Sie sind auf Seite 1von 7

THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS 87-GT-103

345 E. 47 St., New York, N.Y. 10017


The Society shall not be responsible for statements or opinions advanced in papers or in dis-
cussion at meetings of the Society or of its Divisions or Sections, or printed in its publications.
Discussion is printed only if the paper is published in an ASME Journal. Papers are available
from ASME for fifteen months after the meeting.
Printed in USA.
Copyright © 1987 by ASME

Fire Detection and Suppression in Natural Gas Pipeline


Compressor Stations
COLTON W. MEYER, P.E.
Pacific Gas Transmission Company

Presented at the Gas Turbine Conference and Exhibition, Anaheim, California — May 31-June 4, 1987

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/ on 06/29/2018 Terms of Use: http://www.asme.org/about-asme/terms-of-use


ABSTRACT stations, most of these are small volunteer
fire departments and are often not trained
The occurrence of fires in natural gas for or accustomed to fighting gas or oil
compressor stations is fortunately in- fires. The company policy has been not to
frequent. The consequences, however, can be call in the fire department until company
severe. This paper will discuss the design personnel are on the scene and have assured
concepts and experience of Pacific Gas that the station has shut down properly and
Transmission Company (PGT) with fire detec- the gas piping has been depressurized.
tion and suppression systems in its natural
gas pipeline compressor stations.
FIRES

INTRODUCTION The two major causes of fires in compressor


stations are failures of the gas piping
The occurrence of fires in natural gas systems and failures of the lubricating and
compressor stations is fortunately in- seal oil systems on the compressor units.
frequent. The consequences, however, could Gas fires are potentially the most catas-
be severe, ranging from damage or destruction trophic and can normally be contained only by
of equipment to loss of an entire station and cutting off the supply of gas. Oil fires, on
even loss of lives. For this reason, the the other hand, are normally confined to a
prevention, detection and suppression of limited area and can often be extinguished by
fires are important considerations in the chemical, foam or inert gas fire suppression
design and operation of compressor stations. systems. PGT has experienced two major
fires. Both were oil fires on gas turbine
This paper will focus on Pacific Gas driven compressor units.
Transmission Company's design concepts and
experience with fire detection and suppres- On Sunday evening, October 3, 1976, a lube
sion systems. The prevention of fires, oil fire occurred at PGT's compressor station
through good design and operating practices, near Sandpoint, Idaho. At 8:47 p.m., station
is of primary importance but is not the and unit emergency shutdown alarms were
primary thrust of this paper. received at the Spokane Gas Control Center.
The station was unattended at the time.
The PGT system includes 12 pipeline com- Between 9:15 and 9:25 p.m. the first company
pressor stations with a total of 23 gas employees arrived at the station to find the
turbine powered compressor units, all located "B" unit engulfed in flames. The other unit
in the Pacific Northwest. Four stations have at the station, housed in a separate build-
two units in a single building. The re- ing, was not affected. After the second
maining stations have separate buildings for employee arrived, the two men tried
each unit. The stations are all remotely unsuccessfully to extinguish the fire using
controlled via telemetry and operated from 150-pound dry chemical extinguishers. No
the Spokane, Washington Gas Control Center fire suppression system was installed on this
and are normally unattended. Some of them unit. The local volunteer fire department
are located as much as two hours driving time truck arrived at 9:40 p.m. and the fire was
from the nearest maintenance base. ultimately extinguished at 9:55 p.m. by a
company employee using a water hose from the
While there are local fire departments often fire truck.
within 10 to 15 minutes driving time of the

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/ on 06/29/2018 Terms of Use: http://www.asme.org/about-asme/terms-of-use


