Sie sind auf Seite 1von 49

MREC

AGH GHALA 63/20kV Substation Automation


SICAM PAS Solution, System Description

Agh Ghala 63/20kV Substation

Automation & Protection Offer

Siemens
Ray Avin Fan Co.

Chapter 3

SICAM PAS
System Description

SICAM PAS Page 1 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

TABLE OF CONTENTS :
1. SICAM PAS INTRODUCTION .........................................................................................................................4
2. GENERAL SYSTEM DESCRIPTION ..............................................................................................................6
3. SICAM PAS SYSTEM ARCHITECTURE ........................................................................................................7
3.1. SICAM PAS a system with distributed architecture........................................................................................... 7
3.2. Hot-Hot (Control Master/ Monitoring Only) redundancy of a SICAM PAS system ........................................ 9
4. KEY TASKS OF THE SICAM PAS SYSTEM.................................................................................................11
4.1. Fields of Application......................................................................................................................................... 11
4.2. Tasks.................................................................................................................................................................. 11
5. SYSTEM CAPACITY .......................................................................................................................................12
5.1. Quantified Project Scope .................................................................................................................................. 12
5.2. SICAM PAS System Scalability........................................................................................................................ 13
6. SICAM PAS SYSTEM COMPONENTS..........................................................................................................14
6.1. SICAM PAS UI – Configuration...................................................................................................................... 14
6.2. SICAM PAS - Automation Blocks.................................................................................................................... 14
6.3. SICAM PAS UI – Operation ............................................................................................................................ 14
6.4. SICAM PAS Value Viewer ............................................................................................................................... 14
6.5. SICAM PAS CC - Human Machine Interface................................................................................................. 15
6.6. Available Variants of the System Components................................................................................................. 16
7. COMMUNICATION INTERFACES...............................................................................................................16
7.1. Communication via telecontrol protocols......................................................................................................... 17
7.2. Communication with IED’s and satellite RTU’s ............................................................................................. 18
7.3. Communication using the „open interface OPC“ ........................................................................................... 19
7.4. Communication with the HMI system.............................................................................................................. 20
8. SYSTEM SAFETY............................................................................................................................................20
9. OVERVIEW OF FUNCTIONS........................................................................................................................22
9.1. Overview............................................................................................................................................................ 22
9.2. SICAM PAS UI - Configuration ...................................................................................................................... 22
9.2.1. Configuration and Parameterization................................................................................................................ 23
9.2.2. Exchanging Configuration Data ...................................................................................................................... 27
9.3. Automation Functions ...................................................................................................................................... 28
9.4. The Feature Enabler......................................................................................................................................... 30
9.5. SICAM PAS UI - Operation ............................................................................................................................. 31
9.6. The SICAM PAS Value Viewer........................................................................................................................ 32
9.7. HMI................................................................................................................................................................... 33
9.7.1. SICAM PAS CC Components........................................................................................................................... 34
9.7.2. Displaying ......................................................................................................................................................... 40
9.7.3. Controlling ........................................................................................................................................................ 43
9.7.4. Substation Control Functions........................................................................................................................... 45
9.7.4.1. Switching Authority ..................................................................................................................................... 45
9.7.4.2. Bay Blocking................................................................................................................................................ 46
9.7.4.3. Telecontrol Blocking ................................................................................................................................... 46
9.7.4.4. Time Synchronization.................................................................................................................................. 46
9.7.4.5. Ethernet station bus..................................................................................................................................... 46
9.7.4.6. Fault Recording........................................................................................................................................... 47
10. REQUIREMENTS AND NORMS ..............................................................................................................48

SICAM PAS Page 2 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

10.1. Climatic and Ambient Conditions .................................................................................................................... 48


10.2. Physical Requirements...................................................................................................................................... 48
10.2.1. Electromagnetic Compatibility .................................................................................................................... 49

SICAM PAS Page 3 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

1. SICAM PAS INTRODUCTION


The SICAM PAS Power Automation and Telecontrol System sets new trends in the area of
telecontrol and substation automation systems. This is due to its innovative, yet high performance
architecture using standard hard- and software components. The SICAM PAS also uses
international standardized communication technologies in the field of power automation.
The power automation system SICAM PAS completely covers the requirements of todays and
tomorrows distributed automation system. SICAM PAS is an open system, i.e. in addition to the
integrated communication channels, open interfaces are built in for the integration of project
specific applications.
SICAM PAS can be easily integrated into existing structures. Commissioning and maintenance
tasks are supported with state-of-the-art diagnostic tools.
Using standardised components allows flexibility of functionality and configuration. With the
implementation of web based applications, e.g. for diagnostic and monitoring purposes were
created.
Furthermore, the data exchange functions in XML format ensure data consistency; reduce the risk
of errors and saving time and money. In this way investment security is secured.
Decades of extensive experience and know-how are incorporated into the SICAM PAS power
automation / telecontrol technology meeting the highest demands through:

Reliability:
• Designed for critical switchgear environments
• Extensive test and diagnostic features for commissioning
• Autonomous operation of individual components to for critical plant sections
• Extensive self-monitoring in case of faults

High performance:
• Precise real-time acquisition and monitoring for tracking switching commands and system
reactions
• Distributed processor capacity using a distributed system architecture
• Multiple and easily extendable interfaces, whether installed as a line, bus or loop interface

Flexibility in the configuration:


• Convenient configuration using a graphical user interface (also possible online)
• Combination of IED’s freely selectable, scalable or adaptable in case of station modification
or extension
• Complex networks can be implemented; e.g. use of Industrial Ethernet via LAN or WAN
• Data consistency due to bottom-up configuration and data exchange functionality

SICAM PAS Page 4 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Communication:
New communication protocols

• Full IEC61850 functionality for an interoperable connection of IEC 61850 IED’s


• Open communication to other automation systems using OPC client <-> server mechanism

Established standard communication (Slave)

• Flexible network control centre connection (Slave):IEC 60870-5-101,IEC 60870-5-104


(TCP/IP) & DNP V3.00 (level 2)
• Protection IED’S using IEC 60870-5-103 protocol.

