Beruflich Dokumente
Kultur Dokumente
1
Optical and DWDM Testing
T
he rapid development of fiber optic technology has made possible the ever-
increasing flow of data and voice traffic over a single fiber. Increased usage places
exceptional demands on service quality and makes errored or interrupted service
more critical than ever before. Service providers are continuing to increase
bandwidth using higher speeds or Wavelength Division Multiplexing (WDM) technology.
Because many existing optical fiber cables were installed to transport lower rates and single
wavelengths, intermittent errors commonly surface when systems are upgraded to increase
bandwidth. As a result, technological advances create the possibility for problems that could
delay service turn-up and increase callbacks. Testing the physical layer for various wavelengths
and physical impairments during provisioning ensures future acceptability as networks expand,
saving the time and expense of cable replacement. Today, service providers not only need
comprehensive optical tests, but they also need an overall strategy for network installation and
maintenance before live traffic is commissioned.
This application note is one in a series of comprehensive guides for service providers
using the TTC T-BERD 310 to install and maintain telecommunications networks. Each of
the application notes in this series contains specific tests and troubleshooting appendices to
isolate common problems associated with the transport network. If you have difficulty with
any of the tests, call TTC’s Technical Assistance Center (TAC) at 1-800-638-2049. The TAC
staff also would appreciate hearing from you about additional testing tips to enhance the
troubleshooting appendices.
2
degraded service. These problems are
especially evident at today’s high speeds,
since many existing optical fiber cables were
ATM Configuration Layer
Testing Strategy installed to transport lower rates. In some
cases, optical measurements were never
SONET Configuration Layer
performed on these cables.
A high ORL measurement is desirable
because it indicates less light is being
Physical Layer reflected back to the laser source. A
measurement of 30 dB is sufficient for most
applications, while a measurement of about
12 dB indicates a large reflection caused by
an open fiber. The equation for measuring
Figure 1: ORL is shown below. Assuming the power
transmitted stays constant, the lower the
Transport testing layers power received by the transmitter, the higher
the total ORL measurement.
ORL (dBm) = 10 log x TX Power (by Trans)
RX Power (by Trans)
Physical layer testing identifies a performed during installation of the
variety of problems caused by improper line backbone ATM transport network or during Since ORL only measures what is
build-out, connector or cabling faults, configuration of ATM service. It is important happening at the transmitting end of the
repeater failure, optical reflections, optical to include in-service testing since data fiber, it cannot verify the total integrity of the
loss, and improper optical amplifier tuning transport problems, such as delay variation span or that sufficient power actually arrives
in Dense Wavelength Division Multiplexing and congestion, can only be roughly at the optical receiver at the far end. To
(DWDM) systems. Tests include pulse shape, simulated during out-of-service testing. illustrate, Figure 2 on the next page shows
jitter, signal measurements, Bit Error Rate The unpredictable nature of data networks a sharp bend in the fiber, which allows light
Test (BERT), Optical Return Loss (ORL), can cause problems to surface even after to escape the cladding. Because the bend
optical insertion loss, as well as channel out-of-service simulations have functioned reduces total reflection back to the
peak power, center wavelength and properly. In-service tests include monitoring transmitter, the ORL measurement actually
Signal-to-Noise Ratio (SNR) in DWDM ATM congestion, alarms, errors, and delay improves. What the ORL test does not show
systems. Because these tests are performed variation. The application note pertaining is that the bend also reduces the total
primarily at several network locations (DS3 to this layer is ATM Testing with the amount of power crossing the span to the
demarcation points and in the optical T-BERD 310. Thorough testing verifies receiver. A second test is needed to verify
backbone), Optical and DWDM Testing ATM transport configuration to ensure the receiving end of the fiber.
with the T-BERD 310 and DS3 Testing trouble-free service turn-up. An IL test measures total power loss
with the T-BERD 310 application notes across an optical span and indicates overall
were developed to thoroughly test the receiver health. A high IL means excessive
power loss with inadequate levels reaching
physical layer. Since physical layer problems
commonly cause intermittent and hard-to-
Why Test the receiver. A low IL indicates minimal
power loss, which can cause receiver
find trouble at higher layers, it is critical to
verify DS3 and optical backbone operation
Optical Fibers? saturation, especially when high power
during installation to prevent callbacks. Testing the optical network lasers are used. Long reach lasers require a
SONET configuration layer testing during service turn-up is one way to avoid minimum of 10 dB insertion loss. To prevent
eliminates common problems associated expensive upgrades and callbacks due to intermittent errors or system failure, total IL
with SONET circuit setup. Tests include intermittent errors that surface after the should be within a defined range.
