AC Motors In-Depth
.
Keys to Successful Motor Operation
Proper installation
Proper maintenance
Incorrect voltage
Operating above rated voltage increases core losses thus
reducing efficiency
Operating below rated voltage, motor draws more current and
overheats
Unbalanced voltage
A 1% imbalance in voltage can lead to an 8% imbalance in
current
Hot spots are produced while net torque is reduced
Generally, 10°C rise cuts motor life in half
Stator leads, coils and connections are covered with a dielectric insulation
Stator is subjected to dip/bake cycles for low voltage motors
Low voltage motors utilize random wound coils
Under ideal conditions, insulation system can be expected to have life
cycles in excess of 100,000 operating hours
Insulation is classified according to total temperature capability of the
system
A 110°
B 130°
F 155°
H 180°
For every 10°C above the insulation class thermal limit a motor is operated, the insulation life
expectancy is reduced by as much as 50%.
For internal use only.
Proper Motor Installation
Dimensional limitations
Distance from shaft centerline to mounting feet (adapter base)
Job site obstructions
Location of conduit box
Obstructions placed near motor may deflect air back into the inlet
Noise reduction enclosures restrict ventilation
Windings overheat
Thermal life is shortened
Bearing lubrication
Cleaning
Testing
Motor protection
Excess grease can be forced out of the bearing housings and into
the motor windings
Thermal Protection
Thermistors
Thermostats
Resistance Temperature Detectors
Bearing temperature monitoring
Vibration monitoring
Moisture protection
Install space heaters
Apply low DC voltage to one phase of motor windings
Belt
Pull
Force
Force on
on Force on
ODE
ODE Bearing
Bearing DE Bearing
Considerations:
Large diameter motor sheaves are good for the motor (lower
bending moment acting on shaft)
Small diameter motors sheaves are bad for the motor (higher
bending moment acting on shaft)
Minimum sheave diameter information provided on page 8-29
of 2008 price catalog and in the NEMA Motor Application
Manual
Wide sheaves (excessive # of belts) are bad for the motor
Moves the center of the radial force further from the DE bearing
(higher bending moment on shaft)
Other considerations:
2-Pole (3600RPM) motors not recommended for belting applications ( >
25 HP )
Generally limited by speed capability of bearings and excessive tension
needed due to centrifugal force on the belts
NEMA does not address 2-pole, belted applications ( > 25 HP )
Mounting of the motor
Roller bearing motors mounted vertically, shaft down require a special
grease path so that grease is applied above the bearing
Roller bearings can be used in horizontal, direct connect applications (not
recommended) if customer OK with the grumbling bearing noise that
results
Roller bearing motors should never be used in a vertical, direct connect
application as rotor weight is needed to put minimum radial load on
bearing.
Centrifuges
Large fans
Two-speed motors
Brake motors
Two-speed motors
Commonly used in cooling tower ( fan ) applications
Two types of applications
Variable torque
Constant torque
Two types of configurations
Single winding ( low speed must be ½ of high speed )
Two winding ( lower cost controls )
Brake Motors
Integrally-mounted on NDE to stop motor in applications where
coasting to a stop is not desired
Common uses include material handling
Not recommended for high inertia applications