1. Purpose
This specification concerns the Lube Oil cooling by water circulation.
The purpose of the system is the cooling of the following elements :
Generator bearings lubricating oil,
2. Description
2.1 Constitution
Lube Oil are cooled in paralel.
The off-base cooling system is mainly composed of :
Fin fan cooler modules
An atmospheric expansion tank
All interconnecting piping, instrumentation and valves
c). Instrumentation
Temperature indicator 1A-1B-1C measures the water temp. at fin fan coolers inlet.
Temperature indicator 1A-1B-1C measures the water temp. at fin fan coolers outlet.
Pressure indicator 1A-1B-1C measures the water pressure at fin fan coolers inlet.
Pressure indicator 1A-1B-1C measures the water pressure at fin fan coolers outlet.
Resistance thermal detector 1A-1B- measures the fin fan coolers water outlet
temperature (type : PT100 – 3 wires).
An alarm “High cooling water temperature” is displayed if fin fan coolers outlet water
temperature higher than 45 ̊ C.
An alarm “Cooling water temperature sensor is trouble” is displaied if water
temperature is below 20 C
̊ or above 80 C
̊ .
Each module can be isolated with butterfly valves at the inlet 1A-1B-1C and at the outlet
b). Instrumentation
Level indicator 1A-1B-1C indicates the water level in the expansion tank
The low level switch 1A-1B-1C send an alarm “ expansion tank low water level” on
The GT control panel if the level is under the low level.
Setting point : 200 mm under the centre line of the expansion tank.
3. Fluid
Water Quality and control : according to Gas Turbine Manufacturer specification
Additive : Nalco 2000 as anti-corrosion product for the first filling and the make-up.
Supplier : NALCO COMPANY, Indonesia
4. Reference documents
Performance Data Basis Data for Water Base Generator Cooler Design