SONET timing, SONET path configuration, optical transmission equipment is placed
error and alarm reporting, and concatenated on the span. ORL and Insertion Loss (IL)
signal configuration. These tests, detailed in are the two tests that, when performed
the SONET Testing with the T-BERD 310 together, ensure the fiber span has been This application note defines
application note, ensure the circuit is thoroughly verified. 5 dB to 15 dB power loss as an
properly installed for the desired service. ORL indicates the optical network’s
acceptable range for single
This testing results in reduced turn-up time ability to transport high-speed signals
because it measures the total accumulated mode fibers. This is calculated
and fewer maintenance calls.
power from reflections in the fiber. The ORL using a known output of the
ATM configuration layer testing
verifies ATM Virtual Path/Virtual Channel measurement is taken at the transmitting end T-BERD 310 stable source
(VP/VC) configuration. Specific tests include of the fiber using an Optical Continuous as -10.0 dBm, while optical
ATM switch configuration, end-to-end Wave Reflectometer (OCWR), also referred power is verified between
channel setup, alarm and error reporting, to as the stable source. Too much total
-15.0 dBm and -25.0 dBm.
errored cell handling, and bandwidth and reflected power can interfere with the
priority configuration. These tests are operation of the transmitting laser, causing
3
• A single optical fiber that transports
all the channels throughout the network.
• EDFAs which boost total optical power
in the fiber without extracting information
carried by the optical signals.
• A splitter, or passive demultiplexer.
Bend in fiber (Splits one fiber back into its original
SONET multiple of “n” fibers.)
Network • A selector (filter) to separate
Element Tx
specific wavelengths.
Rx
SONET
Network A splitter and a selector are
Figure 2: Element often combined into a single
Sharp bend in optical fiber optical structure.
4
Transmitter
from
Transmission Selector Second-generation DWDM
Element Transponder (Filter) systems have a receiver for
increased performance
λ1
λ1 WDM 1
Tx Rx
EDFA EDFA
Tx Optical Optical Rx
MUX Demux
Tx Rx
λn Transponder-Based n
λn
Tx Rx
Figure 3.1:
Transponder-based system
Selector
Transmitter Coupler Splitter (Filter)
λ1 WDM WDM λ1
Tx Rx
EDFA EDFA
Tx Rx
Tx Rx
λn Non-Transponder-Based λn
Tx Rx Figure 3.2:
Non-transponder-based system
5
Peak power is the energy that lies
Original Level
beneath the filter skirt of each laser line. Each
New Level channel at every available interconnection
Power
Time Time
Crosstalk
Figure 5:
Chromatic dispersion
6
Power
ASE
Wavelength
— Channel Peak Power
– – – – Channel Center Wavelength
Figure 6: ASE = Amplified Spontaneous Emission
Gain
Tilt
Power
ASE
Wavelength
Figure 7:
Gain tilt
Power
SNR
ASE
Wavelength
Figure 8:
SNR
7
SNR does not necessarily indicate a low BER • Two T-BERD 310 test sets with these DWDM Testing w/OC-12
because of four-wave mixing (see Figure 4 options: DWDM OPTION (310-22)
on page 6) or dispersion (see Figure 5 on 310-12 SONET OC-12 TX/RX SONET OC-12 OPTION (310-12) or
page 6), both of which can cause a high SNR 310-14R SONET STS-1, OC-1/3, OC-12 DUAL nm OPT (310-12-DUAL)
and a high BER. It also characterizes the OC-3c RX BER Testing w/OC-48
optical noise level detected at the receiving 310-14T SONET STS-1, OC-1/3, SONET OC-48 OPTION (310-21-1300/1550) or
OC-3c TX OC-48 DUAL nm OPT (310-21-DUAL)
end of the dense WDM optical link. Therefore,
the ultimate test is end-to-end BER testing. 310-16 Optical Media Test BER Testing w/OC-12
310-21 1300 nm SONET OC-48, SONET OC-12 OPTION (310-12) or
The decisive parameter in
OC-48c TX/RX OC-12 DUAL nm OPT
determining the transmission quality of a
system is the BER in an end-to-end test. 310-22 DWDM Channel Monitor If the option is installed, the display
Since DWDM systems typically carry • Four tags to label fiber jumpers shows “Installed” or “Module Code = a
SONET/SDH framed traffic, a transmission revision number”. If the option is not
quality cover of 10-12 BER or better is installed, the option code may not appear or
expected as per Bellcore GR2918 and Equipment shows “Not installed”. If the required option
ITU-T G.692. The following approaches are is not installed, please call your local TTC
commonly used for BERT analysis. A lengthy Verification sales office or distributor listed on the back
soak test is the most common approach for To determine if the necessary options cover, or call TAC at 1-800-638-2049.
qualifying DWDM systems. are installed in your T-BERD 310, complete
the following steps:
1. Turn off the power to the test set. Pre-Test Setup
Equipment Required 2. Press and hold the MODE switch down Each test setup in this Application Note
while turning power on.
for Optical and 3. Release the MODE switch when the first
assumes that the T-BERD 310 is restored to
factory default settings before testing begins.
hardware revision appears.
DWDM Testing 4. Press the MODE down arrow to scroll
Follow this procedure to restore all factory
default settings:
In order to perform this test, the through a list of installed boards and
options. Look for the appropriate 1. Turn off power to the test set.
following equipment is required:
option code: 2. Press and hold RESTART.
• Fiber Optic Cleaning Kit Optical Testing 3. Turn on power. Look for the “RELOADING
(Model No. FO-Cleaner) OPTIC MEDIA TST OPT (310-16) NOVRAM” message. When the message
DWDM Testing w/OC-48 appears, release the RESTART button.
DWDM OPTION (310-22) Factory default settings restore in about
SONET OC-48 OPTION (310-21-1300/1550) or 60 seconds.
OC-48 DUAL nm OPT (310-21-DUAL)
8
Optical Testing
A Testing Optical
s a rule, optical testing should be connectors and test set connectors. Tag
done before other types of testing optical fibers with arbitrary TRANSMIT
because optical problems affect
other International Standards
Return Loss and RECEIVE designations.
2. At East and West, connect the fiber
Organization (ISO) layers. Additionally, since The objective of this test is to designated TRANSMIT to the RETURN
handling fibers and connectors may invalidate verify ORL is within specification at the LOSS/SOURCE connector on the side
SONET transmitters. panel of the T-BERD 310. Leave the fiber
ORL and IL tests, optical tests should be designated RECEIVE connected to the
repeated after all other testing is completed. SONET network element. It is important
The instructions in this application note are Test Setup that this end of the fiber is closed. If the
written for the T-BERD 310-S SONET/ATM 1. Place a T-BERD 310 at each end of the network element is not available, connect
User Interface as shown in Figure 9. circuit and arbitrarily identify one as East the fiber directly into the POWER METER
and the other as West. Clean all fiber optic connector on the T-BERD 310. Figure 10
on the next page shows the proper
connections for this test.
1 2 3 4 5 6 7 8 9 10
T-BERD 310 C O M M U N I C AT I O N S A N A LY Z E R
ATM
CELL SYNC
SONET
SIGNAL PRESENT
CELL SYNC LOSS
FRAME SYNC
AIS RDI PATH PTR PRES
HISTORY VT PTR PRES
CONCAT PAYLOAD
14
15 16 17 18 19 20 21
Legend:
1. Setup 12. Channel Control
2. MODE 13. INSERT
Figure 9: 3. PATTERN 14. DROP
4. LASER ENABLE button 15. ERROR INSERT button
The T-BERD 310
5. RESULTS I arrowed switch 16. SONET TRANSMIT TIMING
with SONET/ATM 6. RESULTS I blank switch 17. ERROR INSERT select switch
user interface 7. RESULTS II blank switch 18. ALARM INSERT button
8. RESULTS II arrowed switch 19. DS3 TRANSMIT TIMING
9. RESTART 20. ALARM INSERT select switch
10. DISPLAY HOLD 21. DS3 SOURCE
11. AUX
9
West East
Rx Rx
Figure 10:
Connecting the T-BERD 310 to the
network to test optical return loss
10
West East
Tx Rx Tx
Rx
Span
Figure 11:
Connecting the T-BERD 310 to the
network to test for insertion loss
DWDM Testing
11
Press RESULTS I arrowed switch; 7. Configure the user interface as follows:
scroll through the following Define UNITS:
measurements: The PEAK EXCURSION defines
Select nm or THz.