Established standard communication (Master)

• Data concentrator for connection of satellite RTUs:IEC60870-5-101 & DNP V3.00 (level 2)
• IED connection also possible: Profibus DP, Modbus & DNP V3.00 (level 2)
• Propriety IED protocols: Profibus FMS

High Availability:

• Robust and immune to electrical disturbances, proven in various type tests


• Fast and convenient diagnosis using integrated tools ensuring shortened repair times
• Long life cycle by virtue of high integration density and modern production technologies

Optimized Operation Management:

• Real time process information


• Processing functions dedicated to the power automation tasks
• High speed and efficient communication
• Simple and secure operation due to intuitive user interface

Convenient Design:

• User can use own staff for system configuration


• Various configuration options of the different system components
• Large control systems can be engineered in a step by step fashion (bottom-up configuration)
• Data import functionality means reduction of parameterisation
• Data import functionality ensures data consistency

SICAM PAS Page 5 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

2. GENERAL SYSTEM DESCRIPTION


The SICAM PAS system is an open, modularly-designed numerical system for energy automation.
The specific functions of a power automation system are combined with those of a programmable
logic controller system and include the communication possibilities of today’s IT-world.
SICAM PAS has been designed specifically for the requirements of energy & power automation
systems and is scalable due to its distributed architecture. The SICAM PAS power automation
system provides a system solution for an efficient execution of all tasks required in a substation.
SICAM PAS can be integrated into the existing communication structure of the substation, using
standardized communication standards. SICAM PAS can also be used as a communication
gateway.
The full graphical process visualisation system SICAM PAS CC (CC: control centre) can be
located directly in the substation and provides for easy control and monitoring. (See chapter 3 for
a more detailed description of SICAM PAS CC).
The CFC (Continuous Function Chart), a user-friendly graphical configuration tool for automation
purposes is an option, included in the option is the specifically developed substation automation
CFC function blocks.
New devices can be integrated into the system and can be intuitively configured (via SICAM PAS
UI). Especially using the possibility to adapt the configuration and the on-line settings (when the
configuration is done on the SICAM PAS running the same hardware), without generation and
loading, this makes the parameterisation and testing quicker and easier.
For diagnostic purposes SICAM PAS has dedicated tools aboard.
With using IT technology and with its integrated tools for test and diagnostics SICAM PAS is ready
for the future, which a also secures the investment.
The SICAM PAS power automation system provides innovative solutions for most diverse task
definitions resulting from the use of distributed information systems in different locations. It is
suitable for use both in interconnected and distributed switchgears of electric utilities and in the
manufacturing industry.
SICAM PAS has been designed as a modular, open system which complies with all widely used
communication standards. In addition to this, it supports you in the implementation of project-
specific automation tasks in the field of substation automation and power automation.
The SICAM PAS CC control and display system provides numerous options to realize your system
management concept via individually designed user interfaces and operator actions.
The consistent use of Windows technologies, convenient user interfaces and the operating logic of
the system components ensure that newcomers become familiar with SICAM PAS within a short
time.

SICAM PAS Page 6 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

3. SICAM PAS SYSTEM ARCHITECTURE


Possible topologies of the SICAM PAS system are shown below. These do not necessarily fit
together with the architecture on which this offer is based.
Please see part C for the valid SICAM PAS architecture, as well as part B for the scope of delivery
and service for this offer.

3.1. SICAM PAS a system with distributed architecture


The SICAM PAS system consists of one Station Unit called “Full Server” (In a SICAM PAS hot-hot
redundant system there are 2 “Full Server”) When wanting to increase the performance, numbers
of connections ,system availability and topological reasons the SICAM PAS system can be
extended with additional Station Units named “Device Interface
Processor DIP“.
• SICAM PAS is suited for the operation in a substation with one SICAM PAS Station Unit
• Can also work in co-operation with other SICAM PAS Station Units in a distributed system.
The various SICAM PAS Station Units are in this case exchange information via a powerful
Ethernet- LAN.

A powerful data distribution system for real time data enables the SICAM PAS system to allocate
tasks to various SICAM PAS Station Units. These Station Units together form one SICAM PAS
system and thus have a higher performance, system availability and more connections
communication possibilities.

SICAM PAS Page 7 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 1- SICAM PAS System consisting of one Station Unit „Full Server“

Picture 2- Distributed SICAM PAS system (one Station Unit „Full Server“ and up to 6 Station Units „Device
Interface Processor“)

SICAM PAS Page 8 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

3.2. Hot-Hot (Control Master/ Monitoring Only) redundancy of a SICAM


PAS system
The availability of the SICAM PAS power automation system can be further enhanced in doubling
the SICAM PAS Station Unit „Full Server“.
The HMI server can also be built redundantly, as shown below and can serve several HMI clients.

Picture 3- redundant SICAM system (2 Station Units „Full Server“ and redundant HMI server with 3 HMI
clients)

The architecture consists of the 2 SICAM PAS systems in a hot-hot configuration. Both systems
are acquiring data independently from each from the connected IED’s and/or satellite RTU’s.
This hot-hot redundancy can be used only together with IED’s and satellite RTU’s which support
dual/multiple master protocols (i.e. Profibus FMS, IEC 60870-5-101) or client <-> server protocols
as a server which can be accessed from dual / multiple clients (IEC61850) Both SICAM PAS “Full
Servers” data bases are automatically yet independently updated from the field connected IED’s
and satellite RTU’S (monitoring direction) No information exchange between the HOT-HOT
SICAM PAS station units is required when no internal commands are generated (e.g. derivation

SICAM PAS Page 9 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

from an indication) and there are 2 independent telecontrol connections to the control centre
(which selects the active channel).
In case internal commands are generated or only one telecontrol interface is available, an
exchange of a status (“Control Master” / “Monitoring only”) between both SICAM PAS Station
Units is a necessity to ensure that only one source is enabled to send commands and to switch
the telecontrol interface to the Station Unit with the status “Control Master”.
Possible locations for controls are:
• Local HMI SICAM PAS CC
• Remote control from a control centre
• Internally generated command (derivation, automatic sequence,…)

The following mechanisms are providing the necessary functionality of a single command source:
• SICAM PAS CC => Software redundancy function of WinCC
• Remote Command => task of the connected control centre
=> Switching the telecontrol interface, when one is only available
• Internally generated command => CFC logic

The switching between of the status (“Control Master” / “monitoring only”) of the 2 „Full Server“
can be done via:
• Internal supervision function
o Done with CFC logic
o Exchange of status via OPC mechanisms
• Operator from SICAM PAS CC HMI place

Optional additional information can be generated and exchanged Verification of the status of the
communication drivers to IED’s and satellite RTU’S connected to both Station Units
=> Switch over criterion: Station Unit 1 drivers not o.k. / Station Unit 2: drivers o.k.
• Information to the control centre which Station Unit is the “Control Master”
• Life signal from both Station Units to the control centre

SICAM PAS Page 10 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

4. KEY TASKS OF THE SICAM PAS SYSTEM


SICAM PAS is designed for the following tasks:
• Telecommunication
• Monitoring
• Automation
• Local and remote control / control with switchgear interlocking / switching sequences
• Connection of protection relays and bay controllers
• Editing and displaying of process information in the station using SICAM PAS CC
• Archiving and logging of operation and disturbance data via SICAM PAS CC
• Integration of industrial networks using Profibus DP or OPC-communication
• Open communication channel using OPC client <-> server mechanisms

4.1. Fields of Application


SICAM PAS can be used for all applications where
• various communication standards are required, e.g. for the connection
o of distributed substation automation systems via IEC 61850
o of distributed substation automation systems via PROFIBUS FMS
o of bay devices and substations with serial interfaces and via the IEC 60870-5-103,
IEC 60870-5-101 or DNP V3.00 protocol
o to telecontrol centers via serial connections and the IEC 60870-5-101 or DNP V3.00
protocol or data transmission via LAN/WAN with Ethernet TCP/IP and the IEC 60870-
5-104 protocol.

• you require flexible solutions for


o local visualization, archiving and logging
o remote visualization, archiving and logging,
o e.g. using the SIMATIC Web Navigator.