On the positive side, the station emergency mechanic were called out. They reported to
shutdown system functioned properly. The the maintenance base at Wallula, Washington
unit was stopped and the station piping and departed for the Ione Compressor Station
isolated from the main line and depressur- (approximately 85 miles away) at approxi-
ized. mately 6:45 a.m.. The first report by a
neighbor of smoke coming from the compressor
A post-mortem investigation found that the station was received at 8:15 a.m.. The crew
fire, which caused extensive damage to the arrived at the station at 9:05 a.m. to find
gas turbine, related equipment and building, a fire burning on the "B" unit. After
was caused by an interaction of two separate verifying that the station emergency shutdown
problems. The outboard thrust bearing seal system had functioned properly and all gas
on the gas compressor failed, allowing was evacuated, they attempted to extinguish
excessive lubricating oil to flow into the the fire using 150-pound dry chemical and 30-
drain cavity between the thrust bearing and pound CO2 fire extinguishers. They were
the outboard journal bearing. This over- successful in extinguishing the flames but
loaded the drain line, causing a positive unable to prevent a flashback.
pressure of several pounds per square inch in
the drain cavity, which normally operates at The Ione Volunteer Fire Department was
a slightly negative pressure. An improperly summoned and arrived at the station shortly
tightened 3/4 inch pipe plug had backed out, after 10:00 a.m.. The fire was then extin-
allowing a stream of oil to escape. This oil guished by company personnel using the Fire
was ignited by contact with the exposed hot Department's CO2 extinguishers. A water hose
parts in the vicinity of the turbine bearing in the compressor building was used to cool
and on the exhaust duct, which operate at the metal to prevent a flashback.
800° to 1000°F. The flash point of the
mineral oil was in the range of 600° to The cause of the fire was determined to be a
750°F. A portion of the burning oil then crack in the threads of a half inch pipe
flowed under the axial air compressor and nipple in a gauge tap on the lube oil pump
combustion sections of the turbine. The fire discharge line. The oil spraying from the
in this area caused most of the damage. crack was ignited by striking exposed hot
surfaces on the load side of the turbine.
The turbine, a General Electric Frame 3, was The foam fire suppression system, which had
removed and shipped to the G.E. repair been installed at Ione after the Sandpoint,
facility in Salt Lake City on October 21, Idaho, fire, had activated. It was the
1976. It was received back at the station on significant factor in confining the fire to
December 13, 1976 and returned to service on the area between the power turbine and the
February 3, 1977, four months after the gas compressor of the "B" unit. The "A"
fire. unit, which was in the same building, was not
damaged. There was, however, major damage to
The second major fire on the PGT system the lighting and other systems in the build-
occurred on the morning of Tuesday, December ing.
18, 1984, at a compressor station near Ione,
The damaged unit, an Ingersoll-Rand GT51
Oregon. At about 5:15 a.m., a shutdown/ power turbine with a G.E. LM 1500 gas genera-
lockout alarm on the "B" unit was received by tor driving an Ingersoll-Rand compressor, was
the Gas Control Center in Spokane. As no installed in 1969 and had logged over 90,000
personnel were on site, a technician and a hours of operation. A preliminary assessment

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/ on 06/29/2018 Terms of Use: http://www.asme.org/about-asme/terms-of-use


indicated that replacement would be prefera- o Smoke Detectors, including
ble to repair. PGT awarded a contract for a
replacement unit based on competitive bids in Photoelectric
early March 1985. The new unit was placed in Ionization
service on November 26, 1985, eleven months
after the fire. o Flame Detectors, including

The lessons learned from these two fires have Infra-red


influenced PGT's design concepts and policies Ultra-violet
regarding fire detection and suppression.
One obvious conclusion has been that there is Regardless of the type of system, reliability
a significant risk of fire resulting from is of great importance. In PGT's experience,
failures in the lube and seal oil systems on false operation has been a major concern.
pipeline compressor units. Unnecessary shutdowns of equipment can in-
crease operating costs and disrupt through-
put. Station piping blowdowns are wasteful
FIRE DETECTION of gas. False operations of fire suppression
systems are costly and in some cases can
Fire detection can take a number of forms, leave a mess to be cleaned up. In our search
starting of course with merely the visual for the ideal system, PGT has tried different
observation of smoke and flame. Because this types of fire detection systems. We give
requires the presence of an observer, it them mixed reviews.
won't work when a station is unattended.
Most operators prefer something more sophis- Our original installations used high temper-
ticated and utilize automatic systems at ature fusible link or bimetallic detectors.
unattended locations. Typical functions of While quite simple, they had the disadvantage
these fire detection systems in pipeline that they would trip under high ambient
compressor stations include initiation of temperature conditions, particularly if the
alarms, shutdown of equipment, blowdown of unit was running. Turbine bleed valve opera-
gas piping systems and operation of fire tion would sometimes trip the detectors. To
suppression systems. PGT also uses the fire avoid false operation it was necessary to set
detection system to shut down the building the detectors to operate well above maximum
ventilation system to reduce the air avail- normal temperatures. The frequency of false
able to the fire. fire detection was at the annoyance level,
but the costs were not major as we did not at
Some of the common types of detectors are: that time have fire suppression systems
installed on any of our units.
o Heat Detectors, including
After the fire at the Sandpoint Compressor
High temperature, fusible link Station in 1976, we installed fire suppres-
or bimetallic strip sion systems on certain units, specifically
High temperature, pneumatic those where two units were in a single build-
tube ing. Due to our lack of confidence in the
Rate of temperature rise fire detectors, and in order to avoid the
Combination high temperature cleanup and recharging cost of false opera-
and rate of rise tions, we tied the operation of the fire

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/ on 06/29/2018 Terms of Use: http://www.asme.org/about-asme/terms-of-use


suppression systems to fire detection in but had elected not to install them. After
conjunction with a low lube oil level alarm. the fire, the subject was reopened. The
We also changed the set points for the low potential benefits of installing fire
lube oil level alarm and shutdown so that suppression systems were thought to include:
they would trip with less oil loss than was
previously the case. We took this approach o Reduced risk to personnel
due to our belief that the most likely cause (primarily from fighting fires)
of fire was from oil system problems, and o Minimized fire damage and reduced
that in a major fire enough oil would be downtime
dumped (three to four barrels) to trip the o Minimized loss of system throughput
low lube oil level alarm. We were not capacity
terribly comfortable with this solution; o Reduced financial loss from fire
however, it was expedient and was likely to damage and business interruption
satisfy our primary concern of not losing
both units at a station in a single fire. We The potential costs or problems included:
also began looking at alternative fire detec-
tion systems. o Cost to install, maintain and
operate the systems
Our next move was to install ultra-violet o Potential for false operation
detectors at those locations where we had o Depending upon the type of system,
installed fire suppression systems. These risk to personnel or equipment
were found to be a substantial improvement.
While ultra-violet detectors are susceptible Due to PGT's insurance coverage and its cost
to being set off by, among other things, of service tariff, there was no significant
welding and lightning, this has not been a economic benefit from installing fire
serious problem if care is taken. We have suppression systems. For PGT, the primary
found, however, as a plus, that they will consideration in doing so was to assure the
detect a spark plug or cross fire tube blow- ability to maintain service to our customers
out and will shutdown the unit. without interruption.

We have recently installed both infra-red and The design of the PGT pipeline system is such
pneumatic tube detectors at two stations and that the loss of a single unit will have only
plan to do so this year at three more. a minor effect on system capacity as long as
Existing systems (high temperature and ultra- the other nearby units remain available for
violet) will be left in operation. The operation. Loss of both units at a two unit
operating performance of each of these fire station, however, can be a serious concern.
detection systems will be evaluated for For this reason, PGT concluded that fire
reliability and effectiveness for possible suppression systems were warranted at those
installation at other stations in addition to stations where both units were contained in a
the high temperature and ultra-violet single building such that a major fire could
systems. damage or destroy both units. The decision
was made, therefore, to install fire suppres-
sion systems at the four stations with two-
FIRE SUPPRESSION unit buildings.

PGT had considered the installation of fire The types of fire suppression systems which
suppression systems prior to the 1976 fire were considered included CO2, Halon, dry

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/ on 06/29/2018 Terms of Use: http://www.asme.org/about-asme/terms-of-use


chemical, water and foam. CO2 and Halon were the Spokane Gas Control Center. Due to SCADA
rejected due to the large volume required. limitations which have since been eliminated,
As none of PGT's units have enclosures, the a fire alarm was previously lumped with other
entire building would have to be filled. CO2 alarms requiring immediate dispatch of
was also rejected due to personnel hazard. personnel to the station. The gas control
Dry chemical systems were rejected as they do operator in Spokane therefore only knew that
not have a lasting effect. Re-ignition could there was a problem, not that there was a
occur requiring subsequent repeated opera- fire. Now, the operator can distinguish a
tion. There is also a clean-up problem, as fire from other alarms. The other change is
the residue can "cook on" to a hot unit. in the activation of the fire suppression
Water was considered undesirable due to the systems. Having installed multiple types of
potential for damage to hot equipment by fire detectors at those stations with fire
causing warpage. The system selected was an suppression systems, the fire suppression is
Aqueous Film Forming Foam (AFFF). now activated by the operation of any two
different fire detection systems. The low
A prototype system was installed in 1979 at lube oil level alarm has been eliminated from
the Rosalia, Washington Compressor Station. this logic.
While this system met most design require-
ments, it was found that the premixed foam PGT considers multiple redundant fire detec-
was unstable and did not have a reasonable tion systems to be cheap insurance in that
"shelf life." The system was therefore they increase the chance of early detection
modified to store water and the foam concen- of a fire. The voting system reduces the
trate separately for mixing at time of use. probability of false fire suppression system
AFFF systems were then installed in the operation.
remaining stations with two-unit buildings.
Another action taken following the recent
The 1984 fire, defying all expectations, fire was to make a complete review of the
occurred at one of the four stations with a fire suppression system design for compliance
fire suppression system installed. The with the latest National Fire Protection
functioning of the system was a qualified Association codes and standards.
success. There was no ignition of pooled oil
under the unit, the major cause of damage in
the 1976 fire. There was also no significant FUTURE CONSIDERATIONS
damage to the other unit in the building.
The location of the fire was confined to the PGT does not have any definite program to
area between the power turbine and the install fire suppression systems on all our
compressor, above the level protected by the compressor units, although we have recently
foam. Damage in this area, however, was installed a system in conjunction with a
major as was the damage to building systems. turbine replacement at one station. We are
continuing to consider other ways of reducing
fire risk and improving our fire detection
RECENT ACTIONS and suppression systems. Possible ideas
include the following:
As a result of the most recent fire experi-
ence, we have made two changes in our control o PGT has avoided spraying foam onto
system with regard to fire detection. The the hot parts of the turbine to
first is to have a fire alarm telemetered to avoid the risk of warpage damage.

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/ on 06/29/2018 Terms of Use: http://www.asme.org/about-asme/terms-of-use


This is being reconsidered. Had operation of the lube oil pumps
the foam nozzles been directed at during the cool-down period. While
the ignition sources, the fire possibly protecting the shaft, this
damage could have been minimized. has the disadvantage of continuing
While there may have been some to feed oil to the fire. We are
warpage, it would probably have considering shutting down the pumps
been repairable and would have been to cut off the oil flow, even if it
more than offset by the reduced means sacrificing the shaft. This
fire damage. would also be tied into our voting
logic with multiple fire detection
o One way to reduce the risk of fire systems to avoid losing a shaft on
is to reduce or eliminate the a false alarm.
sources of oil to fuel the fire.
PGT plans to install dry seals in
its compressors in conjunction with SUMMARY
turbine replacements, thus elimi-
nating the high pressure seal oil Based on PGT's experience, we believe that
systems. The first dry seal was there is a significant risk of lube oil fires
installed in 1986. We are also on compressor units; however, the extent of
considering the use of magnetic the damage from fires can be significantly
bearings. reduced by properly designed fire suppression
systems. Effective operation of the fire
o PGT currently uses mineral oil for suppression systems is dependent in turn upon
the compressor lube and seal oil reliable fire detection systems which must be
systems. Fire resistant synthetic designed to minimize false operation. PGT's
oils are available which have flash solution has been to install redundant fire
temperatures in the order of detection systems and to require two inde-
1150°F, thus considerably reducing pendent systems to detect a fire before the
the chance of ignition. While suppression system is actuated.
these are used in the separate gas
generator lube oil systems of Fire suppression systems are not warranted
aircraft derivitive units, PGT has for all applications. Factors to consider
not used these fire resistant oils include whether the station is attended or
for compressor lube and seal oil not, economics, and the affect of the unit
systems due to their potential loss on the system operation. I hope, how-
deleterious affect on seals, ever, that PGT's experience may provide some
gaskets and diaphragms in the food for thought.
downstream gas systems if oil is
lost into the line. If the
compressors are converted to dry ACKNOWLEDGMENTS
seals, this would not be a problem.
Fire resistant oils could then be In writing this paper I have drawn greatly
used for the gas turbine lubricat- upon the knowledge and experience of various
ing systems. members of the PGT staff, including but not
limited to Thomas J. Cusworth, John S.
o Even in the event of a unit shut- Dughman, John G. Lisk, Douglas E. Tuck,
down due to a fire, we follow the Alfredo W. Visitacion and Hiro Yamada.
manufacturer's recommendations for

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/ on 06/29/2018 Terms of Use: http://www.asme.org/about-asme/terms-of-use

Das könnte Ihnen auch gefallen