Beruflich Dokumente
Kultur Dokumente
5
Please note that the data given here has been taken from the online catalog. For comprehensive information and
data, please refer to the user documentation at http://www.download.phoenixcontact.com. The General Terms
and Conditions of Use apply to Internet downloads.
EAN 4017918890858
Pack 1 Pcs.
Customs tariff 85363030
Weight/Piece 0,3199 KG
Catalog page information Page 17 (TT-2005)
Product notes
WEEE/RoHS-compliant since: 07/17/2009
Technical data
Standards
Housing material PA
Inflammability class acc. to UL 94 V0
Color black
Degree of protection IP20
Mounting type DIN rail 35 mm
Design Rail-mountable module, one-piece
Ambient temperature (operation) -40 °C ... 85 °C
Direction of action N-PE
Protective circuit
IEC category I
EN type T1
Nominal voltage U N
230 V AC (N-PE)
Arrester rated voltage Uc (N-PE) 260 V AC
Nominal frequency f N
50 Hz
Nominal frequency f N
60 Hz
Discharge current to PE at U C
≤ 20 µA
Operating current I at U C N
≤ 20 µA
Nominal discharge surge current In (8/20) µs 100 kA
Lightning test current (10/350) µs, charge 50 As
Lightning test current (10/350) µs, specific energy 2500.00 kJ/Ω
Lightning test current (10/350) µs, peak value limp 100 kA
Protection level Up ≤ 1.5 kV
Response time ≤ 100 ns
Required maximum backup fuse with branch wiring 125 A (gL)
Short circuit resistance I with max. backup fuse
CC
25 kA
(effective)
Short circuit current self-quenching 100 A (260 V)
Environmental conditions
Standards/regulations IEC 61643-1
Standards/regulations prEN 61643-1
Standards/regulations E DIN VDE 0675-6/A1
Standards/regulations E DIN VDE 0675-6/A2
Drawings
Circuit diagram
Address
Type 1 / Class I / B arrester (lightning current arrester) with arc chopping spark gap and ignition electronics,
quenching plates for high mains follow-through current quenching capacity, 1-channel. Protection level: 0.9
kV. Housing width: 35 mm (2 Div.)
GTIN
Technical data
Dimensions
Height 149.8 mm
Width 35.5 mm
Depth 80.5 mm
Horizontal pitch 2 Div.
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 85 °C
Permissible humidity (operation) ≤ 95 %
General
Housing material PBT/PA-F
Inflammability class according to UL 94 V0
Color black
Standards for air and creepage distances VDE 0110-1
IEC 60664-1
VDE 0675-6
NF C61-740
04/02/2014 Page 1 / 7
https://www.phoenixcontact.com/in/products/2818643
Protective circuit
IEC test classification I
T1
EN type T1
Nominal voltage UN 240 V AC
230 V AC ... 277 V AC
Maximum continuous operating voltage UC 335 V AC
Maximum continuous operating voltage UC (L-N) 335 V AC
Maximum continuous operating voltage UC (L-PEN) 335 V AC
Nominal frequency fN 50 Hz
60 Hz
Residual current IPE ≤ 0.1 mA
Operating effective current IC at UN ≤ 0.1 mA
Standby power consumption PC ≤ 35 mW
Nominal discharge current In (8/20) µs 50 kA
Nominal discharge current In (8/20) µs (L-N) 50 kA
Nominal discharge current In (8/20) µs (L-PEN) 50 kA
Impulse discharge current (10/350) µs, charge 25 As
Impulse discharge current (10/350) µs, specific energy 625.00 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp 50 kA
Voltage protection level Up ≤ 0.9 kV
Voltage protection level Up (L-N) ≤ 0.9 kV
Voltage protection level Up (L-PEN) ≤ 0.9 kV
Response time ≤ 100 ns
Response time (L-N) ≤ 100 ns
Response time (L-PEN) ≤ 100 ns
Max. required backup fuse with branch wiring 250 A (gL)
Short-circuit resistance IP with max. backup fuse (effective) 50 kA
Short-circuit current self-quenching 50 kA (400 V)
Follow current quenching capacity If (L-N) 50 kA
Follow current quenching capacity If (L-PEN) 50 kA
04/02/2014 Page 2 / 7
https://www.phoenixcontact.com/in/products/2818643
Classifications
eCl@ss
ETIM
UNSPSC
04/02/2014 Page 3 / 7
https://www.phoenixcontact.com/in/products/2818643
Approvals
GOST
Ex Approvals
Approvals submitted
Approval details
GOST
Accessories
Accessories
Bridge
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 57-pos.
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 12-pos.
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 9-pos.
04/02/2014 Page 4 / 7
https://www.phoenixcontact.com/in/products/2818643
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 8-pos.
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 6-pos.
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 4-pos.
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 3-pos.
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 2-pos.
Device marking
04/02/2014 Page 5 / 7
https://www.phoenixcontact.com/in/products/2818643
Zack marker strip, Strip, white, Unlabeled, Can be labeled with: Plotter, Mounting type: Snap into tall marker groove,
For terminal block width: 18 mm, Lettering field: 18 x 5 mm
End block
Quick mounting end clamp for NS 35/7,5 DIN rail or NS 35/15 DIN rail, with marking option, width: 9.5 mm, color:
gray
Marker for terminal blocks, Strip, white, labeled, Horizontal: Grounding symbol, Mounting type: Snap into tall marker
groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
Marker for terminal blocks, Strip, white, labeled, Horizontal: L1, L2, L3, N, GND, Mounting type: Snap into tall marker
groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
Marker pen
Marker pen - B-STIFT - 1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Drawings
04/02/2014 Page 6 / 7
https://www.phoenixcontact.com/in/products/2818643
150
45
29
L/N( ) L/N( )
51,5
04/02/2014 Page 7 / 7