• automation tasks must be performed


• the data exchange via OPC is used
• you expect that data are acquired and transmitted in realtime

4.2. Tasks
SICAM PAS performs the following tasks:
• Data exchange with subsystems and higher-level control centers via
numerous communication protocols
• Acquisition of process data in realtime
• Telecontrol/control with switchgear interlocks
• Visualization of process data via individually designed user interfaces such as overviews,
station diagrams, event lists, etc.
• Archiving of measured values and metered values
• Evaluation of fault records

SICAM PAS Page 11 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

• Transmission of process data via an OPC server


• Processing of project-specific automation tasks

5. SYSTEM CAPACITY
SICAM SAS is an open and modularly extendible system. The following chapter describes typical
extension options, not a precise customer application.
SICAM SAS comprises the substation automation unit SICAM SC
• With Input/Output (I/O) modules in the module rack for central process connection,
• Decentral periphery comprising protection or bay units or IED's,
• SICAM WinCC process visualization system
• And associated communication modules.
In total SICAM SAS can process 10,000 information items (analog and/or digital discrete
input/output signal).

5.1. Quantified Project Scope

The number of items of information processed by SICAM PAS is mainly determined by the
structure and the transmission speed of the communication components used.
The following guidelines are valid:
• Maximally 100 devices on a SICAM PAS Full server or SICAM PAS DIP with maximally 5000
items of information
• Maximally 150 devices on a SICAM PAS system (Full server and DIP) with maximally 10,000
items of information.

In SICAM PAS, the SICAM PAS DIP (Device Interface Processor) is used as a data concentrator.
The transmission protocol determines how many bay devices and substations can be connected.
The following limit values apply:
• PROFIBUS FMS
Maximally 2 CP5613 communication processors with maximally 30 devices each on one
SICAM PAS station unit
• PROFIBUS DP
Recommended: maximally 2 CP5613 communication processors with maximally 31 devices
each on a full server or DIP
• IEC 60870-5-103, IEC 60870-5-101, DNP V3.00, Modbus
The use of COM expanders (e.g. Rocket Ports) or serial hubs is recommended for
performance reasons.
Connection options:
- Maximally 2 Rocket Ports with 32 interfaces each
- Maximally 100 devices on a SICAM PAS full server or DIP.

SICAM PAS Page 12 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

• IEC 61850
maximally 100 devices on a SICAM PAS fullserver or DIP.

5.2. SICAM PAS System Scalability


SICAM PAS is a scalable system due to its distributed architecture, which is a requirement for any
modern system.
The basic and optional components and packages introduced in this chapter is a summary of the
principal features available as software components and drivers. These or may not fit the
particulars in this offer.
Please see part B for the scope of delivery and service included in this offer.
The SICAM PAS system consists of one Station Unit named “Full Server” (In a SICAM PAS hot-
hot redundant system there are 2 “Full Server”). Due to reasons of performance, numbers of
connections, system availability and topological reasons the SICAM PAS system can be extended
with up to 6 further Station Units named “Device Interface Processor” (or “DIP“).
The following components are part of the SICAM PAS basic system (depending on the order
number):
• SICAM PAS UI – Operation („Full Server“ / „DIP“)
• SICAM PAS UI – Configuration („Full Server“ / „DIP“)
• SCADA-Value-Viewer („Full Server“ / „DIP“)
• OPC Server („Full Server“ / „DIP“)
• Data handler for real time data („Full Server“)
• Sybase SQL data base („Full Server“)

SICAM PAS is a scalable system. Additional software components and drivers can therefore
ordered if and when needed.
The following optional packages are available:
• Automation tool CFC
• IEC 61850 (Client) for connection of IEC61850 IED’s
• Protocol driver for Profibus FMS IED’s for connection of SIPROTEC 4 IED’s
• Protocol driver for Profibus DP
• Protocol driver for IEC 60870-5-103 Master for connecting IED’s
• Protocol driver for IEC 60870-5-101 Master for connecting satellite RTU’s
• Protocol driver for IEC 60870-5-101 Slave for the connection to control centres
• Protocol driver for IEC 60870-5-104 Slave for the connection to control centres
• Protocol driver for DNP V3.00 (level 2) Master for connecting IED’s
• Protocol driver for DNP V3.00 (level 2) Slave for the connection to control centres
• Protocol driver for Modbus Master for connecting IED’s
• OPC Client

SICAM PAS Page 13 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

6. SICAM PAS SYSTEM COMPONENTS


6.1. SICAM PAS UI – Configuration
The SICAM PAS UI - Configuration system component is used for
• The configuration and parameterization of your system as well as for
• The exchange of configuration data.

In the different views, you can specify the type and the transmission modes of your ommunication
links. In addition to this, you also define which devices, substations, control centers or control and
display systems are connected.
For each of the connected system components, you can also specify which information is valuated
in the SICAM PAS substation unit. You also determine which information is to be available for the
communication with higher-level control centers and for the system management via SICAM PAS
CC.
You can individually structure your system data in the topological view to map your operating
conditions.
Predefined device- and project-specific descriptions ensure that your system can be configured
and parameterized conveniently and within a short time.

6.2. SICAM PAS - Automation Blocks


Project-specific automation tasks are performed in SICAM PAS via a graphical interconnection of
functional blocks or by specifying automating functions via Structured Text.
A comprehensive library of different functional blocks is available for these tasks. These blocks
have been especially designed to provide sophisticated solutions for your power automation tasks.

6.3. SICAM PAS UI – Operation


SICAM PAS UI - Operation provides you with a quick overview of the runtime status of your
system components. In addition to this, you can enable or disable individual components such as
interfaces or devices.

6.4. SICAM PAS Value Viewer


If the communication links have been established properly, the SICAM PAS Value Viewer displays
information on the selected device or substation. Within the framework of commissioning, for

SICAM PAS Page 14 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

example, you can use this information view to test data circuits and to check whether an interface
or a device transmits correct values.
Command outputs may be initiated for test purposes.

6.5. SICAM PAS CC - Human Machine Interface


The SICAM PAS CC Human Machine Interface (HMI) is used to monitor and control your system.
SICAM PAS CC consists of
• The SIMATIC WinCC process visualization system and
• The SICAM PAS CC components.

SIMATIC WinCC provides standard function modules for graphical representation, for messaging,
archiving and logging. It ensures high availability through its powerful process interface, fast
display refresh and safe data archiving.
The SICAM PAS CC components complement the standard functions by system management-
specific features and convenience functions for the configuration and parameterization of your
user interface.
SICAM PAS CC components include:
• SICAM PAS Wizard
Supports you in the creation of a new WinCC project or in updating an already existing
WinCC project.
• SICAM PAS Symbol Library
As an example, this library includes objects for the representation of switching devices,
measured values, metered values and control elements.
• Switching device objects
These objects dynamize the system based on IndustrialX Controls. Status and state displays,
the execution of switching operations, etc. are realized via these objects.
• SICAM PAS CC Alarm Logging - Message Lists
For messaging with the appropriate timing sequence. Incoming messages are logged in the
message lists with the absolute time stamps formed in the bay devices or substations. The
time stamp and the message state are complemented by additional information such
as cause, event source, status information, protection times, etc.
• SICAM Valpro
For the processing, representation and evaluation of archived measured values and metered
values.
• SICAM Recpro
For the management, archiving and display of fault records.

