DOC. TITLE: STEEL TANK FARM TAIF P&I DIAGRAM
DOC. NO: 7 6 - Q P 2 0 - D - 0 0 2
REV. DATE: 13.05.2018
4. Max. Water level in tank 19.600m, Min. Max. and Min. Water level in tank is as per
water level 0.300m, Overflow level approved Tank Sizing Calculation Report for
19.91m, shell height 20.26m. Tanks at Taif Storage Tanks at Taif (76-QP40-J-
004, Rev D).
The Referred Overflow level 19.91m, shell height
20.26m is not tank level (from top of the bottom
plate) this is from finish ground level (FGL)
5. Automatic Vent Valve at outlet ID# Automatic Vent shall be provided at highest
76XP17S should be on the 60" main pipe potion of the piping. Since all the 60 “header
similar at inlet. will be underground, then air vent will be
positioned at the lowest side of the branch
above ground piping. Final location, numbers
and size will be as per hydraulic calculation
report. Refer Notes#4.
Tank drain valves size is as per QP20-
6. Tank drain valves size should be based D-5485 Typical Steel Tank 170000m³-
on design calculations. Tank Drain to be TaifStrategicReservoir-P&IDiagram-
connected to storm water system piping. Rev1(Tender drawing). Tank Drain will
be connected to station drain
network.
7. Valves 76XP17S704 and 76XP17S705, The Referred 200mm nozzles are inlet tap for
200mm dia. at inlet purpose to be mobile drain pumps outlet. Refer Notes#3.
described.
8. Vent at Dome Roof, Automatic vents Tank venting and automatic vent shall be as per
design / dimensions to be based on tank design calculation report. Refer notes#8
calculations.
11. Low level switch signal position to be Noted. The correct position of the switches is
shown correctly (in layout near high level described in the Typical Steel Tank
switch), for example (76XP15L301). Instrumentation Overview for Taif “76-QP10-S-
002”.