Beruflich Dokumente
Kultur Dokumente
Excitation Basics
MPW Release 10 March 2003 Operation and Maintenance Training 1 UNITROL® 5000
MPW Release 10 March 2003 Operation and Maintenance Training 2 UNITROL® 5000
The inducing of a voltage using the electromagnet is said to “EXCITE” the machine, and therefore the
system that supplies the current is called an Excitation System.
The amount of current supplied directly influences the strength of the electromagnet and therefore the
level of the induced voltage on the stator.
For a synchronous generator, the field winding (the electromagnet) is always on the rotor. This is
because the amount of current is smaller than on the stator and is therefore easier to arrange on a moving
shaft. (e.g. by use of brushes)
It is also possible to eliminate the need for brushes and large scale power electronics by use of an exciter
machine, and diodes. (see configuration section)
However, with modern Power Electronic equipment it is possible to take advantage of the superior
control characteristic of a direct excitation. This is usually cheaper than buying a second machine.
Excitation
System Voltage
Regulation Voltage
Current
Control
Power Rotor Current
Supply Production
MPW Release 10 March 2003 Operation and Maintenance Training 3 UNITROL® 5000
In any excitation system, several components can be identified. Depending on the age and type of the system, the equipment
may vary greatly, however the basic components can still be classified.
Power Supply
The excitation system needs a power supply in order to produce a current. There are many different configurations.
Shunt Supply – The supply is taken from the machine terminals.
Line Supply – The supply is taken from an auxiliary supply.
Permanent Magnet Generator – A small permanent magnet generator is mounted on the same shaft as the main machine.
Current Control
No matter how the current is produced, there must be some method of controlling how much current is produced. In the case
of Unitrol 5000 this is a state of the art control system, but in other the systems this could be very different. In the case of a
Variac, this might be a wheel mounted on the front of the device.
Voltage Regulation
Voltage regulation in Unitrol 5000 is done in the control system by the Automatic Voltage Regulator (AVR).
In some older systems, the AVR was a separate control unit, but in Unitrol 5000 it is integrated.
In some systems the voltage regulation might have been done by the operator continually monitoring the voltage.
MPW Release 10 March 2003 Operation and Maintenance Training 4 UNITROL® 5000
In any excitation system, the principle function is produce the field current.
In Unitrol 5000 excitation systems there is a high speed sophisticated control system.
Due to the fact that the excitation systems is in a perfect situation to monitor the operation of the
machine, many protective features are included on board the control system.
Turbine Generator
Field Generator
Current Voltage
Excitation
System
MPW Release 10 March 2003 Operation and Maintenance Training 5 UNITROL® 5000
AC & DC
HV SYSTEM HV- BREAKER AUXILIARY
SYSTEMS
CONTROL
AUX. SYSTEMS
PROTECTION
TRANSF
.
GOVERNOR
1
GENERATOR
1 BREAKER
PT’s
&
CT’s
SYNCHRONIZING
SYNCHRONOUS EXCITATION
TURBINE GENERATOR SYSTEM
STAR
POINT EXCITATION
CUBICLE TRANSFORMER
MPW Release 10 March 2003 Operation and Maintenance Training 6 UNITROL® 5000
The following diagram shows the main components installed in a power station with their connections to
a static excitation system, as shown in this example.
Inputs to the excitation system:
- The main supply to the excitation system is taken directly from the generator
terminals via an excitation transformer.
- In order to regulate the generator voltage, this is picked up from the
generator terminals via converters.
- To control the excitation, the control commands are passed to the excitation
system from a higher-level control system.
Outputs from the excitation system:
- The main output from the excitation system is the exciter voltage, which is
passed to the rotor winding via slip rings.
- Messages from the excitation system to the higher-level control system such
as alarm and status messages.
Excitation
System
MPW Release 10 March 2003 Operation and Maintenance Training 7 UNITROL® 5000
A regulated synchronous machine coupled to the network can be represented in simplified form.