SICAM PAS Page 15 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

6.6. Available Variants of the System Components


Different variants of the SICAM PAS system components are available.
You can compose your system from basic and optional packages appropriate for your individual
application and the resulting requirements.

7. COMMUNICATION INTERFACES
The communication with the control centres, satellite RTU’s and IED’s are processed using the
following interfaces:
• LAN - Ethernet TCP/IP interface(s) of Station Unit(s) „Full Server / DIP“
• Communication with IED’s IEC 61850 client
• Communication with control centres using IEC 60870-5-104
• Communication between Station Units „Full Server“ and „DIP“
• Communication between SICAM PAS Station Unit(s) and SICAM PAS CC HMI
• Communication with the open interface using OPC client-server mechanisms
• Connection of a COM-Expander via TCP/IP
• Serial COM-interfaces of the Station Unit(s) „Full Server / DIP“
• Communication with control centres using IEC 60870-5-101 slave or DNP V3.00 (level 2)
• Communication with satellite RTU’s using IEC 60870-5-101 master or DNP V3.00 (level 2)
• Communication with IED’s using IEC 60870-5-103
• Communication with IED’s using DNP V3.00 (level 2) or Modbus RTU
• Profibus interface modules plugged in the Station Unit(s) „Full Server / DIP“
• Communication with SIPROTEC 4 IED’s via Profibus FMS
• Communication with IED’s via Profibus DP
• The SICAM PAS Station Unit(s) is/are equipped always with:
• 1 x LAN – Ethernet TCP/IP interface
• 2 serial COM interfaces

Up to 4 CPCI modules (depending on the ordered type) can be used additionally in a SICAM PAS
Station Unit. One of these CPCI slots is used (by default) to insert a GPS-time synchronization
module. Thus when using GPS only 3 slots can be used for extension of the communication
interfaces of the SICAM PAS Station Unit(s):
• Additional serial interfaces:
o Using PCI COM-Expander (e.g. Rocket Port) to extend the number of serial
interfaces up to 32
o Using Rocket Port serial Hub via the Ethernet LAN.

• A Rocket Port serial Hub can provide up to 8 RS232/RS485 interfaces


o Profibus interfaces using CP5613Profibus PCI module
o Up to 4 x CP5613 per Station Unit
o Up to 2 of them can be used for Profibus FMS communication
o Per CP5613 used as Profibus DP master, up to 31 Profibus DP slaves can be
connected,

SICAM PAS Page 16 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

o Per CP5613 used as Profibus FMS master, up to 30 Profibus FMS IED’s can be
connected,
• LAN connection via Ethernet TCP/IP of the SICAM PAS Station Unit(s)
o Ethernet Switches
o Ethernet Hubs
o In the IEC 61850 Standardization papers special requirements are defined regarding
environmental conditions Switches und Hubs, these requirements are considered in
the selection of used Switches / Hubs for connection of IEC61850 IED’s

For the connection of IED’s via a fibre optic network, using fibre optic star-couplers, OLM’s (optical
link module), OSM’s (optical switch module) or Ethernet switches/Hubs with fibre optic interfaces
can be used, depending on the used transmission protocol.

7.1. Communication via telecontrol protocols


The communication up to 5 control centres per SICAM PAS system with different protocols can be
used. The communication interfaces are independent of each other and can be located, in a „Full
Server“ and also in a „DIP“.
The following protocols are implemented for communication to a control centre:
• IEC 60870-5-104 (TCP/IP),
• IEC 60870-5-101 (balanced and unbalanced),
• DNP V3.00 (level 2)
Our scope of supply ends with the physical telecontrol interface of the SICAM PAS Station Unit(s).
Especially in case of the LAN/WAN based telecontrol protocol IEC60870-5-104 where the
substation is connected via a router (not in our scope) it is necessary that the owner of the
substation implements all aspects of security (like firewall …) in the used router in order to protect
the substation against unauthorized access.
Satellite RTU’s can be connected to the SICAM PAS system via the telecontrol protocols IEC
60870-5-101 and/or DNP V3.00 (level 2).
The transmission rate of the implemented protocols can be at maximum:
• IEC 60870-5-104 (Slave) 10/100 MBit/s
• IEC 60870-5-101 (Slave) up to 38,4 kBit/s (balanced and unbalanced mode)
• DNP V3.00 Level 2 (Slave) up to 38,4 kBit/s
• IEC 60870-5-101 (Master) up to 38,4 kBit/s (balanced and unbalanced mode)
• DNP V3.00 Level 2 (Master) up to 38,4 kBit/s

The implemented functions of these protocols and the rules for exchanging the data between the
SICAM PAS system and the control centre are described in the attached protocol description /
interoperability list.

SICAM PAS Page 17 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

7.2. Communication with IED’s and satellite RTU’s


The maximum number of IED’s and/or satellite RTU’s which can be connected to a SICAM PAS
system is 150, independent of the used communication protocol (IEC61850, IEC 60870-5-101,
IEC 60870-5-103, DNP V3.00 (level 2), Profibus FMS / DP or Modbus-RTU).
The following protocol options (available per order code) for communication to IED’s and satellite
RTU’s are available for the SICAM PAS system:

IEC 61850 IEC 61850 is the international standardized communication protocol in a


substation for connecting IED’s and devices within a substation using
Ethernet MMS. IEC 61850 also supports a direct data exchange (broadcast,
multicast) between IED’s and therefore allows for example system
interlocking without a central unit.
Profibus FMS Most SIPROTEC 4 bay control and protection relays can be connected to the
SICAM PAS Station Unit using Profibus FMS. Within Profibus FMS many
features which a re later found in the IEC61850 can already be used.
IEC 60870-5-103 Many of suppliers of protection relays, bay controller, and other IED’s
support this protocol and can be connected to the SICAM PAS.
IEC 60870-5-101 (Master) the international standardized protocol IEC 60870-5-101 is
used for the connection of satellite RTU’s.
‚balanced‘ and ‚unbalanced‘ modes are supported.
For the connection of satellite RTU’s automatic dial-up
communication is also supported.
The establishment of the connection to the satellite RTU can be
done cyclically and driven by event (e.g. to send a command). In
monitoring direction the establishment of the connection can also be
done cyclically and driven by events.
Analogue and ISDM modems can be used; it is also possible to use
a GSM modem in the substation. For the communication to the
satellite RTU’s Backup modems can also be used.
" other satellite RTU’s can therefore be connected when the
“standard modem” is busy.
PROFIBUS DP PROFIBUS DP is a powerful field bus protocol using the Token-
assingprocedure.
This protocol is mainly used in the process automation area and also
in automation systems for energy- and gas- substations.
For simple applications, where functions like time synchronization
and transmission of fault recording is not required, SIPROTEC 4

SICAM PAS Page 18 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

relays can be connected to the SICAM PAS Station Unit using


Profibus DP.

Additionally connecting IED’s with DNP V3.00 (level 2) and Modbus RTU protocol is possible.

