Sie sind auf Seite 1von 6

CONDITION BASED RANKING FOR RELIABILITY CENTERED

MAINTENANCE OF CIRCUIT BREAKER

P.K.Pattanaik
Deputy Manager (ELECT.)
Orissa Power Transmission Corp. Ltd. Burla

1. SYNOPSIS 2. INTRODUCTION
This paper deals with the concept of a quantifiable Electrical equipments like Circuit Breakers (CB),
condition assessment, by considering the data of Current Transformers (CT), Voltage Transformers
the circuit breakers in service. By the use of the (VT), Power Transformers (PT) etc are
available advanced techniques/models/methods, considered as the important and costly assets for
the on-line condition data of circuit breakers are generation, transmission, and distribution
obtained. Similarly by the available laboratory set systems. So, the condition assessments of these
up as well as testing methods, different other data high-voltage electrical equipments have become
about the condition of circuit breakers are also the catchword for every electrical utility.
obtained. The data bank is formed with the on line
field data and testing analysis laboratory data. By During service condition, due to change of
these data (Values from different Test methods), environments like voltage, current and frequency
the GMD (Geometric Mean Data) is prepared to parameters, the electrical equipment are
obtain the condition code of the equipments. The subjected with electrical, chemical and
other aspect of the equipment is its residual life mechanical stresses. The condition of the
expectancy. This factor also plays an important role equipment gets deteriorated. According to the rate
to determine the condition code of the equipment. of deterioration, the performance and efficiency of
the equipment is also affected. So it needs
This factor is called Survive factor (  ).
continuous condition monitoring of the materials.
Now, by considering the history, commissioning The different types of conditioning monitoring
data, present technical and non-technical methods are available like 1.On Line Condition
parameters of the circuit breakers the condition Monitoring 2. Off Line Condition Monitoring etc..
code is prepared. This code is used to determine From these methods, the necessary data and test
the ranking of the circuit breakers for values are collected for the preparation of
maintenance. condition code. For thecae of circuit breaker, the
available and suitable testing methods and
The detail preparation of Breaker Condition Code conditioning practices are considered for the
(BCC) and application of the same for finding the preparation of conditioning code, called Breaker
Condition Based Rank (CBR) of the circuit Condition Code ( BCC )
breakers have been focused in this paper.
This technique of obtaining CBR helps to develop 3. BREAKER CONDITION CODE (BCC)
CBM (Condition Based Maintenance), which From the available advanced
becomes economical in comparison to the old techniques/models/methods the condition data of
method i.e. TBM (Time Based Maintenance). the equipment are obtained. To study the status
Using this program, the circuit breaker that /condition, the following steps/methods are
required for immediate maintenance can be usually attempted.
identified easily. So by focusing the identified
 Routine/Annual Testing.
breaker, the reliability will be improved and
 On line condition Monitoring
maintenance cost can also be reduced. In actual
practice the BCC should be prepared annually for  Off line condition monitoring
in service equipment to bring a reference for  On line test analysis
CBM. But sometimes the data that required from  Off line laboratory analysis.
testing methods do not become available in time. The results such obtained are usually compared
Because for few tests, the equipment requires with the previous factors, by considering the
complete shut down, which demands proper standards, reference data etc. of the equipment.
planning for rescheduling of system loads. So Then the data bank protocol is used to determine a
instead of annual preparation of BCC, the same factor called GMD (Geometric Mean Data). The
can be prepared once in two years according to other aspect of the equipment is its residual life
the suitability of system load availability. expectancy. This factor also plays an important role
to determine the condition code of the equipment.
This factor is called Survive factor (  ).