The synchronous machine represents the regulated object. All other components together form the
regulator or excitation system. In parallel operation with the network, the network influences the
behaviour of the closed regulating circuit and in this sense acts as an external interference variable.
The characteristics of the synchronous machine and the network are largely determined by the
equipment that has been used.
i.e. The generator, the transformers, the transmission cables, etc.
The excitation system can be used to set up the steady state operating conditions of the machine.
In transient conditions, the excitation only allows an adjustment of the overall behaviour in the sense of
a technical optimisation. Optimisation is done during commissioning.
Steady State
A point around which
changes may take place,
but to where there is a
general tendency to return.
Transient
The relatively short period
of change that follows any
event.
MPW Release 10 March 2003 Operation and Maintenance Training 8 UNITROL® 5000
In examining the behaviour of the regulated synchronous machine, a distinction must be made between
the
Steady State behaviour, and
Transient or dynamic behaviour of the synchronous machine.
Electrical Behaviour
Machine Reactive
Voltage Power
Mechanical Behaviour
Machine Real
Speed Power
MPW Release 10 March 2003 Operation and Maintenance Training 9 UNITROL® 5000
The generator is where the conversion between mechanical energy and electrical energy takes place.
The generator has displays both electrical and mechanical behaviour. As this is the place where the
conversion takes place it makes things simpler if a separation is made between mechanical and electrical
behaviour.
Electrical Behaviour
Excitation Current
Machine Voltage
Reactive Power
Mechanical Behaviour
Machine Speed
Machine Torque (= Power in the per unit system)
In many ways there is a strong analogy between the mechanical behaviour and the electrical behaviour
of the machine, however they are most definitely separate.
It would be very nice if it were possible to make real power using the excitation system!!!!
(You could then make real power without the need for coal, oil, gas etc.)
Release 10.06.2004 Excitation Basics Page 9
U n itro l 5 0 0 0 T rain in g
Solid Pole
Machine
Salient Pole
Machine
South
MPW Release 10 March 2003 Operation and Maintenance Training 10 UNITROL® 5000
To form a generalized equivalent circuit for a synchronous machine of any construction it is necessary to
consider that the machine has two axis. A direct axis, and a quadrature axis.
The direct axis arises from flux that flows directly from the pole face to the stator winding.
The quadrature axis arises from flux that flows perpendicular to the pole face.
The solid pole machine has a smooth cylindrical profile. The flux can therefore flow between the rotor
and the stator in any direction with similar difficulty, because the main obstacle is the air gap.
For a salient pole machine, the air gap in the direct axis is quite small, however the air gap in the
quadrature axis is significant, and therefore it becomes necessary to produce a different (and more
complex) equivalent circuit.
The magnetic
flux between
rotor and
stator has a
small air gap
in both the
quadrature
and direct
axis.
• High speed application for speed range > 1500 rpm
• Xd and Xq are similar
MPW Release 10 March 2003 Operation and Maintenance Training 11 UNITROL® 5000
Xd = Xq = Synchronous Reactance
The difference between the solid pole machine and the salient pole machine makes an important
difference to the operating characteristic of the machine.
For the moment, we shall study the equivalent circuit of the solid pole machine, but later on we return to
the salient pole machine in order to examine the differences.
Q-Axis Xd
D-Axis
Ep
For the solid pole machine the equivalent circuit diagram is simply an EMF and a synchronous
reactance.
MPW Release 10 March 2003 Operation and Maintenance Training 14 UNITROL® 5000
1. No Load Operation.
2. Machine loaded and operating in parallel with
other machines on a large network.
3. Machine loaded and operating alone with load
= island operation.
MPW Release 10 March 2003 Operation and Maintenance Training 15 UNITROL® 5000
Now that an equivalent Steady State Equivalent diagram has been made, we can consider the circuit in a
few different operating modes.
1. No Load Operation.
The machine runs at nominal speed and the generator circuit breaker is open.
The speed of the machine is set by the turbine.
3. Island Operation
The machine is connected to a load without any other generator being connected.
The frequency and voltage depends on the Generator AND the Load.
(In actual fact both of these quantities must be actively controlled to achieve acceptable operation.)
Ug
Xd Saturation
Ugn
Generator
Ep rated voltage
UG
No Load Operation
At lower values of field current, the relationship between field current and terminal voltage is linear.
However, above a certain level of current, the machine starts to saturate.
Most machines are designed to have the nominal voltage of the machine lying just inside the saturated
region of the characteristic.
In the range up to nominal generator voltage, a more or less linear relationship exists between field
current and generator voltage. When the generator voltage exceeds the nominal value, a saturation effect
takes place which is essentially determined by the design of the stator iron. If one wishes to increase the
generator voltage further, above its nominal value, the field current must be increased over-
proportionately.
Generator On Load
Xd I X tr + ex
G
Network
Ep
UG Ubus
Generator On Load
The machine is now connected to a large network through a step up transformer, and the turbine delivers
a real load (MW).
The internal Emf of the machine is still determined by the excitation current, however the terminal
voltage of the machine also strongly dependant upon the network.
If the machine is under load, a current flows in the stator windings, which causes a voltage drop through
the synchronous reactance. If the excitation current remains constant, the terminal voltage would
therefore be reduced. Here, the excitation system has the function of preventing this drop in voltage by
altering the excitation current.
Generator On Load
Ig 2 * Xd Ig 1 * Xd
Ig 1 * Xd
EM
Ug
F
Ug
1
Ig2
X d
EM
2* δ2
Ig
F
δ2 Ig1
1
δ1
EM
F2 EMF 1
δ1 = EMF 2
MPW Release 10 March 2003 Operation and Maintenance Training 18 UNITROL® 5000
In the above examples we shall assume that to begin with the network load is purely resistive and therefore the
generator current is in phase with the voltage. The voltage taken by the load is assumed to be at a fixed value and
angle, rather like the bus network of a large network. The current flowing in the stator winding causes a voltage
drop across the synchronous reactance Xd, and hence the EMF of the machine may be drawn at an angle delta to
the bus voltage Ubus.
Subsequently the resistive load is increased, and the turbine load is increased to match the load.
We shall consider two cases:
If the increase in turbine power had been greater, then it can be easily seen that it is not possible to draw the EMF
and IXd vectors in such a way that they meet!!! Therefore it is simply not possible to increase the load above a
certain threshold.
"rubber band"
T95_0154.DRW
MPW Release 10 March 2003 Operation and Maintenance Training 19 UNITROL® 5000
The importance of the angle delta can be seen from the previous example.
The drawing of the voltage drop and the EMF is no longer possible when delta reaches 90°. At this
point it would not be possible to remain synchronized with the network.
We could see that if the excitation current is increased, then the situation is changed. The excitation
current therefore provides a synchronizing torque.
We can imagine the rotor of the machine to be connected to the network voltage by an elastic band.
•The strength of the elastic band is dependant on its elastic constant. In the case of the machine, the
elastic constant is variable, and is dependant on the amount of excitation current.
•The extension of the elastic band depends on how strongly it is pulled. In the case of the machine this
is the amount of torque applied to the shaft.
If the excitation current is increased, then the elastic band becomes stronger, and the rotor is pulled back
towards the network voltage.
Md1 ~ If1
Drive torque
δ2 δ1 δ
MPW Release 10 March 2003 Operation and Maintenance Training 20 UNITROL® 5000
For a more mathematical approach, the torque of the machine is given by the above equation.
For each amount of EMF (and therefore excitation current) a curve can be drawn on the Torque vs. delta
graph.
The analogy with the elastic band can be tested using the two curves shown above.
When delta reaches 90°, this point is called the stability limit.