Examples for the connection of IED’s

Depending on the implemented functions and the technical specifications of the hardware and the
interfaces, the following combinations may be implemented:

IEC 61850
• SIPROTEC 4 protection relay
• SIPROTEC 4 Bay Processing Unit
• Protection devices of third party manufacturers

IEC 60870-5-103
• SIPROTEC 3 protection relays
• SIPROTEC 4 IED’s
• Protection devices of third party manufacturers
• Bay coupling unit 6MB525
• Measuring transformer SIMEAS T
• Transformer controller manufactured by Companies: Eberle or Reinhausen

Profibus FMS
• SIPROTEC 4 protection relay
• SIPROTEC 4 Bay Processing Unit

DNP V3.00 (level 2)


• IED’s of third party manufacturers

Profibus DP
• DP standard slaves (e.g. ET200)
• Power meter SIMEAS P

Modbus
• IED’s of third party manufacturers (e.g. Measuring Centers)
• PLC units

7.3. Communication using the „open interface OPC“

SICAM PAS can be configured as an OPC Server and OPC Client.

SICAM PAS Page 19 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

With the OPC Server SICAM PAS process variables can be read and written from OPC clients
which arelocated either in the same system or connected via TCP/IP to the SICAM PAS system.
Using these OPC mechanisms it is for example possible to connect a third party HMI.
The OPC Server is part of the SICAM PAS basic package.
The OPC Client can read and write data from other OPC-Servers. An application example is the
data exchange between the SICAM PAS Station Unit and the SIMATIC automation systems.

7.4. Communication with the HMI system


The process visualization and control System SICAM PAS CC is connected via LAN connection
(Industrial Ethernet TCP/IP) to the SICAM PAS Station Unit(s).
The SICAM PAS CC visualization and control system can be configured as:
• Single User System (1 SICAM PAS CC to control 1 SICAM PAS system)
• Multi User System (1 SICAM PAS CC to control several SICAM PAS systems)
• Multi User System using client/server architecture
The SICAM PAS CC Server can be redundant Please see chapter 3 for more detailed description
of the SICAM PAS CC visualization and control system and the system requirements.

8. SYSTEM SAFETY
Reliability and safety requirements as required in a substation automation system are fulfilled to a
high degree by the SICAM PAS system. Electromagnetic compatibility of SICAM PAS electronic
components is also given particular attention.
SICAM PAS promptly signals faults because it has continuous running safety check running in the
background. This ensures that the operation /maintenance personnel can locate the faulty system
components more quickly.
• Interruption of power supply
The SICAM PAS system automatically reboots after an interruption of the supply voltage. All
the parameters are securely stored in the real-time data base and all applications are started
as “services” automatically in the same state as before the interruption. The SICAM PAS
system is designed to be maintenance free, i.e. no buffer batteries are required and there is
fan -free operation.
• Communication
Faults in data transmission caused by electromagnetic influences, earth potential differences,
ageing of components or other disturbances or noise sources on the transmission channels,
are reliably detected. The safety procedures of the protocols detect:

SICAM PAS Page 20 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

• Bit and message errors,


• Information loss or repetition,
• Faulty information items,
• Separation or corruption of contiguous information items.
• Priority-controlled message preparation
Messages activated by events are priority-controlled and rapidly made available to the
system. The following lists are provided:
• Basic cycle list
• Periodic list
• Interrogation lists
• Time-controlled lists
• Spontaneous lists,
• with/without time delay
• prompt memory/message memory
• Organizational list
• A telecontrol fault group indication can be parameterised from individual information items
and transmitted as a group indication to the control centre, logged or used for signalling
at the cubicle.
Using the graphical automation tool CFC single faults can be easily and comfortably
grouped in a user friendly way, using the structured text function of the automation tool of
SICAM PAS.
Our scope of supply ends with the physical telecontrol interface of the SICAM PAS Station
Unit(s). The connection to a public net using Web-browser or WAN connections via router is
within the responsibility of the substation owner.
Especially in case of the LAN/WAN based telecontrol protocol IEC60870-5-104 where the
substation is connected via a router (not in our scope), it is necessary that the owner of the
substation implements all aspects of security (like firewall …) in the used router in order to
protect the substation of unauthorized access. At the latest after commissioning or transfer of
the equipment for operation Siemens will not be able to ensure that all security relevant
patches can be installed, therefore Siemens must reject the responsibility for the protection
against unauthorised access.

SICAM PAS Page 21 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

9. OVERVIEW OF FUNCTIONS
9.1. Overview
SICAM PAS has been designed as a modular system with open communication interfaces. In
this way, it meets the requirements of stateof-the-art power management systems and of the
power supply equipment of industrial manufacturing plants.
This modular structure also allows to flexibly combine the individual system functions. Only
those components required on a certain computer must be installed and authorized there.
The following sections provide an overview of the individual system components and their
tasks. These include:
9 SICAM PAS UI - Configuration
9 Automation Functions
9 Feature Enabler
9 SICAM PAS UI - Operation
9 SICAM PAS Value Viewer
9 SICAM PAS CC
9 SICAM Recpro
9 SICAM Valpro
Complementary to the above-mentioned components, following Chapters describes
substation control functions such as:
9 Switching authority
9 Bay blocking
9 Telecontrol blocking
9 Time synchronization
9 Fault recording

9.2. SICAM PAS UI - Configuration


The SICAM PAS UI - Configuration system component is used for
• the configuration and parameterization of your system as well as for
• the exchange of configuration data.

SICAM PAS Page 22 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

9.2.1. Configuration and Parameterization


The clearly structured configuration interface provides you a comprehensive overview of your
system parameters.
Import and export functions allow the exchange of configuration data. This reduces the
expenditure and error sensitivity during the configuration and parameterization of a system.
The elements of the user interface can be arranged according to the requirements of the
individual user. You can specify that continuously required table columns are always shown
in the corresponding view, whereas non-required columns are hidden. The settings are
maintained also after a restart of the program.
Sorting and filter options provide for increased transparency and convenient
parameterization.
System-specific automation functions are graphically configured. To do so, you use both
default logic functions and specific power automation function blocks.
Your parameter entries are immediately checked for plausibility. Tooltips provide information
on the permissible values or on the value range. In addition to this, the user is supported by a
context-sensitive online help.
It is not necessary to explicitly generate the configured and parameterized data for the
runtime environment.
SICAM PAS UI - Configuration structures the parameters in the individual views:
• Configuration
• Mapping
• Topology and
• Templates
Configuration In this view, you specify the components of which your SICAM PAS
system consists. These include:
• Applications
IED protocols, control center connection, HMI (SICAM PAS CC), automation (CFC) and
OPC.
• Interfaces
Serial interfaces, Ethernet, PROFIBUS
• Devices / control center
Bay controllers and protection devices, transformer controllers, distributed I/Os or
depending on the protocol of a control center.
The configured components are represented in a tree structure, whereas the parameters of
the selected components are displayed in the data pane.

SICAM PAS Page 23 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 4- SICAM PAS Configuration

Mapping In this view, you select which information is to be used in the previously
inserted applications of your system.
For the interface to higher-level control centers, you also specify telecontrol
addresses, the list assignment and protocol type-specific parameters.

SICAM PAS Page 24 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 5- SICAM PAS Mapping of the information of a device

Topology The configuration view of your system is orientated towards communication.


In contrast to this, the topological view allows to create a system view which
is structured according to the requirements of an individual project. Levels of
information such as substation, voltage level, bay and any other
structurization levels are created in this context.
On these levels, you can simply distribute the configured and parameterized
information via Drag & Drop.

SICAM PAS Page 25 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 6- SICAM PAS topology, example of information of the SICAM PAS substation

Templates In the template view, you can define device- and project-specific device
descriptions and templates for normalizations of information.
You can assign project-specific information names and addresses. Moreover,
you can specify command execution times, the assignment of commands
and command feedbacks or the type of information.

SICAM PAS Page 26 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 7- SICAM PAS templates, example of a PROFIBUS FMS device

9.2.2. Exchanging Configuration Data

If devices which have already been parameterized completely are integrated in


interconnected systems, these configuration data can be imported in SICAM PAS. As
an example, you can integrate substations parameterized with SICAM plusTOOLS or
the project-specific information volume of the bay and protection devices into SICAM
PAS.
If modifications to the information volume result, you can conveniously update
already imported project data.
Configuration data are exchanged in different formats on the file level.

SICAM PAS Page 27 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Importing configuration data

You can import the configuration data of bay and protection devices in the DBF, XML
or SCD format, whereas configuration data of substations are imported in the XML
format.
For IEC 61850, all devices included in an SCD file are imported and created
automatically within the framework of the SCD file import.

Export of configuration data

Control center Configuration data created via SICAM PAS for the
connection of your station to higher-level control centers via
IEC 60870-5-101 can be exported in the XML format and
then imported by the control system.

SICAM PAS CC Configuration data required for the process visualization via
SICAM PAS CC are exported in the PXD format. Afterwards,
these data are imported by the SICAM PAS Wizard and
used for the generation of the control and display interface of
your SICAM PAS system.

Exchange of configuration data via OPC


If your SICAM PAS system works as an OPC Client, you can
apply data of the corresponding OPC Server. In this context,
the OPC Browser displays in a comprehensive manner
which information is available and which information is
already used.
This is a convenient method to extend or reduce an already
performed data selection.

9.3. Automation Functions

The SICAM PAS automation blocks provide a comprehensive tool allowing individual
solutions of operational automation tasks.
Automation functions are formulated via CFC or Structured Text (ST). CFC allows the
graphical connection of function blocks. In addition to usual link blocks such as AND,
OR, NOR, etc., you can use a comprehensive library of system-tested power
automation function blocks.
In this way, you can realize typical task definitions such as

SICAM PAS Page 28 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

• Command processing
o Command derivation
o Interlock tasks
• Message processing
o Message derivation
o Message filtering
o Inversion and conversion of messages
o Group indication formation
o Transformer tap and bit pattern comparisons
• Measured- and metered-value calculation
o Non-linear characteristic
o Limit value monitoring
o Slave pointer
o Mean value formation
o Arithmetic and comparison blocks
• Switching sequences
Simple configuration rules simplify the definition and interpretation of function charts;
the chart-to-chart technology provides for a comprehensive overview.
For the configuration via SICAM PAS UI - Configuration, you simply selet information
required for your automation tasks. Already there, you can group information which is
used collectively (if required).

SICAM PAS Page 29 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 8- SICAM PAS, example of a command interlock

9.4. The Feature Enabler


Use the Feature Enabler to enable the applications which you require in your project
or on the corresponding computer.
In this context, applications are:
• the different protocols
• the configuration tool
• the CFC automation function
• OPC connections

SICAM PAS Page 30 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 9- Feature Enabler

9.5. SICAM PAS UI - Operation

SICAM PAS UI - Operation provides a quick overview of the runtime status of your
system. The configuration is displayed in the tree structure and the representation via
different colors provides a quick overview of the status of interfaces, devices or other
applications.
The component selected in the tree structure can be enabled or disabled in the data
pane.

SICAM PAS Page 31 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 11- SICAM PAS UI - Operation

9.6. The SICAM PAS Value Viewer

The SICAM PAS Value Viewer is an important tool for the project phases of
configuration, testing, commissioning and operation.
Without any additional configuration expenditure, it allows the visualization of process
and system information and informs you about the current status of your system.
In addition to the check in monitoring direction, tests can also be performed in control
direction via command outputs.
The value display is updated continuously.

SICAM PAS Page 32 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 12- SICAM PAS Value Viewer

9.7. HMI
In the SICAM PAS system, SICAM PAS CC performs the control and display
functions of the process information of your system.
In this way, functional and spatial contexts of your system components are
represented conveniently in overview and system diagrams.
The logging of status changes of your process information and operator actions in
the correct time sequence is performed via message lists such as the alarm and
event list.
You can intervene into the process and control it from system diagrams.
System data such as messages and measured values can be logged and saved in
freely definable archives.
The assignment of specific authorizations, the possibility to use bay and telecontrol
blockings, different switching modes and the consideration of switching authorities
complete the control functions. For more information on these functions.
The communication with the SICAM PAS is performed via Ethernet (TCP/IP).

SICAM PAS Page 33 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

SICAM PAS CC consists of the SIMATIC WinCC process visualization system and
the SICAM PAS CC components.

Picture 13- SICAM PAS CC Components

SIMATIC WinCC SIMATIC WinCC provides standard function modules for the
graphical display, for messaging, archiving and logging of
information. With its powerful process interface, the fast diagram
update and the safe data archiving, it ensures high availability of
your system data.

9.7.1. SICAM PAS CC Components


The SICAM PAS CC components extend the SIMATIC WinCC standard functionality by
functions for the use of the control and display system in the field of power automation.
SICAM PAS Wizard
The organizational functions of the SICAM PAS Wizard support you in the
configuration of your project.

SICAM PAS Page 34 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Import
After the creation of a station, you use the SICAM PAS Wizard to import
SICAM PAS information configured and parameterized with the SICAM PAS
UI - Configuration tool.
The import includes:
• Import of the SICAM PAS tags to the SICAM PAS CC tag management.
• Import of the SICAM PAS messages to the SICAM PAS CC alarm logging.
• Import of the SICAM PAS measured values and metered value to the
SICAM PAS CC tag logging.
• Creation of the SICAM-specific structure tags and of the required
internal tags (variables).

Initialisation
The SICAM PAS Wizard initializes the project. Within the framework of
the initialization:
• the SICAM symbol library is imported.
• the SICAM-specific alarm logging is created.
• the SICAM text library is created.
The initialization can be performed independently of the SICAM PAS data
import. In this way, you can start the configuration of the SICAM PAS CC
project before the completion of the project via SICAM PAS UI - Configuration.
The activities of the SICAM PAS Wizard are logged in the SICAM Report which
provides you with detailed information on the success of the activities or on
error messages and warnings.

SICAM PAS symbol library

The SICAM PAS symbol library includes


• Objects for the representation of the switching devices
• Objects for the visualization of measured and metered values
• Message window templates for alarm logging (templates for the event list, warning
message list and the protection message list)
• Control elements e. g. for the control of the switching authority, for synchronized
switching, etc.

