Beruflich Dokumente
Kultur Dokumente
Table 19.1
Inspection Requirements for Centrifugal Pumps
1 2 3
b b Radiograph inspection of impeller
a a Liquid penetrant inspection of impeller
b b Liquid penetrant inspection of casing repairs
C C Impact test
b a Hydrostatic test
b a Performance test
Certified performance test and NPSH curve
Mechanical run test with vibration measurements
Manufacturer's standard mechanical run test
C C Noise level test
a a Dismantling in case of failed mechanical run test
c a Balancing of rotating assembly
c c Hardness test for impeller and casing welds*
Key:
I = Centrifugal utility pumps < 50 hp or < 250 psig discharge pressure
2 = All centrifugal pumps > 50 hp or > 250 psig discharge pressure
3 = Process pumps < 50 hp or < 250 psig discharge pressure
142
Inspection and Testing 143
The buyer must determine the inspection procedures he or she wants. If a witnessed
test is necessary, the inspector should be instructed to perform the following tasks:
Hydrostatic Test
Hydrotest the pump casing at 1.5 times its design pressure. The gaskets used for
this test should perfectly match the gaskets used in the pump. Leaks past the gaskets
are not acceptable. Discard the test gaskets after the test.
If any leakage or pressure drop occurs during the test, repeat the test after making
necessary repairs. Test pumps whose medium has a specific gravity of 0.7 or less
with kerosene.
Use dye penetrant solution for the hydrotest if the casing pattern is new or
changed, and/or if the pump media will consistently remain above 500*F. Any dye-
penetration test shall adhere to ASTM E165. If the buyer does not require a witnessed
hydrotest, the vendor shall submit its test data for client review.
Performance Test
The buyer may insist on a performance string test, which shall include the actual
driver, instrumentation, and eventual gear (see Figure 19.1 for setup). Because the
vendor's lack of the electric power required may render this test inconvenient or
impossible, most companies allow the vendor to use a shop driver. The shop driver
often consists of a hydraulic turbine instead of an electric motor. Preferably, the test
shall run at rated speed, but the vendor may run the test at other speeds. In this case,
the vendor should submit the conversion-to-rated-speed calculations to the buyer for
approval before starting the test. The actual string test will then occur at start-up.
The manufacturer usually will use water during the performance test. If the real
pump medium is viscous, the manufacturer shall make the necessary correction,
according to the latest issue of the Hydraulic Institute Complete Pump Standards.
The vendor often submits a list of the test equipment it will use. Upon request, the
vendor shall submit calibration data for this equipment. Typical instruments include:
The performance test shall be combined with the mechanical run test, which shall
last a minimum of four hours. The inspector shall check the following data, which
should match the actual performance curve:
The buyer shall select at least five flow rates for inspection. These should include
the following points:
• Shut-off
• Minimum flow as specified by vendor
• A point between rated and minimum flow
• Flow at best efficiency point
• Rated flow
• 110 percent of rated flow
If there is a gear in the pump package, the inspector shall check the gear contact
pattern after the conclusion of the performance test. Gear contact shall be consistent.
A contact area of less than 75 percent will affect gear performance.
After the performance test, it is customary to open multistage and barrel pumps to
inspect the rotor assembly. After draining the test liquid, the test crew shall dry all
the pump components.
Inspection and Testing 145
ORIFICE
VALVE VAL
NPSH Test
It is a good idea to run a NPSH test on pumps 100 hp and larger where the
NPSHA is close to the pump's required NPSH. The suppression test may determine
the NPSH at 3 percent differential head loss or at 0 percent loss if the pump is in crit-
ical service with variable flow. The NPSH shall be plotted at the following flow
rates, as a minimum: