Sie sind auf Seite 1von 12

BECHTEL CHILE LTDA.

STANDARD

0000-E-004

FOR

ELECTRICAL NUMBERING AND


IDENTIFICATION SYSTEM

FOR

MINERA ESCONDIDA LIMITADA

PHASE IV EXPANSION PROJECT

0 20/SEP/99 Issued for Project Use OSF NV CZ RH MC SIGNED


B 04/AGO/99 Issued for Approval OSF NV CZ RH MC
A 01/Mar/99 Issued for Coordination OSF NV CZ
REV. DATE REASON FOR REVISION BY CHECK EGS VEM PE PEM CLIENT
JOB No. 24017 SHEET 1 OF 12

REV.
BECHTEL CHILE LTDA. STANDARD No. 0
0000-E-004

\\IW\job24017\Drawings\Electrical\OSF\pu
07/09/18
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

TABLE OF CONTENTS

SECTION DESCRIPTION PAGE

1.0 GENERAL NOTES 3

2.0 FACILITY CODES NUMBERS 4

3.0 ELECTRICAL EQUIPMENT DESIGNATORS 4

4.0 EQUIPMENT NUMBERING IDENTIFICATION 4

5.0 DRAWING TYPE DESIGNATOR 5

6.0 DRAWING NUMBERING SYSTEMS 6

7.0 CABLE AND RACEWAYS SERVICE LEVEL 7

8.0 SCHEME/LOOP/CABLE/WIRE NUMBER SYSTEM 8

9.0 RACEWAY NUMBER 10

10.0 220 & 69kV SUBSTATIONS EQUIPMENT CODES 12

References:

1) Project Procedure.
2) 0000-E-006, Setroute Notes & Details.

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 2 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

1.0 GENERAL NOTES

1.1 Purpose

The purpose of the Electrical Numbering System is to provide a clear and


simplified method to identify all electrical equipment, drawings, schemes, cables,
raceways and devices, in a manner suitable for manipulation in a common
database, setroute.

This electrical numbering system suplements and clarifies further the project
numbering systems as specifically applicable to the electrical equipment, devices
and engineering documents. It utilizes the facility codes and equipment
designations included in the project engineering procedure.

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 3 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

2.0 FACILITY CODE NUMBERS

Refer to Project Procedure Manual, Section 5, Subject Numbering systems


for facility designator.

3.0 ELECTRICAL EQUIPMENT DESIGNATORS

Refer to Project Procedure Manual, Section 5, Subject Numbering systems, Exhibit A for
equipment designator

4.0 EQUIPMENT NUMBERING IDENTIFICATION

4.1 ELECTRICAL EQUIPMENT NUMBER

Equipment number is assigned using associated 4 digit Facility Code and


applicable equipment designator as illustrated below.

4.1.1 SWITCHGEAR

EXAMPLE : 4.16kV SWITCHGEAR


COARSE ORE OVERLAND CONVEYOR # 4 : 0220SG221

0220SG221

0220 : Facility Designator

SG : Electrical Equipment Designator

221 : Sequential Number (3 digits)


(First number from facility & last two digits are the sequential number)
see note b) below.

4.1.2 MOTORS

EXAMPLE : 0210CR001-1A (Primary Crusher Hydraulic System Skid motor)

0210CR001-1A

0210 : Facility Designator

CR : Equipment Designator, two letters followed by three digits.


(see section called “ Equipment Project Instruction, Sec. 5.0
Design Engineering)
001 : Number, three digits assigned sequentially

1 : Ancilliary number, two digit assignment (1-99)

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 4 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

A : Designator for Electric Motor

Note :

a) Letters A to P are reserved only for Motors (letters “O & I” are not used).

b) The sequential number shall be unique for each equipment in association


with the “Equipment Designator”.

4.1.3 CONTROL PANEL

EXAMPLE : IF A CONTROL PANEL IS DEDICATED TO ONE


MECHANICAL EQUIPMENT SUCH AS THE PRIMARY CRUSHER
HYDRAULIC SYSTEM SKID 0210CR001-1, THE IDENTIFICATION WILL
BE AS FOLLOWS :

0210CR001-1CO1

0210CR001-1 : Mechanical Equipment or Sub-Equipment from


Mechanical Equipment List

CO : Electrical Control Panel

1 : Sequential Number (if only one panel is used, the


number “1” can be ommited).

5.0 DRAWING TYPE DESIGNATOR (from Project Instruction)

Refer to Project Procedure Manual, Section 5, Subject Numbering systems.

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 5 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

6.0 DRAWING NUMBERING SYSTEM

Schematic and block diagram numbering system is described below for numbering other
type of document see project procedure (Reference 1)

6.1 TYPICAL SCHEMATIC AND BLOCK DIAGRAMS

Typical schematic Drawing numbers consist of seven or eight alphanumeric


characters as follows :

EXAMPLE : 0000-E-501-1

0210-E-501-1

0000 : Process Plant & Mine Facility Code

E : Electrical Discipline

501 : Drawing type Designator

-1 : (1-99) Used only if there are multisheet drawings

6.2 SPECIFIC SCHEMATIC AND BLOCK DIAGRAM

Specific schematic drawing number consist of thirteen alphanumeric character as


follows:

EXAMPLE 1

0320-E-FT001 (Rougher flotation cell)

0320 : Facility Code Number

E : Electrical Discipline Designator

FT001: Mechanical Equipment Number

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 6 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

EXAMPLE 2

0230-E-CR001-1 (Primary Crusher Hydraulic System Skid)

0230 : Facility Code Number

E : Electrical Discipline Designator

CR001: Mechanical Equipment Number

-1 : Sequential auxiliary equipment number

NOTE: In case of schematic drawing has more than one sheet, add “-1, -2, etc” at the
end of the drawing number described before, as follow:

0230-E-CR001-1-1 Primary Crusher Hydraulic System Skid)

0230-E-CR001-1 : Schematic drawing number for primary crusher


hydraulic system skid.

