5 Ambient Temperature °F 100 °F 6 Compressed Air Inlet Temperature °F 100 °F 7 Compressed Air Pressure Psig 100 Psig 8 Compressed Air Flow Rate** CFM CFM 9 Correction Factor (if available) - 1 - Refrigeration Cycle 10 Suction Pressure Psig 30.5 Psig 11 Discharge Pressure Psig 130.5-174 Psig For Multiple Fans (if available) 12 1st Fan Working Pressure Psig 130.5-174 Psig 13 2nd Fan Working Pressure Psig 145-188.5 Psig 14 3rd Fan Working Pressure Psig 159.5-203 Psig
Refrigerant Temperatures Reading From Surface of The Relevant Pipes
Condenser (All Types) Possible Range for Normal Operation 15 Inlet Temperature °F 122-186 °F 16 Outlet Temperature °F 95-113 °F Evaporator 17 Inlet Temperature °F 33.8-39.2 °F 18 Outlet Temperature °F 39.2-59 °F Compressor 19 Inlet Temperature °F 39.2-68 °F 20 Outlet Temperature °F 122-186 °F Filter Dryer 21 Inlet Temperature °F 95-113 °F 22 Outlet Temperature °F 95-113 °F 23 Condenser Fans Working O Not Working O 24 Compressor Working O Not Working O For RC Dryers 25 Water Level*** Full O Middle O Bottom O 26 Water Pressure Psig 2.9-43.5 Psig 27 Freezing Point of the mixture °F 5 °F
Condenser (Water Cooled) Possible Range for Normal Operation
28 Water Flow Rate**** CFM CFM 29 Water Inlet Temperature °F 41-86 °F 30 Water Outlet Temperature °F 95-158 °F 31 Water Inlet Pressure Psig 13-58 Psig 32 Water Outlet Pressure Psig 13-58 Psig
** Please write actual and design values
*** Please tick one **** Check the range by using water condenser capacity table