SICAM PAS Page 35 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

• Control elements for the control of the message list entries for defining which
updates of a process information initiate entries in the message lists.

Picture 14- SICAM Symbol Library

When creating your system diagrams, you simply move these graphical objects via
Drag&Drop from the library to your diagram. As a next step, you connect them with the
information parameterized via SICAM PAS UI - Configuration.

Switching device objects


IndustrialX Controls are used in SICAM PAS for the visualization and control of the
switching objects. IndustrialX Controls can be used in the multi-client and Web navigator
environment.
The SICAM switching device objects for circuit breakers and disconnectors support four
representation modes each:
• SICAM
• DIN 42200
• IEC 445 and
• LSA

SICAM PAS Page 36 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

If other representation options are required, you can assign the different states to bitmaps
which have been defined for this purpose. The GIF image format ensures optimum display
performance.

Bay overview objects


Bay overview objects are available in the SICAM PAS symbol library. These IndustrialX
Controls visualize the switching status of the overall bay. During the parameterization, you
select the individual switching devices for which the color is to change when the switching
state changes. In this way, bay overview objects increase the information content of your
overview diagrams.

Status display
The status display graphically visualizes the information statuses Not topical, WIN CC
status not OK, Bay blocking, Telecontrol blocking and Manually updated.
Via a context menu, you can display the current status of a selected information object in
text form.
The color representation of the individual status in the graphical representation can be
selected for the individual user.

Dynamizations
If a distinction must be made between synchronized and unsynchronized controlling of a
switching device, you can define additional dynamizations in the switching device object. In
this way, the control dialogs are extended and the control method can be chosen in runtime.
Some SIPROTEC 4 bay devices support synchronized switching.
If the switching device objects are only used in monitoring direction (missing entry of the
control variables), no control dialog is output.

Two-step controlling
The switching devices are controlled in two steps with the IndustrialX Controls. The
switching direction is selected in the first step, whereas the command output is initiated in
the second step.
If a subdevice supports the Select before Operate function, it can be combined with the
two-step method.

SICAM PAS Page 37 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

EnableSwitching
Depending on other tabs (variables), control dialogs can be prevented in runtime. As an
example, this feature is used if the switching authority changes between several operator
terminals of a SICAM WinCC Client/ Server configuration.

PermissionLevel
In the WinCC properties dialog, you can specify the user authorizations to determine which
operator actions or parameterization tasks may be performed by a certain operator.

LabelButtonOn
With this parameter in the WinCC properties dialog, you can specify object-specific texts for
runtime dialogs e. g. Step up/Step down for the transformer control.

Language adaptation
The default version of SICAM PAS CC provides German and English configuration and
runtime dialogs.
However, all texts used in these configuration and runtime dialogs are stored in text files.
For this reason, they can be translated conveniently to other languages.

SICAM PAS CC alarm logging - message lists


In the SICAM PAS CC message lists, the incoming messages are logged with the absolute
time stamps formed in the bay devices or substations.
The time stamp and the message state are completed by additional information. Examples
of additional information: Cause, event source, status information, protection times, etc.
Besides the values IN/OFF and RAISED/CLEAR, the value display also comprises fault
positions (double-point indications) and bit pattern indications.
Value texts can be parameterized for the individual message, such as Step up/down. You
can create up to eight different value text groups.
Command output indications are logged in addition to process indications.
In the alarm list, you can select which indication status is to be acknowledged.
• RAISED state
• CLEAR state
• RAISED and CLEAR state.
RAISED indications remain in the alarm list until the corresponding CLEAR indication and
the acknowledgement which might be required.

SICAM PAS Page 38 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Status of the devices SICAM PAS CC visualizes the status of the device connections to the
SICAM PAS Station Unit. If the connection is lost, the color of the switching device objects
and measured-value objects in the diagram changes.
In addition to this, the device status can be logged in the message lists.

SICAM Valpro
SICAM Valpro is an optional component for the processing, display and printing of archived
measured and metered values. It is based on the SICAM PAS CC archive system (SIMATIC
WinCC tag logging).
SICAM Valpro displays archived values in a graphical or tabular representation. The
following values are evaluated:
• Original values
• Maximum and minimum values in different time intervals, e. g. 15
minutes or hourly values
• Power factors
• Sum/difference values of metered values in different time intervals.
Groups can be defined for the representation and measured values can be assigned to the
groups.
The diagram representation can be defined freely with regard to many properties, such as
the curve type or the background.
Curve properties can be defined specifically for an individual curve.
Measured-value curves are represented analogous to the fault record evaluation.
The tabular representation of the archived values can be added to the graphical
representation or positioned independently. The cursor position and the first visible table
row correlate.
Graphical representations and tables can be output on a printer.
Tables with archive data can be exported in the CSV format, whereas text reports can be
exported in the text format. In this way, they are available for further processing in other
programs (such as Excel).
SICAM Valpro can be used on the SIMATIC WinCC Server or clients. As an alternative, it
can also be executed independently of SIMATIC WinCC. For the offline evaluation, you
require group files which you have created with SICAM Valpro in the SIMATIC WinCC
environment.
SICAM Valpro requires an individual authorization for each computer.

SICAM PAS Page 39 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

SICAM Recpro
SICAM Recpro is an optional extension block for the management, archiving and evaluation
of fault records. It can also be used independently of SICAM PAS CC.
For protection devices connected to a SICAM PAS Station Unit via the IEC 60870-5-103,
PROFIBUS FMS or IEC 61850 protocols, the fault records created in these devices are
transmitted automatically. These fault records are archived automatically in communication-
specific directories on the fullserver or DIP.
The fault records transmitted can be evaluated using SICAM Recpro.
SICAM Recpro consists of the following components:
• SICAM Recpro Explorer
for the management and evaluation of fault record archives in combination with an
evaluation program.
• SICAM Recpro Collector
for the generation and management of a central fault record archive
• ComtradeView
for the visualization of fault records
SICAM Recpro provides additional, complementary features such as
• Adaptation of the channel texts in the fault records via device-specific channel text
files, also from third-party devices
• Export functions
Export of fault records in the Comtrade format
Export of an overview of the fault record archive contents to a text file
• Import of external fault records in the Comtrade format
• Evaluation function
Zone diagram based on a fault value file in the RIO format.

9.7.2. Displaying
The spatial and functional correlations of your system components can be represented in
more or less detailed diagrams.
Graphical representations of individual system components or devices can be constructed
in addition to overview and system diagrams.
In addition to this, your process information can be logged in an event list.
SICAM Valpro can also evaluate archived measured and metered value via graphical or
tabular representations.

SICAM PAS Page 40 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

The graphical fault record evaluation with SICAM Recpro completes the visualization
options of your system data.

