Sie sind auf Seite 1von 4

Transformer Inrush Current

In this post we will discuss the Magnetizing Inrush Current in a Power Transformer.
Magnetizing Inrush current in Transformers results from any abrupt changes of the
magnetizing voltage. This current in transformer may be caused by energizing an
unloaded transformer, occurrence of an external fault, voltage recovery after clearing an
external fault and out-of phase synchronizing of connected Generator.Because the
amplitude of inrush current can be as high as a short circuit current, a detailed analysis
of the magnetizing inrush current under various conditions is necessary for the making
required setting of protective system for the Transformers.

First question which will come up in your smart mind, why a Power Transformer takes
Inrush Current when energized in unloaded condition?

When a power transformer is energized while keeping its secondary circuit open, it acts
as an inductance. In normal condition of a Power Transformer, the flux produced in the
core is in quadrature with applied voltage i.e. Flux lags behind the applied voltage by
90° as shown in the figure below.

This means, Flux wave will reach its maximum value after 1/4 cycle or π/2 angle
reaching maximum value of voltage wave. Hence as per the waves shown in the figure,
at the instant when, the voltage is zero; the corresponding steady state value of flux
should be negative maximum. But practically it is not possible to have flux at the instant
of switching on the supply of Transformer. This is because, there will be no flux linked to
the core prior to switching on the supply. The steady state value of flux will only reach
after some finite time which in turn depends upon how fast the circuit can take energy.
So the flux in the core also will start from its zero value at the time of switching on the
transformer.

As we know that,

e = dφ/dt where φ is the Flux in the core

Therefore assuming e = ESinωt,

Unrestricted
Now suppose, Transformer is switched on when Voltage is zero. Therefore Flux will
also start from zero. Therefore, total Flux at the end of first half cycle of voltage wave
will be,

Where Øm = Maximum flux in the core in steady state or normal operating condition.

Therefore, the flux in the core of Transformer will be double the maximum value of flux
in steady state condition. This phenomenon is also shown in figure below.

It is clear from the above graph that maximum flux in the core of Transformer will be
2Ømwhen the applied voltage is at its zero.

Unrestricted
Now what will happen because of this higher value of flux in the core of
Transformer?

Transformer core is saturated just above the maximum steady state value of flux Øm.
But when we switch on power supply to the Transformer’s primary, the maximum value
of flux will jump to double of its steady state maximum value Øm. As, after steady state
maximum value of fluxØm, the Transformer core becomes saturated, the current
required to produced rest (2Øm-Øm= Øm) of flux will be very high. So transformer primary
will draw a very high current from the source which is called Magnetizing Inrush
Current in Transformer or Inrush Current in Transformer. The nature of Transformer
Inrush Current is shown in figure below.

It should be noted that waveform of Transformer Inrush Current is asymmetric


which means in Transformer Inrush current mainly 2nd harmonic component will
be present. It shall also be noted from the waveform that as time passes the
Magnetizing Inrush Current of Transformer decays and becomes zero. Normally it
takes few millisecond for Magnetizing Inrush Current to decay to zero.

The Magnetizing Inrush Current of Transformer may be up to 10 times higher than


normal rated current of Transformer. Even though the magnitude of Magnetizing
Inrush Currentis so high but it generally does not create any permanent fault in
Transformer as it exists for few miliseconds. But still Magnetizing Inrush Current in
Power Transformer is a problem, because during the time of Magnetizing Inrush
Current the protection scheme of Transformer may operate and hence may trip
the Primary side Circuit Breaker of Transformer which is not expected.

How do we prevent Tripping of Transformer due to Magnetizing Inrush


Current?

In Transformer Differential Protection an intestinal time delay of 20 milisecond is


provided to prevent tripping of Transformer due to high Magnetizing Inrush Current. In
modern Numerical Relay, 2nd Harmonics blocking feature is provided which blocks the
2ndHarmonics when it is more than set value, thereby don’t issue trip command to
Transformer Primary side Breaker due to Magnetizing Inrush Current.

Unrestricted
Normally the setting of 2nd Harmonics blocking is set to 20% which means if
2ndHarmonic component is more than 20% of fundamental frequency value of current
then Relay will understand that it is because of Magnetizing Inrush Current and hence
won’t issue trip command but if it is less than 20% fundamental frequency value of
current then Relay will treat it due to fault and will issue trip command to the primary
side Circuit Breaker.

Is there no way to minimize Magnetizing Inrush Current of Transformer?

Point on Wave Switch is used to minimize the Magnetizing Inrush Current of


Transformer. If you want to know more about Point on Wave Switch, please read
“Point on Wave Switch“

Unrestricted

Das könnte Ihnen auch gefallen