1
The performance and efficiency depends upon
The fundamental theory of obtaining the the loading pattern on the equipment. For the
equipment condition code can be formulated by case of circuit breaker the loading on the
the following rules. equipment is considered as the pattern and the
Breaker Condition Code (BCC) = D  magnitude of the current flow through the breaker.
Every circuit breaker is rated with certain value of
D = Geometric Mean Data (GMD)
Normal current (Normal current of 145 KV Circuit
 = Survive Factor breakers is 2000 Amp.)
3.1 GMD (Geometric Mean Data) In actual practice, the loading pattern on the
It is the Geometric mean of the Data factors, such Circuit breaker depends upon the requirement of
obtained from the different test results, analysis the circuit behavior. So as per the loading of the
and methods of the equipment. current this factor can be decided to determine
GMD = (D1 x D2…….. Dn)1/n the survive factor. It is calculated as follows.
D1 = Data Factor of the 1st type test result.
(Ave. Current Flow from the Comm. Date)
 Obt . Data  Comm . Data  L=
= (Normal Current of the Circuit Breaker)
(Standard Data) 2
3.2.2 Service Factor (S)
D2, D3 ………… Dn = Data Factors for 2nd, 3rd, nth The equipment suffers to withstand numerous
Type of test results. stresses, while it is kept in working condition.
These stresses are of thermal, electrical and
It may be noted here that determination of GMD,
mechanical in nature and cause the deterioration
completely depends upon the choice of the utility.
of the equipment. So, for calculation of survive
According to the availability and practice of the
factor, the period of working condition and the
utility, the quantum of data factors is decided for
period of Non-working condition like maintenance
obtaining the condition code. The accuracy of the
condition and Shut down Condition are also to be
code depends upon the number of the data
considered. It has been formulated below.
factors i.e more the data factors taken into the
account, increases the accuracy of the condition (Total Time Period, that equipment in
code. Service)
S=
3.2 Survive Factor (  ):
(Total Time Period, not in service or
Before commissioning of the equipment, generally period of maintenance)
different pre-commissioning tests are carried out.
After obtaining the successful and suitable test
results, the equipment is taken into the service. 3.2.3 Temperature Factor (T):
But after commissioning and during service Ageing characteristic of oil/paper insulation mainly
condition, due to the change of different depends upon the temperature such developed
parameters the survival of the equipment is inside the equipment. The origin of temperature
affected. By considering these parameters the rise, results due to abnormal loading, imperfect
condition code of equipment is determined. The design and environmental conditions on the
factors are described below. equipment. For the case of Circuit breaker the
 Loading Factor (L). flow of current plays the role of loading pattern on
 Service factor (S) the system. So, temperature factor is also
 Temperature factor (T) considered for obtaining the survive factor and
 Fault factor (F) described as follows:
 * Other Factors (K)
( Ave. Min. Temperature from the
The survive factor (  ) is obtained by taking the comm.. date )
T=
5th root of all the possible products of five factors
( Ave. Max. Temperature from the
such described above.
comm.. date )
δ  (LSTFK * )1/5 3.2.4 Fault Factor (F): -
 The concept of obtaining this factor depends The Short Circuit fault (External close in short
the choice and availability of the deciding circuit) and continuous over loading situation of
factors of the utility. It is also obtained by equipment, the current on the equipment
taking the nth root of all the possible products becomes more than that of the rated value.
of ‘ n’ factors as required for deciding this Because of this, the Radial and Axial forces act
factor (K). on the equipment and result the deterioration of
the condition of the equipment.
3.2.1 Loading Factor (L)

