discharges from
TRAP the system through the open
PITCH 1" IN vent on the condensate pump
20 FEET
DRY RETURN receiver. Piping and heating
BOILER HEADER
DRIP CONNECTION units must be installed with
STEAM F&T proper pitch to provide gravity
OPEN VENT DIRT
TRAP POCKET
flow of all condensate to the
“Y” STRAINER
BOILER pump receiver.
WATER LINE

BOILER STEAM

GATE VALVE CONDENSATE


CHECK VALVE “Y” STRAINER
GATE VALVE
CONDENSATE PUMP

2
Parallel Flow

Dry Return
Applications—
VENT VALVE One-Pipe
SUPPLY Systems
VALVE

MAIN VENT PITCH 1 INCH IN 20FEET

DRIP CONNECTION

BOILER
WATER LINE

Down-Feed

MAIN VENT
SUPPLY
STEAM MAIN

VENT VALVE

DOWN-FEED RISER
SUPPLY
SUPPLY VALVE
RISER

VENT

BOILER WATER LINE


WET RETURN

Mechanical Return

VENT VALVE
SUPPLY
VALVE

F&T TRAP
“Y” STRAINER
STEAM SUPPLY MAIN

OPEN AIR VENT

DRIP
BOILER CONNECTION
BOILER WATER LINE

“Y” STRAINER

GATE VALVE CONDENSATE PUMP


CHECK VALVE

3
Parallel Flow

Wet Return
Applications—
One-Pipe VENT VALVE

Systems SUPPLY
VALVE MAIN
VENT

PITCH 1 INCH IN 20FEET


DRIP CONNECTION

WATER LINE
BOILER HARTFORD LOOP
WET RETURN

Up-Feed

VENT VALVE
SUPPLY VALVE

UP-FEED RISER

MAIN
VENT

SUPPLY MAIN
RISER DRIPPED

BOILER WATER LINE


DIRT POCKET
WET RETURN

Counter Flow

VENT VALVE
SUPPLY
VALVE MAIN
VENT

DRIP CONNECTION PITCH 1 INCH IN 10 FEET

BOILER WATER LINE


MAXIMUM MAIN LENGTH 100 FEET

4
Gravity

Down-Feed with Condensate Pump


Applications—
Two-Pipe
STEAM SUPPLY MAIN Systems
PITCH 1" IN SUPPLY
20 FEET DOWN-FEED
SUPPLY RISER VALVE

DOWN-FEED
RETURN RISER THERMOSTATIC
TRAP

OPEN VENT “Y” STRAINER “Y”


STRAINER
F&T
BOILER TRAP
WATER
LINE

GATE VALVE “Y” STRAINER


CHECK VALVE
CONDENSATE PUMP

Up-Feed with Condensate Pump

5
Vacuum

Vacuum
Applications—
Two-Pipe
Systems SUPPLY VALVE
THERMOSTATIC
TRAP
STEAM SUPPLY
MAIN

PITCH 1" IN
20FEET

VACUUM OPEN VENT


“Y”
PUMP STRAINER
EQUALIZER

F&T TRAP
TO
DRAIN VACUUM
BREAKER
VACUUM CONTROL
BOILER SWITCH LINE
WATER
LINE
F & T TRAP
GATE VALVE “Y” STRAINER
CHECK VALVE
VACUUM PUMP

Vacuum with Accumulator Tank

SUPPLY VALVE THERMOSTATIC TRAP


STEAM SUPPLY
MAIN

PITCH 1" IN
20FEET
VACUUM PUMP OPEN
EQUALIZER VENT
“Y”
STRAINER

F&T TRAP
TO DRAIN

CONTROL LINE
BOILER
WATER F & T TRAP
LINE

GATE VALVE
VACUUM BREAKER
CHECK VALVE
LIFT GATE VALVE
VACUUM PUMP FITTING “Y” STRAINER

ACCUMULATOR TANK

6
Steam Mains
Typical
Installations
Correct pitch for
45¡ horizontal supply mains
and dry returns must be
1/4" min. in 10' in the
direction of steam and
ACCEPTABLE PREFERRED condensate flow.

Branching from main Arrows indicate direction


of pipe pitch.

BRANCH

ECCENTRIC
REDUCER

Reducing size of main

RISER

RISER

MAIN

Upfeed branch from main at 45° angle

45° ELL

DRIP PIPE
DIRT
WET POCKET
RETURN

Drop riser branched from Drop riser branched Riser branched from main bottom
main top at 45° angle from main bottom and dripped into wet return

7
Steam Mains
Typical
Installations
B Constant
B 11 1⁄4° 5.126
22 1⁄2° 2.613

C
30° 2.000
45° 1.414
60° 1.155
A

To find C—
multiply A by
constant for angle B

Offset pipe calculation table

RETURN RISER SUPPLY RISER


HORIZONTAL
BRANCH PIPES

DRY
RETURN
45¡ ELBOWS MAIN

SUPPLY MAIN

Upfeed riser connections


(two-pipe system)

RADIATOR
BRANCH

RISER
RISER

ANCHOR

Double radiator branch from riser Pipe expansion joint for riser

8
Typical
FULL SIZE
Installations
AT
LEAST 1"

Looping steam main around an obstruction

AT
LEAST
1"

PLUG FOR
CLEANOUT

Looping dry return around door


(two-pipe systems)

STEAM SUPPLY MAIN STEAM


SUPPLY
HEADER

OPEN
VENT
RETURN
MAIN BOILER
WATER
LINE

CONDENSATE
PUMP
BOILER RETURN
PUMP DISCHARGE HEADER
BOILER HEADER
DRIP CONNECTION—MIN 1" DIA.
EQUALIZES PRESSURE BETWEEN
SUPPLY HEADER AND THE RETURN
HEADER AT THE BOILER

Boiler piping to main

9
Typical
Installations

MAIN VENT

3/4" PIPE
HIGH PRESSURE VENT

3/4" ELBOW

SUPPLY 15" MIN.


18" MINIMUM
MAIN
BOILER WATER LINE
REDUCER

WET
RETURN

Main vent Main and high pressure air valve


(one-pipe system) (one-pipe system)

DROP RISER OR END OF MAIN

MINIMUM COOLING LEGS 5'0" LONG


SAME SIZE AS TRAP

TRAP

DRY RETURN

Drop riser or end of main dripping into Supply main end dripping into dry return
dry return (two-pipe system) (two-pipe system)

10
Accumulator Tank—Where returns in a vacuum Flash Steam—Re-evaporation of condensate
pump heating system are below inlet connection back into steam. It occurs when condensate flows
Glossary
of vacuum pump receiver, an accumulator tank into a reduced pressure area where the
needs to be installed. Its location should be such condensate’s temperature is above boiling point
that condensate flows by gravity to accumulator, for reduced pressure. For example: if hot
and is lifted to vacuum pump receiver. condensate is discharged by a trap into a low
pressure return or into atmosphere, a certain
Boiler-Header Drip Connection—Piping percentage of water will be immediately
arrangement that drips steam header to return transformed into steam. Flash steam usually has a
header and equalizes pressure between the two. white, puffy appearance.
Check Valve—Valve that controls water flow Float and Thermostatic Trap—Stops steam flow
between pump and boiler inlet, so that water and continuously discharges condensate and air
cannot flow back from boiler to pump. accumulations into returns. Install trap far enough
Condensate—The water formed when steam from condensate pump receiver so flash steam
cools, as in a radiator or other heating unit. The does not affect the pump operation.
capacity of traps, pumps, etc., is sometimes Gate Valve—Valve that completely closes off the
expressed in lbs. of condensate they will handle flow of water out of boiler inlet valve, usually open,
per hour. To convert lbs. of condensate or steam can be closed tightly if pump needs repair or
per hour, to sq. ft., EDR, multiply by 4. servicing.
Condensate Pump—Used to return condensate Hartford Loop—Actually two loops, this system of
to the boiler where it cannot be done by gravity. piping acts as a safety device to prevent the water
Pump must be located so that condensate flows from draining out of the boiler if a leak develops in
into receiver by gravity. return piping. First loop surrounds boiler; second
Cooling Leg—A length of uninsulated pipe with is the balance of the system.
sufficient cooling surface to dissipate enough heat Heating Unit—Convectors, cast iron radiators,
so that steam condenses and the trap can open to wall-fin radiation units, and similar heating
discharge condensate from unit. devices.
Counter-Flow System—Steam and condensate Loop Riser—Vertical portion of the wet return that
flow in the opposite direction within the same brings water into the equalizer 2" below water line.
piping. Piping should be one size larger than in a
parallel-flow system to allow sufficient space for Main Vent Valve—Lets air escape from supply
free flow of steam and condensate. main quickly so steam can circulate and reach
heating units for fast warmup. Main Vent should
Differential Pressure—Difference in pressure be located at least 15" from the last fitting of the
measured between inlet and outlet of trap or supply main.
similar equipment.
Mechanical Return—Steam heating systems in
Down Feed Riser—Piping that carries steam which the height between the end of the main and
from supply main above to heating units below. the boiler water line (drip connection) is
This piping also carries condensate from heating insufficient for gravity return of condensate back to
units to the return. the boiler A condensate pump provides the
Down-Feed System—Steam system for more mechanical means for condensation return.
than one floor in which steam supply main is near No Pressure Return—Actually a dry return below
top of structure and down-feed risers carry steam the boiler water line. Condensate flows by gravity
to heating units, as well as condensate to wet through this return and enters the condensate
return. Condensate flows to boiler via the Hartford pump above the high water line of the pump’s
Loop. receiver. Air in this return is at atmospheric
Drip Connection—This section of piping, at least pressure because the receiver has an open air
18" long, is the minimum distance the end of the vent that extends above the boiler water line.
supply main must be above boiler water line for Open Air Vent—Open length of piping extending
gravity flow of condensate back to the boiler. up from the pump receiver to above the boiler
Dry Return—Return piping above the boiler water water line. The vent keeps air pressure in both the
line that carries condensate back to the boiler. pump receiver tank and the no pressure return
equal to atmospheric pressure outside the system.
Equalizer—Piping from top of boiler to maintain
pressure balance on water in boiler return Parallel-Flow System—Piping arrangement of
connection. steam system in which both steam and
condensate flow together in the same direction in
the supply main and return.