WDM Channel Wavelength (nm) the rise and fall in amplitude
WDM Channel Frequency (THz) Define PEAK THRESHOLD:
WDM Channel Power (dBm) Enter value between 0 dB and 40 dB. that must take place for a
WDM Channel SNR (dB) laser line to be recognized.
3. Repeat steps for subsequent individual The default value for PEAK
carrier wavelengths. EXCURSION is 15 dB.
The peak threshold limit defines
Test Setup: the minimum value of optical
power required for peaks to
310 Module w/Laptop 7. Scan Waveform
1. Set Baud Rate: be considered valid DWDM Press RESTART SCAN button
Press AUX. channels. Each laser line must on the PC GUI.
Press MODE; select PRINT. exceed the peak threshold limit. After the waveform updates
(approx. 25 secs. due to Baud rate);
Press PATTERN; It is determined by subtracting
select BAUD RATE. select STOP SCAN.
the PEAK THRESHOLD value
Select 9600.
2. Clean all the fiber optic connectors and
from the power of the largest Test Results
test set connectors. laser line. The default value for 1. Select the desired wavelength:
3. Connect the fiber from the system to the PEAK THRESHOLD is 10 dB. Using table on PC software GUI,
side panel of the T-BERD 310. scroll to desired wavelength
4. Connect the PC to the T-BERD 310 via an and click to select. (See Figure 12.)
RS-232 cable. Define PEAK EXCURSION:
5. Double click on the DWDM icon to run
Enter value between 1 dB and 30 dB.
the program.
6. Verify the connection. The LED on the PC
screen will turn green. A red LED indicates
no connection.
Figure 12:
DWDM scan mode
12
End-to-End useful for system verification. The
real-case scenario of this method,
loads. But while this method provides the
best balance of cost and time effectiveness,
Transponder Selector
Rx Tx Rx Tx
1 1
Rx Tx 2 2
Test Set 3 Optical Optical 3
MUX Demux
16 EDFA EDFA 16
Selector
Transponder
Tx Rx
1 Tx Rx
1
2
2
3
Optical Optical 3
MUX Demux
16
16 16
Figure 13:
Daisy chain testing
Transponder Selector
λ1 Test Set
λ1
Rx
Figure 14:
Multi-channel BERT with
single transmit and receive testing
13
Transponder Selector
Test Set
λ1
λ1 λ1
Rx
Test Set
EDFA
Test Set Tx Splitter Rx
Optical Optical
MUX Demux Test Set
EDFA
(optional Rx
depending on λn
signal strength) λn Test Set
λn
Rx
Figure 15:
Multiple receiver testing
14
5. At East and West, connect the fibers
marked TRANSMIT to one of the following STS-1 Transmit
to the Network Element
T-BERD 310 side-panel connectors:
OC-1/3 TRANSMIT, OC-12 TRANSMIT, OC-48 Transmit To the
or OC-48 TRANSMIT, depending on the Network Element
test access rate. From the STS-1 Receive OC-12 Transmit To the
Network Element Network Element
6. Ensure the test connections are as shown
in Figure 18. T-BERD 310
7. Verify the LED above the side panel (Side Panel)
OC-1/3 RECEIVE, OC-12 RECEIVE, or
OC-12 Receive From the
OC-48 RECEIVE connector is illuminated From the Network Element
if the signal is optical. Network Element OC-1/3 Receive
OC-48 Receive From the
8. At East and West, configure transmit Network Element
signals as follows: OC-1/3 Transmit
to the Network Element
Press Setup switch; select SONET TX.
Press MODE; select signal rate
(STS-1 or OC-1/3/12/48). Figure 18:
Verify the LASER ENABLE button is
illuminated if the signal is optical. Connections for testing SONET path continuity
Press PATTERN; select DS1 ASYN
INT, DS3 ASYN INT, CONCAT(3c),
CONCAT(12c), or CONCAT(48c).
Press SONET TRANSMIT TIMING;
select DS1 BITS CLK. 11. At West, configure the transmitted path 2. At East and West, examine the
trace message as follows: SONET LEDs.
Press AUX. Verify no red LEDs are illuminated.
Press MODE; select SONET TX. Verify the following SONET LEDs are
This requires an external clock
Press PATTERN; select PATH TRACE. illuminated (green):
source, synchronized to the
Press RESULTS I arrowed switch; SIGNAL PRESENT, FRAME SYNC, and PATH PTR
SONET network, to be connected select USER 3. PRES and also VT PTR PRES will illuminate if a DS1
to the bantam DS1 BITS CLOCK Press AUX to exit. payload is being tested, CONCAT PAYLOAD will
connector on the side panel of 12. If the transmit signal is OC-3/12/48 with illuminate if OC-3c/12c/48c is being tested.
a DS1 or DS3 payload at East and West, 3. At East and West,
the T-BERD 310. If a clock is not
select the STS-1 channel as follows: Press RESULTS I blank switch;
available, then RECOVD timing
Press Channel Control switch; select SUMMARY.
can be used, but only if it can be select SONET-STS. Verify RESULTS I window indicates
verified that the device under Press DROP switch; select the STS-1 “ALL RESULTS OK”.
test is timed to the BITS clock. channel which maps the DS1 or 4. At East and West, verify timing of the
DS3 payload. signal as follows:
Press INSERT switch; select the same Press DISPLAY HOLD.
STS-1 channel as above. Press RESULTS II blank switch;
9. If testing DS1, perform this step.
Otherwise, skip this step and proceed 13. For all signal rates, at East and West, select SECTION.
to Step 10. configure receive signals as follows: Press RESULTS II arrowed switch;
At East and West, configure the transmit Press DS3 SOURCE; select SONET. select SON RX FREQ.
signal using the 310-1 lid Press Setup switch; select SONET RX. Verify the result is within the range
as follows: Press MODE; select signal rate (STS-1 according to the following table,
Press 310-1 MODE; select T1 D4. or OC-1/3/12/48). depending on the line rate.
Press 310-1 PATTERN; select 3 IN 24. Press PATTERN; select AUTO.
Press 310-1 TRANSMIT TIMING; 14. Verify ds1 asyn, ds3 asyn, or concat(3c) Line Rate Min. Freq Max. Freq
select INTERNAL. is displayed (as selected in Step 9). (Hz) (Hz)
10. At East, configure transmitted path trace
message as follows: Test Results STS-1/OC-1 51,838,963 51,841,037
Press AUX. 1. At East and West, verify the LED
OC-3 155,516,890 155,523,110
Press MODE; select SONET TX. above the side panel OC-1/3/12/48
Press PATTERN; select PATH TRACE. RECEIVE connector is illuminated if OC-12 622,067,558 622,092,442
Press RESULTS I arrowed switch; the signal is optical.
select USER 1. OC-48 2,488,279,234 2,488,369,766
Press AUX to exit.
Press DISPLAY HOLD.
15
5. At East and West, PATH EQU BER is less than 1.0 E-10
Press RESULTS II blank switch; PATH BIP ES = 0
select LINE. PATH BIP ESB = 0 If the termination point and
Press RESULTS II arrowed switch. PATH BIP SES = 0 the monitoring point at the
PATH UAS = 0
Verify the following results: mid-span are not co-located,
POINTER JUST = 0 Press RESULTS II blank switch;
select LINE. then two T-BERD 310s will be
POINTER DATA = stable, any value from 0 to 782
Press RESULTS II arrowed switch; needed for this test (one at the
6. At West, verify path configuration verify results: West side and the other at the
as follows:
POINTER JUST = 0 East side).
Press RESULTS II blank switch; POINTER NDF = 0
select PATH. LINE EQU BER is less than 1.0 E-10
Press RESULTS II arrowed switch; LINE BIP ES = 0
select PATH TRACE. LINE BIP ESB = 0 Test Setup
Verify the result indicates: LINE BIP SES = 0 1. Clean all the fiber optic connectors and
The quick brown fox jumps over the lazy dog LINE UAS = 0 test set connectors. Tag optical fibers with
1234567890!@#$%* 10. At East and West, TRANSMIT and RECEIVE designations as
7. At East, verify path configuration shown in Figure 17 on page 14.
Verify no HISTORY LEDs or red LEDs
as follows: are illuminated. 2. At East, the fiber marked RECEIVE
should be connected from the
Press RESULTS II blank switch; Verify RESULTS I window indicates
T-BERD 310 DWDM input port to the
select PATH. “ALL RESULTS OK”.
EDFA monitor jack.
Press RESULTS II arrowed switch;
3. At West, the fiber marked TRANSMIT
select PATH TRACE.
should be connected from the
Verify the result indicates: OC-1/3/12/48 system receiver to the
T-BERD 310: Communications Analyzer Mid-Span T-BERD 310 transmitter.
for SONET, DS3, DS1, & DS0
8. At East and West, BER Testing 4. At West, connect a fiber cable from
the channel output connector to the
Press RESTART to initiate test. Allow The objective of this test is to provide T-BERD 310 side-panel connectors:
to run undisturbed for at least the capability to filter out a single channel and OC-1/3 RECEIVE, OC-12 RECEIVE,
30 minutes. locate the source of the impairment in a DWDM or OC-48 RECEIVE, depending on the
system. An optional EDFA may be required if the test access rate.
9. At East and West, verify results
individual signal strength is -19 dBm or less.
as follows:
(See Figure 19).
Press RESULTS II blank switch;
select PATH.
Press RESULTS II arrowed switch;
verify results:
West East
Transponder Selector
Tx Optical Rx
Optical
MUX Demux
Tx Rx
λn
Test Set
λn
Tx Rx
Figure 19:
Mid-span BER testing
16
5. At East, configure receive signal Press ALARM INSERT select switch;
as follows: select LINE AIS.
Press AUX. The PEAK EXCURSION defines Press ALARM INSERT button.
Press MODE; select WDM RX. the rise and fall in amplitude Verify the SONET NE goes into alarm
Define UNITS: and generates required local alarms.
that must take place for a
Press PATTERN; select UNITS. Verify remote management center
laser line to be recognized. alarms, if applicable.
Press RESULTS I arrowed switch;
The default value for Verify only the LINE RDI LED (red)
select NM or THz.
PEAK EXCURSION is 15 dB. is illuminated.
Define PEAK THRESHOLD and
PEAK EXCURSION: 3. At East, verify AIS results as follows:
17
Appendix A:
Troubleshooting Tips for Optical Testing
T
his appendix provides a list
of items to check when your
test setup or test results do
not match what is described in
this application note.
Table 1:
Optical testing troubleshooting tips
18
Appendix B:
Troubleshooting Tips for DWDM Testing
T
his appendix provides a list
of items to check when your
test setup or test results do
not match what is described
in this application note.
Table 2:
DWDM testing troubleshooting tips
19
Trouble Found Items to Check
Daisy Chain—Bit errors Indicates too many channels may be daisy chained (TTC recommends <7 channels).
are detected at SONET layer • Verify fibers are clean. Polish if necessary.
• Verify test set connectors are properly cleaned.
• Verify connector keys are properly aligned.
• Reduce number of channels being daisy chained.
• Sectionalize errors via end-to-end BERT using the T-BERD 310 SONET capabilities.
End-to-end BERT—Bit • Verify fibers are clean. Polish if necessary.
errors are detected at • Verify test set connectors are properly cleaned.
SONET layer • Verify connector keys are properly aligned.
• Sectionalize errors via mid-span BERT with DWDM drop capabilities.
Mid-span BERT—dB level Indicates there is not enough signal power on the dropped channel.
cannot be recovered at • Verify fibers are clean. Polish if necessary.
SONET layer • Verify test set connectors are properly cleaned.
