Sie sind auf Seite 1von 6

TANGEDCO

FROM TO
Assistant Engineer The Asst. Executive Engineer
O&M / TANGEDCO O&M / TANGEDCO
Koovathur Cheyyur.

Lr No: AE / O&M / KOOVATHUR / F.DOC / Pro. No / 2018 date . .2018


Sir,

Sub: Elecy:- CEDC --- Koovathur Section EOS to 1 No HT Sc to M/S. Mailam


Murugan Mines for a demand of 1000 KVA at Nerkunapattu village –
Estimate submission reg.

************

I am herewith submitting the estimate for EOS to 1 No HT Sc to M/S. Mailam


Murugan Mines for a demand of 1000 KVA at Nerkunapattu village, Cheyyur TK
Kancheepuram DT. The Estimate cost works out Rs 9409190 Gross & Rs. 9310600 Nett
Board side and Rs. 98590 Consumer side.

Hence, the estimate may kindly be sanctioned and communicated early please

Encl.:-
1. FR – 3 set
2. Estimate in Triplicate.
REPORT ACCOMPANYING THE ESTIMATE

1 SCOPE

This proposal envisages extension of EOS to 1 No HT Sc to M/S. Mailam Murugan Mines for a
demand of 1000 KVA at Nerkunapattu village Cheyyur TK Kancheepuram District

II Point of Supply

The proposed load of 1000 KVA Load will be connected in the newly proposed 11 KV
feeder fed off from Adaiyalachery 33/11KV SS

III Main Features:-

The above extension involves erection of the following main features.

1. Erection of 11 KV Line with AAAC 7/3.15 conductor from SS to the Location


No:158 to a distance of 1 8818 meters.
2. Introduction of Newly VCB for extension of 11 KV to M/S. Mailam Murgan
Mines
3. Laying of 11 KV UG cable 3 X 120 Sq. mm XLPE cable for the distance of 500
meters
4. Erection of 1 No 11 KV DP Structure at Location “F” with 11 KV Metering
arrangement
5. Erection of 3 Nos. Newly 11 KV AB switch at Location “G”, “H”,:I”

Resason for Erection of 11 KV Feeder at Adaiyalacherry SS

New 11 KV feeder is to be erected from Adiyalacherry SS as the Industrial Feeder from 110/11KV
Vellur SS has a voltage regulation of 11.35 evenafter strengthening till tailend for the distance of 14.77
KM. Aslo all the feeders available at 33/11KV Adaiyalacherry SS is being Rural Feeder. Hence a new
11 KV Feeder with VCB is to be erected at 33/11 KV Adiyalacherry SS and the distance of Newly
proposed 11 KV feeder is 6.090KM having voltage regulation 2.33%.
IV List of Party

Sno Name & Address Reg No & CL SF TF Purpose/PR.NO/DATE


Date NO
1 M/S. Mailam Murgan 1000
Mines KVA
Nergunapattu Village
Cheyyur TK
Kancheepuram Dist

V ESTIMATE COST
The Estimate cost works out Rs 9409190/- Gross & Rs. 9310600/- Nett Board
side and Rs. 98590 Consumer side

REFERENCE
 Proposed PSC 9 mtr Pole

Proposed RSJ 42’ Pole

 Replacement of Exg 7.5 mtr and 9 mtr poles into RSJ 42’ Pole at Locs –
52, 53, 54, 55, 56, 57, 58, 59, 60, 61, 62, 72, 73, 74, 75, 76, 77, 78, 117,
118, 119,120, 121, 123, 124, 125, 126, 127, 128, 129

 Replacement of Exg 7.5m PSC piole into Psc 9m Pole at Locs 68, 69, 70,
71, 147, 148, 149, 150, 151, 152, 153, 154, 155.

 Loc-Prop Breaker to Loc F- New Proposed New AAAC 7/3.15 mm


Conductor

 Loc G,H, I – New Proposed AB Switch (DP) %