2
The magnitude of the fault current depends upon practice the BCC should be prepared annually for
the S.C. Fault MVA of the system. Because of in service equipment to bring a reference for
the use of suitable protective relays the rating of CBM. But sometimes the data that required from
deterioration does not become severe and testing methods do not become available in time.
remains within the limit of design value. But for Because for few tests, the equipment requires
every situation of fault tripping, the condition of complete shut down, which demands proper
equipment is hampered. planning for rescheduling of system loads. So
instead of annual preparation of BCC, the same
So, Fault factor also adjudges the quantum of can be prepared once in two years according to
survival and calculated as follows: the suitability of system load availability.
(No. of fault tripping x Fault Current)
F= 4.1 Advantages: -
(Short Time Current withstanding  Reliability of the equipment rises.
Capacity)  Maintenance cost becomes less.
 Maintenance intervals are increased.
3.2.5 Other Factor (K)  Maintenance as per requirement is done.
The decision of using this factor for electrical  Life of equipment increases.
equipment in addition to the above-described  Preparation of Data Bank becomes helpful for
factors depends upon choice/practice of the future reference.
utilities/organizations. Sometimes according to
the type of equipment, different other factors are
also considered for Survive Factor. For example, 5. PRACTICAL STUDY OF BCC
flux factor may be taken into account for the For practical study and preparation of BCC, the
equipment like generator, transformer. For the circuit breakers of the selected zone are taken
case of Circuit Breaker the characteristics of into account. Preferably the equipments of same
Insulation can be taken as the additional factor for make with same specification should be selected
calculation. For oil insulation, the factors like I.R for the study. For example the equipments on 220
Value, BDV and P.I of the same are considered KV systems should be categorized under a
particular selection. Similarly the other voltage
for the calculation. # But for other quenching class equipment to be considered under other
medium like SF6 gas, vacuum etc.. this factor is selection. Sometimes the similar rating
not taken into account. equipments are not made available for the
# When this factor is not taken into the comparison. Such situation can be managed by
calculation, the survive factor is calculated adopting the proportionate value for the
with the available four factors and the fourth calculation.
root is accordingly taken to calculate the
survive factor(  ) 6. CONDITION ASSESSMENT TECHNIQUES
Every circuit breaker has different mechanism
4. CONDITION BASED RANKING: - that needs to be maintained for fault free
A data Protocol is formed by the logarithms of the operation. On the basis of working operation the
data that made suitable from different maintenance practice the circuit breaker can be
test/methods/analysis used by the organizations. classified with the following categories.
Now the BCC that prepared by the data protocol 1. Maintenance of Electrical Controlling Circuit
becomes helpful for ranking the equipment to 2. Maintenance of Operating Mechanism
declare for maintenance. So, this new method of 3. Maintenance of Quenching medium
CBM (Condition Based Maintenance) becomes 4. Maintenance of Other supporting Mechanism
economical in comparison to the old method i.e. 6.1 Maintenance of Electrical Controlling
TBM (Time Based Maintenance). Moreover Circuit
because of reduced budget, reduced working The electrical controlling circuit includes different
personnel and growing of electrical equipment operational circuit for correct working of the circuit
population the utilities fail to maintain the breaker.
condition of the equipment in time, for which the
maintenance interval time increases.  Electrical Closing circuit ( Remote and Local )
Unfortunately as maintenance interval is  Electrical Tripping Circuit (Remote and Local )
increased, the equipment reliability becomes  Protection Tripping Circuit
compromised. The best approach to overcome  Trip Coil Supervision Circuit
this shortcoming is CBM (Condition Based  Pole discrepancy operational circuit
Ranking) Using this program, electrical equipment  Anti-Pumping Operation circuit
that required for immediate maintenance can be  Auto Reclosure Circuit.
identified easily. So by focusing these identified
equipment, reliability will be improved and All the electrical controlling circuits as described
maintenance cost can also be reduced. In actual above include different electrical items like