Picture 15- Overview diagram, example

SICAM PAS Page 41 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 16- System diagram - section, example

SICAM PAS Page 42 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 17- Representation of a SIPROTEC bay device, example

9.7.3. Controlling
Depending on the parameterization of your system, you can perform control interventions of
the process via detailed diagrams.
SICAM PAS CC provides different control modes:
• Switching with enabling
• Select before Operate with enable
• Synchronized switching
The example below illustrates the switching of a circuit breaker from OFF to ON with
enabling.
• Select the circuit breaker. Next, select Switching from the context menu.
The switching dialog parameterized for this circuit breaker (information object) is now
displayed.

SICAM PAS Page 43 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 18- Introducing the switching operation

• Click the ON button.


The enabling can now be performed in the next dialog window.

Picture 19- Switching operation - enable

• Click the Enable button.

SICAM PAS Page 44 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

Picture 20- Switching operation completed

The switching operation is executed. The circuit breaker icon changes to the ON operating
state.
The switching operation and the command feedback are logged in the event list.

9.7.4. Substation Control Functions


SICAM PAS provides a series of functions tailored to the requirements of substation control
tasks. These include:
• Switching authority
• Bay blocking
• Telecontrol blocking
• Time synchronization
• Fault recording

9.7.4.1. Switching Authority


In distributed systems, the switching authority defines which layer has the switching
authority. The bay control layer, the station control layer or the control center layer can have
the switching authority.
Besides local/remote switching by means of the key switches of the bay devices, a
distinction between local and remote control can be made on the station control layer.

SICAM PAS Page 45 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

The switching authority can be defined for the specific channel, i. e. one telecontrol channel
has the switching authority, whereas the others and the local control have no authority.

9.7.4.2. Bay Blocking


To perform maintenance tasks on a feeder, it might be useful to interrupt the data exchange
in control and monitoring direction with the bay devices concerned.
The bay blocking can be enabled or disabled for a specific device.
If the bay blocking is set, value changes of the process information and the status
information are not transmitted.
The bay blocking is visualized by the graphical representation variants of the switching
objects.
Setting and clearing of the bay blocking is logged in the event list of the SICAM PAS CC
HMI.
In addition to this, you can specify during the parameterization whether the information
affected by the bay blocking are also marked individually as Not topical in the event list.

9.7.4.3. Telecontrol Blocking


To perform maintenance tasks in a station, it might be useful to interrupt the communication
with higher-level control centers in the control and monitoring direction.
The telecontrol blocking can be enabled or disabled for a specific channel.
If a telecontrol blocking is set, the local control has the full volume of information available.
Setting and clearing of the telecontrol blocking is logged in the event list of the SICAM PAS
CC control and display system.

9.7.4.4. Time Synchronization

If your SICAM PAS Station Unit is to take over the time synchronization of bay devices,
substations and SICAM PAS CC, this can be performed via a DCF 77 or GPS time signal
receiver manufactured by the Hopf company. The SICAM PAS Station Unit itself can also
be synchronized via this time signal.

9.7.4.5. Ethernet station bus


In the case of system configurations with an Ethernet station bus (IEC 61850), a separate
time master can be used on the Ethernet which synchronizes all connected devices, the
SNTP clients, as an SNTP server (Simple Network Time Protocol).

SICAM PAS Page 46 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

In this case, the SICAM PAS Station Unit also acts as the SNTP client with regard to the
time synchronization. Nevertheless, it performs the synchronization of the devices
connected to the SICAM PAS Station Unit via other protocols.

9.7.4.6. Fault Recording


For protection devices connected to a SICAM PAS Station Unit via the PROFIBUS FMS,
IEC 61850 or IEC 60870-5-103 protocols, the fault records created in these devices are
transmitted automatically. These fault records are archived automatically in communication-
specific directories on the fullserver or DIP.
The fault records transmitted can be evaluated using SICAM Recpro.
SICAM Recpro consists of the following components:
• SICAM Recpro Explorer
for the management and evaluation of fault record archives in combination with an
evaluation program.
• SICAM Recpro Collector
for the generation and management of a central fault record archive
• ComtradeView
for the visualization of fault records
SIGRA 4 can be used for a comprehensive and sophisticated fault record analysis. This
analysis tool calculates further tags and graphically represents the fault records in different
views.

SICAM PAS Page 47 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

10. REQUIREMENTS AND NORMS


10.1. Climatic and Ambient Conditions

Factor Operation Transport and Storage

Ambient temperature 795 hPa to 1080


0 °C to 55 °C –40 °C to 70 °C
hPa 1) 660 hPa to 1080

relative humidity (RH) 10 % to 90 % 10 % to 90 %

acceptable air pressure 795 hPa to 1080 hPa 1) 660 hPa to 1080 hPa

0.5 K/min, no condensation (but not to exceed 10 K in 30


acceptable temperature changes
minutes)

1) At higher altitudes (i.e. > 2000 m), reduced ventilation may make it necessary to reduce the maximum
operating temperature and use a fan.

10.2. Physical Requirements

Factor Operation Transportation and Storage

Oscillation Fc test, 20 cycles on 3 axes: 10


10 cycles on 3 axes: 5 to 9 Hz: 3.5
stressw. IEC in acc. to 61 Hz: 0.2 mm amplitude 61
mm amplitude 9 to 500 Hz: 9.8 m/s2
60068-2-6 to 500 Hz: 19.6 m/s2

Shock stress Ea test, half-sine, 3 each per


inIEC 60068-2- acc. w. axis in both directions: 300
27 m/s2, 11 msec

Shock stress in acc. w. Half-sine, 1000 shocks per axis:


IEC 60068-2-29 250 m/s2, 6 msec

SICAM PAS Page 48 / 49 1/10/2005


MREC
AGH GHALA 63/20kV Substation Automation
SICAM PAS Solution, System Description

10.2.1. Electromagnetic Compatibility

Specification Testing in Accordance with


Interference immunity against discharge of static
electricity (ESD)
• Discharge through the air EN 61000-4-2:1995 8 kV 1) 4 kV 1)
•Discharge on contact

Interference immunity against fast transient interference


(bursts)
• Power supply cables for 120/230 V AC EN 61000-4-4:1995 2 kV 2 kV 2)
• Signal cables (input/output and bus cables)

EN 61000-4-5:1995 1 kV symmetrical 4) 2
kV unsymmetrical 4) 0,5 kV symmetrical 3)
Interference immunity against surge voltages 3) 0,5 kV unsymmetrical 3)
• Power supply cables for 120/230 V AC • Power supply
cables for 24 V DC

Interference immunity against electro-magnetic fields 1) EN 61000-4-3:1996 10 V/m 5) 80% AM (1


• Amplitude-modulated HF, 80 to 1000 MHz kHz)

EN 61000-4-3:1996
Interference immunity against electro-magnetic fields 1) ENV 50204:1995
• Pulse-modulated HF, 900 MHz 10 V/m 5)
50% ED, 200 Hz repetition frequency

Interference immunity against cable-conducted


EN 61000-4-6:1996 10 V 5) 80% AM (1
interference, induced by high-frequency fields
kHz) source impedance 150 W
• 0.15 to 80 MHz

Interference emission1) EN 55011:1991, Group 1


• Emission via the field (CISPR11:1997+A1:1999) limit value class
• Interference emission via power cable A limit value class A

SICAM PAS Page 49 / 49 1/10/2005

Das könnte Ihnen auch gefallen