11
Glossary Pitch of Mains—Pitch is the amount of slope
given to a pipe. Correct pitch for horizontal supply
Thermostatic Steam Trap—Located at the
bottom outlet connection of the heating unit,
mains and dry returns must be 1/4" min. in 10' in thermostatic trap stops flow-out of live steam, but
the direction of steam and condensate flow. opens to drain condensate and air into the return.
Pressure Drop—Difference between steam Two-Pipe Vacuum System—An ordinary two-
pressure at top of boiler and pressure at the end pipe vacuum system uses a vacuum pump to
of the steam supply main. It is caused from friction create a subatmospheric pressure, usually
within piping and the condensing process in mains 3" to 8" Hg (Mercury), in the return piping.
and heating units. Vacuum removes air from system piping and
heating units to provide quick heating and efficient
Safety Factor—Additional static head needed to steam distribution. Condensate flows to the pump
compensate for higher pressures and greater receiver by gravity.
steam consumption during warm-up periods.
Up-Feed System—Steam system for more than
Static Head—Amount of water needed in returns one floor in which the steam supply main is in the
to build up necessary pressure to force water back basement above the boiler. Risers carry steam to
into the boiler in a gravity feed system. heating units. Condensate from each up-feed riser
Steam Boiler—A closed vessel for conversion of is dripped by gravity into wet return and then flows
water into steam. It should be equipped with via Hartford Loop to boiler. Supply main is kept
automatic controls to maintain water level and free of condensate accumulation for free flow of
sufficient safety devices for proper burning of fuel. steam.

Square Foot of Heating Surface—Equivalent Vacuum System—A closed heating system in


Direct Radiation (EDR) the amount of heating which a partial vacuum is induced when the
surface which will give off 240 Btu per hour when heating units and the main cool below the boiling
filled with steam at 215°F and surrounded by air at point of water at atmospheric pressure. Pressures
70°F. (Equivalent square foot of heating surface in a vacuum system range from below
may have no direct relation to the actual surface atmospheric pressure to a higher pre-determined
area.) pressure. Space heating is more even, and boiler
water temperatures are usually lower; heating is
Strainer—Used to protect valve pins, seats, and more economical. Vacuum vent valves and
other parts from dirt and foreign matter. vacuum main vents must be used.

Supply Main—Primary piping that carries steam Vacuum Pump Equalizer—Piping arrangement
from boiler to heating units, and, in a one-pipe that equalizes induced vacuum between the
system, condensate from heating units to return supply header and vacuum pump receiver.
main.
Vent Valve—Installed on a tapping at the
Supply Riser—Vertical piping that carries steam opposite end of the supply valve, float and
under pressure from boiler up to supply main. A thermostatic vent valves let air escape from the
riser carries steam up from supply main to heating heating unit under pressure, but closes against
unit. the passage of steam and condensate.

Supply Valve— Water Hammer—A wave transmitted through a


One-Pipe System—Located at the bottom of pipe filled, or partially filled, with water. It may
heating unit’s inlet connection. Supply Valve originate as waves set up by steam passing at a
controls admission of steam, and flow out of high velocity over condensate collected in piping.
condensate. In a one-pipe system, the supply It is one of the main causes of noise in steam
valve should be fully open or closed tightly, since a heating systems and is the cause of much
partially open valve obstructs free flow of steam in damage to thermostats and floats in traps.
and condensate out.
Wet Return—Portion of the return which is below
Two-Pipe System—Modulating-type supply the boiler water line and filled with water (does not
valves—either spring packed or packless— carry air or steam).
admit steam to the heating unit through its top
inlet connection. Selection depends upon
construction requirements and system pressures.

3500 N. Spaulding Avenue


Chicago, Illinois 60618
tel: 773 267-1600
fax: 773 267-0991
www.hoffmanspecialty.com

©1999 ITT Industries


Printed in U.S.A. 1-99 HS-901(A)

Das könnte Ihnen auch gefallen