3
contactors, relays, switches etc... For correct above can not be exactly selected for the study.
operation of the circuit, these items are needed to As per the choice and available methods of the
be monitored for its healthiness in the scheme. concerned utility, the BCC for the set of Circuit
The monitoring and maintenance practice of Breakers can be chosen for the study.
these items does not come under the BCC.
Rather it is covered under the fault finding study 6.2.1 Notes on Dynamic Contact Resistance
of the circuit. These items do not get disturbed Measurement
physically for the operation of the scheme. But DCRM is the technique for the measurement of
due to looseness or wrong voltage feeding of the Contact Resistance of the Main Contact during
voltage the electrical items may fail to work. For the operation of the Circuit Breaker. The
such situation, the correct supervision, diagnosis Resistance versus time data provides the useful
and proper monitoring can help to rectify the information on the condition monitoring of the
problems in the circuit. So preparation of the code circuit breaker. The data such obtained can be
(BCC) for these elements do not hold good. compared with the pre- commissioning data of the
circuit breaker. The standard data can also be
6.2 Maintenance of Operating Mechanism referred to obtain the Data factor of the particular
Operating mechanism includes the mechanical breaker. Finally the obtained data factor can be
items like springs, cylinders, cams, pistons, used for the preparation of GMD and BCC of the
latches, pins etc.. This mechanism also includes breaker.
electrical items like Closing Coil and Tripping 6.2.2 Notes on Contact Travel Measurement
Coils etc.. According to the type of the Circuit Circuit Breaker Analyzer is used to determine the
Breaker the operating medium is classified as contact travel of the operating rod and also the
follows actual travel of the main insertion contacts. The
 Pneumatic mechanism ( Air Pressure is used set of transducers and fixtures are fitted to the
for the operating medium) operating mechanism or in the interrupting
 Hydraulic Oil ( Oil pressure is used for the chamber to record the contact travel. From the
medium data obtained the other factors like Contact
 Spring-Spring Mechanism ( Potential energy velocity, acceleration etc.. are also calculated for
of the Springs are used as the medium ) the comparison with the pre-commissioning data.
Similarly by the use of standard values, obtained
The correct adjustments, settings and installations value and commissioning value, the data factor
of these items under the operating mechanism for preparation of the GMD and BCC can be
provide the smooth operation of the circuit calculated.
breaker. But due to mechanical movement of
these items, different wear and tear results in due 6.2.3 Notes on Operating Time Measurement
course of working operation. So the condition The disturbance and displacement of the
monitoring of the mechanism can provide the elements used in the operating mechanism during
status of the equipments associated in the the operation of the breaker affects the operating
operation. time of the breaker contact. The closing, opening
(Tripping) and Close Open (CO timing) of the
Some of the techniques that to be used for contacts are changed. So by the measurement of
condition assessment of Circuit breakers are the timings of the contacts, the intensity of the
stated below. disturbance can be assessed. This method of
 Dynamic Contact Resistance Measurement monitoring and the values such obtained can be
( DCRM) used for the preparation BCC. According to the
 Contact Travel Measurement data, the problems in the mechanism like
 Contact Resistance Measurement alignment of contact, adjustment of moving rod
and replacement of faulty parts can be attended.
 Tan delta Measurement
It is also important to measure the timings of the
 Speed and time Measurement of Main and
auxiliary contacts, because these contacts are
auxiliary Contact
also taken in the electrical operating circuit. The
 Trip/ Close coil Current and resistance adjustment in the link rod can manage the
measurement. problem of the auxiliary contact.
 Mechanical Operation Test (Vibration
Measurement) 6.2.4 Notes on Trip/ Close coil Current and
Resistance measurement.
These described techniques are the usual The operating coil mechanism contains mainly of
available methods for the status measurement of housing with an electrical coil. The operation of
the circuit breakers. But different Power utilities the Coil and consequent operation of the
adopt their own selected and suitable methods for mechanism depends upon the current in the coil
condition assessment of Circuit breakers. So the and the movement of the plunger upon the latch
particular and defined methods as described of the operating mechanism. Sometimes due to

4
incorrect current through the coil or mis- available that produces a tuned sound and varies
adjustment of the gap of the plunger, causes as per the intensity of leakage. This detection
abnormal operation or non-operation of the easily helps to monitor the leakage for quick
breaker. So the study of the associated rectification.
parameters like resistance measurement, current
measurement from correct application of the SF6 is an inert and stable gas, but decomposes
supply voltage and the gap measurement of the under heavy discharging condition after a long
plunger can indicate the status of the operating period of arching. The presence of moisture in the
mechanism. This monitoring method is quite SF6 gas causes chemical degradation, develops
helpful for obtaining the maintenance requirement corrosion in the interruption chamber and affects
of the circuit breaker. the insulation. During chemical reaction some
components like Hydrogen fluoride (HF), H2SO3
6.2.5 Notes on Mechanical Operation Test etc... are resulted and harmful for the insulation.
(Vibration Measurement)
The operation of the breaker and the vibration on As these chemicals cause degradation of
the system can also be considered as one of insulation and corrosion in the chamber,
techniques for monitoring of the status of the monitoring of moisture content in SF 6 is very
operating mechanism. The vibration during important. The SF6 dew point Measurement
closing and opening operation can be recorded by method monitors the availability of moisture
using accelerometers on the system. The content in the gas.
vibration signature such obtained can be
compared with the reference signature. As per the To maintain the moisture level low now-a-days a
variation in the comparison, the problems in the good quality absorbent is used in the apparatus to
mechanism like the mechanical malfunction, remove gaseous decomposed bi-products. So the
excessive contact wear, mis-alignment of quantity of bi-product is remained very low.
mechanism and problem in damping system can
be detected and corrective action can be taken 6.4 Maintenance of Other supporting
accordingly. The data such obtained can also be Mechanism
used for the preparation of the BCC. Every Circuit Breaker has some other supporting
equipment to satisfy the working operation of the
6.3 Maintenance of Quenching medium system. These equipments need to be maintained
Every circuit breaker has certain quenching for correct operation also. These items are as
medium to puff up the arc developed during the follows
operation of main contact. According to the use  Different micro switches, operation switches
of this medium, the breaker is named. Usual  Indicators
quenching mediums are as follows  Control valves
 Oil Medium  Auxiliary switches
 Vacuum  Thermostat, heaters
 SF6 ( Sulfur Hexafluoride)  Containers, Covers etc..
For higher voltage range, SF6 gas is used as the  Holding Items like screw, clamps, bolts etc…
arc-quenching medium in a hermetically sealed  Terminal blocks
chamber. SF6 gas is extensively used now-a-days,
due to its inherent property of immunity to the These items are also to be maintained properly,
climatic and environmental condition. It has other because the status of these items also affects the
advantages such as it is electronegative in nature operating mechanism of the circuit breaker.
with high quenching property and high dielectric
strength. 7. PREPARATION OF BCC
For monitoring of this medium the following As per the normal practice it is seen that power
techniques are used utilities adopt the maintenance techniques as per
 SF6 gas leakage rate Measurement the recommendation of the manufacturers or
according to the time schedules, mentioned in the
 SF6 dew point Measurement
reference catalogues/manuals. It is also seen that
the maintenance group adopt the maintenance
The SF6 gas once filled in the interruption
activities with out knowing the consequence of the
chamber are needed to be maintained in dry
end results. So this method of TBM (Time Based
condition. The leakage of the same if any is to be
Maintenance) does not help much for actual
arrested properly. The leakage is monitored and
maintenance of the electrical equipments. More
detected by the suitable leakage detector. If
over it is also found that most of the equipment do
detected SF6 is more than 10 ppm, the joint is
not show any abnormality during the normal cycle
considered as the leaking joint, needs to be
of time base maintenance program. So
attended for its arrest. Some detector is also
maintenance of the equipment by the TBM

5
method becomes useless and costly in
comparison. Now the CBM (Condition Based 8. CONCLUSION:
Maintenance) method becomes advantageous to For preparation of BCC, the survive factor (  )
the TBM. plays an important role. Sometimes for the
determination of its associated factors,
Based on the described theories like GMD, assumptions are taken for the case of any non-
Survive Factor and the involved Condition availability of the data. However the condition
Assessment Techniques, the practical study for Based Ranking (CBR) becomes quite economic
obtaining Condition Code of the Circuit Breaker for the maintenance of the equipment. And also
can be done. becomes helpful to maintain the data bank of the
Breakers.
7.1 Limitation of the BCC
The preparation of BCC does not hold good for
the following conditions.
 By the method of condition Assessment
Techniques, sometimes the values such
obtained become severe and exceed the
allowable limit of the standard. Such severity
condition must be treated separately and the
action towards the maintenance of those
equipments to be attended immediately
without proceeding the CBR (Condition Based
ranking) for the maintenance practice.
 Some of the condition techniques and testing
methods do not provide any absolute
data/value to decide the status of the
equipment. The results obtained directly
decide the working condition of the
equipment.. For such case either the
equipment is declared faulty or healthy. So
the calculation of the BCC does not hold
good.
 Some case recommendations by the
manufacturer and maintenance practice there
in becomes economic as compared to the
BCC method of Condition Based Ranking of
the Circuit Breaker. For such case also this
method does not hold good.

Das könnte Ihnen auch gefallen