-1 : Sheet number one for schematic drawing of primary


crusher hydraulic system skid.

7.0 CABLE AND RACEWAYS SERVICE LEVEL

The service level is assigned to every cable & raceway to insure that the cable is routed
in the proper service level raceways.

A : MEDIUM VOLTAGE 23 kV (POWER)


B : MEDIUM VOLTAGE 13.8 kV (POWER)
E : MEDIUM VOLTAGE 4.16 kV (POWER)
F : MEDIUM VOLTAGE 7.2 kV (POWER)
P : LOW VOLTAGE 480/400/231 V (POWER) & 120 VAC INSTRUMENT
POWER
C : LOW VOLTAGE 120 VAC (CONTROL)
D : LOW VOLTAGE 125/48/24 VDC (CONTROL)
J : INSTRUMENTATION ANALOG SIGNAL 24 VDC OR BELOW
R : DATA & COMMUNICATION
S : FIRE PROTECTION

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 7 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

8.0 SCHEME/LOOP/CABLE/WIRE NUMBER SYSTEM

8.1 SCHEME NUMBER

Scheme numbers are derived from the Mechanical equipment number and consist
of nine or more alphanumeric characters as follows :

EXAMPLE :
Scheme N°.: 0210-CR001-1 (Primary Crusher Hydraulic System Skid)

0210-CR001-1

0210- : Facility Code Number “ – “ to be ommited

CR001 : Equipment Number

-1 : (1-99) Sequential Ancilliary Equipment Number

8.2 LOOP NUMBER

Loop numbers are derived from P & ID and consists of nine or more
alphanumeric characters as follows:

EXAMPLE :
Scheme N°.: 0210-L0123 (Level measurement on P & ID for FAC 0210)

0210-L0123

0210 : Facility Code Number

L : Loop function (P-Pressure


L-Level
T-Temperature
F-Flow)

0123 : Sequence loop number (commencing from 0001)

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 8 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

8.3 CABLE NUMBER

Cable numbers consist of the scheme or loop number with service level
and cable sequential number.

EXAMPLE : (SCHEME)

0210CR001-1P01

0210 : Facility Code Number

CR001 : Equipment Number

1 : (1-99) Sequential Ancilliary Equipment Number


P : Service Level

01 : (01-99) Cable Sequential Number

EXAMPLE : (LOOP)

0210F1013J01

0210 : Facility Code Number

F : Loop function

1013 : (0001-9999) Sequential Instrument Number

J : Service Level
01 : (01-99) Cable Sequential Number

Cable sequential number will be used in ascending numerical order.

8.4 WIRE NUMBER

Wire numbers will consist of one or two alphanumeric characters.

This number will be shown on the Setroute “Termination Card”, “Cable


Schedule”, “Elementary Diagram” or Loop Diagrams.

9.0 RACEWAY NUMBER

Raceway/Number/Identification consist of nine alphanumeric characters. Each raceway


number is unique in association with the applicable facility code number

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 9 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

9.1 CONDUIT NUMBER

EXAMPLE : 0310CA001

0310CA001

0310 : Facility Code Number

C : Conduit (Raceway type)

A : Service Level

001 : Sequential Number (001-999)

9.2 CABLE TRAY NUMBER

EXAMPLE : 0310TA001

0310TA001

0310 : Facility Code Number

T : Cable Tray (Raceway type)

A : Service Level

001 : Sequential Number (001-999)

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 10 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

9.3 PULL BOX NUMBER

EXAMPLE : 0310PB001

0310PB001

0310 : Facility Code Number

PB : Pull Box (Raceway type)

001 : Sequential Number (001-999)

9.4 SPECIAL RACEWAY NUMBER

EXAMPLE : 0310MH01

0310MH01

0310 : Facility Code Number

MH : Type Special Raceway

01 : Sequential Number (01-99)

SPECIAL RACEWAY TYPE : MH - MANHOLE


HH - HANDHOLE
TR - TRENCH
PB – PULL BOX

NOTE : Additional details for Raceway and Cable Codes are in the document
0000-E-006 : “ SETROUTE NOTES & DETAILS”. (Reference 2)

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 11 of 12
Standard for Electrical Numbering and Identification System
0000-E-004 Rev. 0

10.0 220 & 69Kv SUBSTATIONS EQUIPMENT CODES

Additionally for MEL internal use, the 220/69kV substation equipment are also
numbered as follows in conformance with the numbering system used for the existing
substation equipment.

OPERATIONAL EQUIPMENT CODES

89: Disconnect Switch

52: Circuit Breaker

TX: Transformer X
Where X: 1, 2, 3, 4, 5, 6, 7

LX: Line X
Where X: 1, 2, 3, 4

SERVICE LEVEL

J: 220kV
B: 69kV

EXAMPLES:

a) 89JT1-1
220 kV disconnect switch for transformer # 1

b) 52JL1-1 (when no associated transformer is available)


220 kV circuit breaker for line # 1

\\IW\job24017\Drawings\Electrical\OSF\pu
09/08/99
Page 12 of 12