Active
P
Power 1
rated
Drive Limit power
Load angle Pf
limit Field current
Drive Limit limit
Sn
δ
-1 +1
-Q 1 + Q Reactive
xd Ifo power
under over
excited Motor excited
MPW Release 10 March 2003 Operation and Maintenance Training 21 UNITROL® 5000
The entire range of possible stationary operating conditions is usually described by means of the power
diagram. This diagram can be derived from the vector diagram. The vector diagram is multiplied a
vector Ug/Xd.
In order to cancel the effect of voltage on the diagram, the diagram is always drawn at nominal voltage.
If the voltage changes, however, it is important to remember that the size of the drawing itself also
changes by the square of the terminal voltage.
At nominal voltage, the pu current and pu apparent power are the same. The large circle therefore
represents the maximum thermal capability of the stator.
At nominal voltage, the circle with centre 1/Xd is proportional to the pu field current. This circle
therefore represents the maximum thermal capability of the rotor.
The angle delta is between this vector and the reactive power axis. In order to avoid delta approaching
90° only the region to the right of the 1/Xd point is safe.
Normally the turbine rating is beneath the generator rating, so the real power is limited.
active power P
capacitive generator current limiter inductive generator current limiter
MPW Release 10 March 2003 Operation and Maintenance Training 22 UNITROL® 5000
The power chart for a salient pole machine is quite different to the solid pole machine.
MPW Release 10 March 2003 Operation and Maintenance Training 23 UNITROL® 5000
The basic requirements of the automatic voltage regulating systems, which must be fulfilled in a typical network
under stationary conditions, i.e. without faults, are:
1. The voltage at the consumer connection should be kept within acceptable limits.
The consumer operates equipment that is designed to work within a particular voltage tolerance.
2. Stable reactive power distribution in the case of several parallel-operated generators within the power station
must be guaranteed.
Generators can absorb or generate reactive power. In order to have stable operation, it is essential that reactive
power is shared and not merely passed around between generators!
3. The reactive power distribution within the network system should create minimal line losses, with good
stability, also during load changes.
If a network is to be operated efficiently it is essential to have some way of managing the node voltages at
various points in the network. This can be achieved by excitation systems and tap changing transformers.
4. The generator should always be operated within the safe operating limits.
(see power chart)
The Network
A machine may be
2
1 connected to a large and
complex network.
Tie
Regional grid
How can the reactive
power be used to
understand the
Substation relationship between the
machine and the
network?
Power station
T95_01 57.D RW
MPW Release 10 March 2003 Operation and Maintenance Training 24 UNITROL® 5000
The amount of equipment may be vast, and to model the grid behaviour requires a lot of skill and time.
The complexity of the network can be daunting, however equipped with our simple equivalent circuit
and power chart, we can begin to understand how the machine operating point may be determined.
XTr Xe
G
RL UNet
MPW Release 10 March 2003 Operation and Maintenance Training 25 UNITROL® 5000
The machine and the network can be represented by the greatly simplified equivalent circuit shown
above.
The equivalent-circuit diagram shows the generator G, which can also stand for an entire power station,
with the reactance XTr (transformer reactance) between generator terminals and high voltage busbar.
The resulting load impedance ZL relates to this feed point. The rest of the system is reduced to an
external reactance Xe and a voltage of the rigid networks. All power-generating units are united at this
point. The line resistance's in the immediate vicinity can usually be ignored, whereas the capacity of
longer transmission lines must be taken into account.
UG = 1.05 pu UN = 1.0 pu
If reactive power is exported, then the per unit generator voltage will be greater than the per unit
network voltage.
The generator is therefore making a positive contribution to the network voltage. i.e. keeping the
voltage level up.
If the reactive power is measured at the generator terminals, then it is the machine contribution alone
which is considered. The transformer and external reactance will also requires reactive power, and
therefore the net effect may not be a positive contribution.
If the reactive power is measured after the step up transformer, then it is the combination of the machine
+ transformer that is considered.
From the network point of view, it is the measurement after the transformer that should be considered.
UG = 0.95 pu UN = 1.0 pu
If reactive power is imported, then the per unit generator voltage will be less than the per unit network
voltage.
The generator is therefore making a negative contribution to the network voltage. i.e. keeping the
voltage level down.
If the reactive power is measured at the generator terminals, then it is the machine contribution alone
which is considered. The transformer and external reactance will also requires reactive power, and
therefore the net effect may not be a negative contribution.
If the reactive power is measured after the step up transformer, then it is the combination of the machine
+ transformer that is considered.
From the network point of view, it is the measurement after the transformer that should be considered.
P Q
T 9 5_ 01 58.DR W
MPW Release 10 March 2003 Operation and Maintenance Training 28 UNITROL® 5000
One of the functions of an AVR that was identified was to ensure stable distribution of Reactive Power.
At first this may be difficult to understand in terms of voltage and reactive power.
The analogy between the turbine regulator and the AVR can therefore be utilized.
In order to keep a stable frequency, most turbines use a DROOP setting on top of their power regulation.
i.e. If the speed falls, then the governor increases the real power, even if there is a constant power set point.
We shall now look at how the AVR characteristic helps to distribute reactive power using a reactive power droop
setting, also known as Q static.
-Q +Q
In Unitrol 5000 it is possible to use either a positive droop or a negative droop. This is set by a
parameter.
MPW Release 10 March 2003 Operation and Maintenance Training 30 UNITROL® 5000
Two generators operating on the same bus are considered in this example.
The terminal voltage MUST be the same on both machines because they are directly connected.
If the setpoint on machine 1 was larger than on machine 2, then the AVR of machine 1 would keep
increasing its excitation current until eventually the over excitation limit would become active.
In the same way, the AVR of machine 2 would keep decreasing the excitation current until eventually its
under excitation limit would become active.
Reactive power would therefore be passed from machine 1 to machine 2, regardless of network
requirements!
Voltage
-ve Q +ve Q
MPW Release 10 March 2003 Operation and Maintenance Training 31 UNITROL® 5000
There is no point at which the 2 characteristics cross, and therefore the distribution of reactive power
between the machines is undefined.
IQ
Uref1 Uref2
AVR AVR
Generator 1 Generator 2
U
Uref1
Busbar voltage
Uref2
IQ IQ
Generator 2 Generator 1 Q, IQ
MPW Release 10 March 2003 Operation and Maintenance Training 32 UNITROL® 5000
Therefore, it can be said that the reactive power of one machine AS SEEN FROM THE OTHER
machine is opposite.
A droop characteristic is now applied to each of the 2 AVR’s with the same droop characteristic.
The droop characteristic of machine 2 as seen by machine 1 is in the opposite direction as its own.
Voltage
-ve Q +ve Q
MPW Release 10 March 2003 Operation and Maintenance Training 33 UNITROL® 5000
When the two droop characteristics are plotted on the same graph, then there is clearly a cross over, and
therefore a stable operating point can be achieved.
The setpoint can be used in each machine to change the proportion of reactive power taken by each
machine, as well
“Dynamic” Behaviour
What Type of Changes Can be Expected ?
MPW Release 10 March 2003 Operation and Maintenance Training 34 UNITROL® 5000
The steady state behaviour and dynamic (or transient) behaviour has already been introduced.
So far the steady state has generally been considered, but what about transient changes?
For a machine operating on a network, there are many transient conditions taking place.
Every time a person decides to use a lift, or an electric kettle for example a change in load occurs. Of
course, a kettle is generally very small, but what about the start up of a steel mill?
Large changes in load may be accompanied by the starting up of extra power stations, changes in the
nature of the load ie inductive to capacitive. During sudden changes the network voltage, frequency and
load will change.
The turbine itself, may undergo transient changes and therefore the excitation system may have to cope
with the transient change in torque. For example a coal mill in the boiler may suddenly trip, and there
would be a corresponding drop in the torque.
Network faults are also an important change. Sometimes a part of the network will experience a severe
fault, and this may result in large short circuit currents and load shedding. It will be necessary for the
excitation system to cope with the situation.
UG
115% Maximum Voltage = f{insulation}
110% Max Voltage at Nominal Speed
U V/Hz-gradient = dV/df
f
f
100%
MPW Release 10 March 2003 Operation and Maintenance Training 35 UNITROL® 5000
If the voltage of the machine is regulated by a voltage regulator, then the speed can present a problem. i.e. at lower
speeds, more excitation current is required to achieve the same voltage. As we have already seen, the machine
displays saturation above a certain amount of current. The saturation curve becomes flatter at even higher currents.
To avoid the possibility of saturation, Unitrol 5000 uses a software function called a “Volt per Herz” Limiter.
The limitation of machine voltage should be defined according to a speed dependant characteristic.
The characteristic has a cut off point that reflects the insulation limit of the machine. Naturally the insulation
properties of the machine are not speed dependant.
Should the voltage reach the level of limitation, then Unitrol 5000 will automatically take action to ensure that the
voltage does not increase any further.
“Dynamic” Behaviour
Classification of Changes
2. Mechanical Changes.
Speed/Frequency, Torque, Load Angle, Active
Power.
MPW Release 10 March 2003 Operation and Maintenance Training 36 UNITROL® 5000
A distinction can be made between two groups of physical variables, which we will deal with separately,
although they are not wholly independent of one another:
The mechanical and electrical behaviour of the machine is considered independently in the steady state.
In the transient behaviour of the machine, the mechanical and electrical quantities are most certainly
inter-related.
If the force applied to the elastic band is suddenly increased, then as we all know, the load will not just
suddenly find a new equilibrium.
Assuming that the system is “underdamped”, there would be an initial extension of the elastic band past
its steady state resting position. A period of oscillation about the new resting position would then occur,
whereby energy is stored in the elastic band, and then released.
The same applies to the machine. If a change in mechanical load takes place, then energy may also be
stored in the electrical field of the machine and subsequently released.
If = konst. S
∆U = Ig *Xd
XE
Ug Ugo
t
t=0
MPW Release 10 March 2003 Operation and Maintenance Training 37 UNITROL® 5000
The unloaded generator has a terminal voltage Ug which is equal to the induced rotor voltage Ep.
After the circuit breaker S is closed, a reactive current Ig begins to flow immediately and causes a
voltage drop through the generator reactance.
The original magnetic flux, which passes through stator and rotor, cannot change instantly. The
consequence of this is that a contrary current is induced in the rotor circuit via the air gap in order to
compensate the changes on the stator side and maintain the balance of the circulation.
In the simplified equivalent circuit diagram shown, this means that the direct axis reactance Xd is
replaced by the either the transient reactance Xd’, or the sub-transient reactance Xd’’ (see below)
which is 5…10 times smaller than the synchronous reactance Xd.
Note: Most generators have a rotor damper winding. The damper winding is an extra cage type winding
that is not connected to the main winding, and allows an induced current to flow that is related to the slip
frequency between the rotor and stator fields. The induced current helps to keep the rotor synchronized
with the stator, by developing a synchronizing torque. The damper winding may be compared with the
rotor winding of an induction motor.
This winding is responsible for introducing the sub-transient reactance Xd’’
For very fast transient changes, it is this sub-transient reactance which is used.
Ug
static excitation systems
with rotating exciter When an AVR is used,
the excitation current
∆U = Ig *Xd is adjusted to bring
the voltage back to its
original value
Ugo
t
t=0
MPW Release 10 March 2003 Operation and Maintenance Training 38 UNITROL® 5000
For a machine operating with Automatic Voltage Regulation, the transient condition is automatically
compensated.
The initial drop is fixed by the sub/transient reactance of the machine and the generator current.
The regulator reacts to the drop in voltage by automatically increasing the field current, and therefore
returning the voltage to its previous voltage level.
The response of a static excitation system and a rotating exciter machine can be compared in the
example above.
PA = ω· M A I · XD
E · sin δ
PE = U · I = U ·
XD
U
E
Torque Equation
δ
dω
MA - M E = Θ
dt
θ Inertia
ω speed
MPW Release 10 March 2003 Operation and Maintenance Training 39 UNITROL® 5000
The behaviour of the machine when it reacts to a change in mechanical load is quite different.
When the switch is closed, the load current through R1 flows instantaneously.
The turbine response, however is much slower, and the energy being supplied to the load must come
either from stored kinetic energy in the shaft, or from the energy stored in the field of the generator.
(analogous to the stored “elastic band” energy).
If the field energy was kept constant, then all of the energy must be supplied by releasing the kinetic of
the shaft, which therefore causes the shaft to slow down.
Eventually the turbine governor will react to the fall in speed, and the turbine power will be increased.
In Unitrol 5000, there is a feature called the “Power System Stabilizer”. This purposefully uses the
excitation system to smooth out the exchange of energy between the shaft and the system using the
energy stored in the field of the generator.
Ug
Overvoltage relay
with constant field current
with AVR (static excitation system)
Uo
IQ x Xd "
t
t=0 1 Sec.
MPW Release 10 March 2003 Operation and Maintenance Training 40 UNITROL® 5000
Load Rejection
If there were to be a load rejection (the generator circuit breaker opens) at the nominal operating point of
the generator then you can easily see that the field current would be much too high!
An important function of the AVR is therefore to bring the voltage back to a safe level in the event of
such a load rejection.
The initial rise is dependant on the Xd’’ of the machine, but again the AVR can take fast corrective
action to ensure that the over voltage trip level is not reached.
MPW Release 10 March 2003 Operation and Maintenance Training 41 UNITROL® 5000
The protection system normally requires that current flows into the
fault in order to correctly detect WHICH line should be
disconnected.
It is therefore essential that the excitation system supports the
system voltage during the period that the “selection” takes place.
MPW Release 10 March 2003 Operation and Maintenance Training 42 UNITROL® 5000
Faults
During a distant network fault, it is very important that the network voltage is maintained.
If a fault occurred, then the normally the generator voltage would fall and the generator current would
increase.
If this were allowed to continue, the protection relay may not correctly detect where the fault has
occurred, resulting in the disconnection of more equipment than was actually necessary.
The AVR helps the selection, by feeding current into the fault.
t
t=0 1 sec
Fault causes over
current and under Voltage support enables Fault clearance results in
voltage the network protection to reduction of load and a
clear the fault corresponding rise in voltage
MPW Release 10 March 2003 Operation and Maintenance Training 43 UNITROL® 5000
Thyristors
(Or switch)
V = -L dI/dt
Resistor
Another function that an excitation system has to be able to cope with is de-excitation.
If the current is interrupted for any reason, the inductance will produce an extremely large voltage to try
and maintain the flow of current.
In Unitrol 5000 the crowbar is in fact a carefully calculated non-linear resistance. A thyristor switch is
used to control when the resistors are connected.
Normal De-excitation
Normally de-
excitation of the
field is made by
“Inverting” the
converter.
This is the fastest
way of reducing the
field current.
MPW Release 10 March 2003 Operation and Maintenance Training 45 UNITROL® 5000
Emergency De-excitation
Crowbar De-
excitation occurs
in the event of
field breaker
opening,
excitation tripping
or field
overvoltage.
MPW Release 10 March 2003 Operation and Maintenance Training 46 UNITROL® 5000
De-excitation by crowbar is done in the event of a trip because it provides a fail safe method.
i.e. If the excitation system is not functioning correctly, then the crowbar provides secure de-excitation.
If for example there were thyristor failures, then inversion would no longer be possible.