- 08/2016, UPGRADING OF AL AWABI, AL HAZIM AND WADI BANI GHAFIR PRIMARY SUBSTATION (33/11kV) TO
PROJECT:
SOUTH AL BATINAH GOVERNORATE
1 08/2016/AHM/ELCT-06 01 of 03 1. Submission of Drawing in TWO sheets (Tray & Trench) as they in different levels
1. The Trench and Duct layouts Outside the Control Building shall be shown in one drawing
2 08/2016/AHM/ELCT-06 01 of 03 with No power & control trays.
1. The Tray Drawing should have Power Cable & Control Cable Tray with No doors,
windows Schedule, partition walls etc.
3 08/2016/AHM/EL/CT-06 01 of 03 2. The Equipment should be shown in a Light/ Fades Lines with no floor slab or beams of
ground floor.
4 08/2016/AHM/EL/CT-06A 02 of 03 1. Combine the two Trays (Detail-I & J1) and provide in Two layers
Section A-A
1. Control Cables to marked
7 08/2016/AHM/EL/CT-06B 03 of 03 2. Capcitor Bank Cables to be marked
Section B-B
8 08/2016/AHM/EL/CT-06B 03 of 03 1. Future 33KV incomer Cable to be shown
Section D-D
9 08/2016/AHM/EL/CT-06B 03 of 03 1. 11KV TXN cables to be shown layed on trays
Section E-E
1. Future 33KV Incomer Cable to be Shown
10 08/2016/AHM/EL/CT-06B 03 of 03 2. Future 11KV TX-3 Cable to be Shown
Section E1-E1
1. Future 33KV Incomer Cable to be Shown
11 08/2016/AHM/EL/CT-06B 03 of 03 2. Future 11KV TX-3 Cable to be Shown
Section J-J
13 08/2016/AHM/EL/CT-06B 03 of 03 1. 11KV T1 & T2 cables to be labelled
Detail-B
1. Future Capacitor (C-3) Cable to be Shown
15 08/2016/AHM/EL/CT-06B 03 of 03 2. Future 33KV Incomer (I/C-3) Cable to be Shown
3 Future Transformer (Txn-3) Cable to be Shown
Detail-E
1. Future Capacitor (C-3) Cable to be Shown
16 08/2016/AHM/EL/CT-06B 03 of 03 2. Future Transformer (Txn-3) Cable to be Shown
Detail-F
17 08/2016/AHM/EL/CT-06B 03 of 03 1. Future Transformer (Txn-3) Cable to be Shown
2. LT Cables to be Shifted to the top layer
Detail-G
18 08/2016/AHM/EL/CT-06B 03 of 03 1. Future Transformer (Txn-3) Cable to be Shown
2. 11KV Outgoing Cables to be Shown with Additional Tray
Detail-H
19 08/2016/AHM/EL/CT-06B 03 of 03 1. Future Transformer (Txn-3) Cable to be Shown
2. 11KV Outgoing Cables to be Shown with Additional Tray
Detail-J & J1
20 08/2016/AHM/EL/CT-06B 03 of 03 1. Combine these two trays
2. Transformer (Txn-3) cable to be shown
SUBSTATION (33/11kV) TO 2x20MVA AT
Compilance Remarks
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled
Noted &Compiled