• Verify connector keys are properly aligned.
• Verify signal power level using the optical power meter on the Optical Media Test
Option (310-16).
Input Power Ranges
OC-1/3 -7 dBm to -35 dBm
OC-12 -8 dBm to -26 dBm
OC-48 -9 dBm to -28 dBm
• Amplify the signal where necessary to ensure sufficient signal power.
Table 2:
DWDM testing troubleshooting tips
(continued)
20
Appendix C:
Nominal Central Frequencies
(Taken from ITU-T Recommendation G.692)
Frequencies (THz) for spacings Frequencies (THz) for spacings Wavelengths (nm)
of 50 GHz of 100 GHZ and above
Table 3:
Nominal central frequencies 21
Frequencies (THz) for spacings Frequencies (THz) for spacings Wavelengths (nm)
of 50 GHz of 100 GHZ and above
193.85 – 1546.52
193.80 193.80 1546.92
193.75 – 1547.32
193.70 193.70 1547.72
193.65 – 1548.11
193.60 193.60 1548.51
193.55 – 1548.91
193.50 193.50 1549.32
193.45 – 1549.72
193.40 193.40 1550.12
193.35 – 1550.52
193.30 193.30 1550.92
193.25 – 1551.32
193.20 193.20 1551.72
193.15 – 1552.12
193.10 193.10 1552.52
193.05 – 1552.93
193.00 193.00 1553.33
192.95 – 1553.73
192.90 192.90 1554.13
192.85 – 1554.54
192.80 192.80 1554.94
192.75 _ 1555.34
192.70 192.70 1555.75
192.65 – 1556.15
192.60 192.60 1556.55
192.55 – 1556.96
192.50 192.50 1557.36
192.45 – 1557.77
192.40 192.40 1558.17
192.35 – 1558.58
192.30 192.30 1558.98
192.25 – 1559.39
192.20 192.20 1559.79
192.15 – 1560.20
192.10 192.10 1560.61
192.05* – 1561.01*
192.00* 192.00* 1561.42*
191.95* – 1561.83*
191.90* 191.90* 1562.23*
191.85* – 1562.64*
191.80* 191.80* 1563.05*
191.75* – 1563.45*
191.70* 191.70* 1563.86*
191.65* – 1564.27*
191.60* 191.60* 1564.68*
Copyright 2000, TTC, a division of Dynatech, LLC. All rights reserved. TTC and T-BERD are registered trademarks of TTC. All other trademarks and registered trademarks are the
property of their repective owners. Specifications, terms, and conditions are subject to change without notice.
22
Notes:
23
World Headquarters
20400 Observation Drive
Germantown, Maryland 20876-4023 USA
Toll Free 1-800-638-2049 • +1-301-353-1550 • Fax +1-301-353-0234
www.ttc.com
North America
United States
Atlanta, Georgia • Chicago, Illinois • Dallas, Texas • Denver, Colorado
East Rutherford, New Jersey • Los Angeles, California • Roanoke, Virginia
San Diego, California • San Francisco, California • Terre Haute, Indiana
Canada
Calgary, Alberta • Laval, Quebec • Vancouver, British Columbia
Toronto, Ontario Toll Free 1-888-689-2165 • +1-905-812-7471 • Fax +1-905-812-3892
International
Australia
Melbourne +61-3-9563-4800
Sydney +61-2-9926-1447
Benelux +32-15-28-7686
China
Beijing +86-10-6460-5258
Hong Kong +852-2892-0990
Shanghai +86-21-6255-2333
France +33-1-39-30-24-24
Germany +49-6172-5911-00
United Kingdom +44-1189-759696
European Freephone +800-TTC-UKTAC
(+800-882-85822)
International Distributors
Argentina • Austria • Brazil • Chile • Colombia • Costa Rica
Czech Republic • Denmark • El Salvador • Finland • Hungary
India • Indonesia • Ireland • Israel • Italy • Japan • Korea
Malaysia • Mexico • Norway • Peru • Philippines • Poland
Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa
Spain • Sweden • Switzerland • Taiwan • Thailand
United Arab Emirates • Venezuela
TB-310OPTDWDM-A-4/00
24