APPENDIX

ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD

Copyright © 2009 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
APPENDIX http://www.entecene.co.kr

Table of Contents

Appendix A. Menu Description & Default Setting ….……….………............………...............1

Appendix B. Logic Bit Attributes & Description ………………….………………………......21

Appendix C. Default User PLC Equation …………..………..………………………………….35

ENHANCED TECHNOLOGY i
APPENDIX http://www.entecene.co.kr

Appendix A. Menu Description & Default Setting

Table A-1. Menu Description & Default Setting (1/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT

1.GLOBAL SETTING
1.SYSTEM
1.POWER LINE
Frequency* Power line nominal frequency (50, 60 Hz) 60

Reference Voltage Reference voltage set (A, B, C, NONE) A

Phase Rotation Power line phase rotation (ABC, ACB) ABC

2.CURRENT SENSING
PHA CT Ratio Set phase current ratio (1~2000) 1 1000

GND CT Ratio Set ground current ratio(1~5000) 1 1000

SEF CT Ratio Set SEF current ratio(0(OFF), 0.1~1000.0) 0.1 1000.0

PHA CT Pol’ Set phase CT pole direction (Forward, Reverse) Forward

SEF CT Pol’ Set SEF CT pole direction (Forward, Reverse) Forward

3.VOLTAGE SENSING
1V Connect Type 1st Voltage connector (NONE, WYE, DELTA) WYE

1st Voltage connector


(Applicable for lower than Ver. 3.93 of ETR300-R : 2.00~350.00V,
1V 2nd(V) Applicable for Ver. 3.93~3.99 of ETR300-R : 1.00~350.00V, 0.01 4.00
Applicable for Ver. 4.00~4.15 of ETR300-R : 2.00~350.00V,
Applicable for Ver. 4.16 or higher of ETR300-R : 1.00~350.00V)

1V Ratio 1st Voltage connector (10.0~6500.0) 0.1 3300.0

2V Connect Type 2nd Voltage Connector (NONE, WYE, DELTA) WYE

2nd Voltage Connector


(Applicable for lower than Ver. 3.93 of ETR300-R : 2.00~350.00V,
2V 2nd(V) Applicable for Ver. 3.93~3.99 of ETR300-R : 1.00~350.00V, 0.1 4.0
Applicable for Ver. 4.00~4.15 of ETR300-R : 2.00~350.00V,
Applicable for Ver. 4.16 or higher of ETR300-R : 1.00~350.00V)

2V Ratio 2nd Voltage Connector (10.0~6500.0) 0.1 3300.0

2V INS-Type* Installed VT sensing type in 2V side (3P, 1P-R, 1P-S, 1P-T) 3P

*. NOTE ) “2V INS-Type” setting shall be Ver. 3.80 of ETR300-R or higher to be indicated. .

Source Side Select the Source side of System (1V, 2V) 1V

4.CB OPENING TIME


CB Opening Time Select CB Opening Time (0.000~1.000 sec) 0.001 0.016 sec

5.GAS SENSOR TYPE


Gas Sensor Type Type (NONE, TYPE1, TYPE2) NONE

ENHANCED TECHNOLOGY 1
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (2/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
6.TIME ZONE *
Sign* Display the receive UTC time and the local time off-set direction. +

Hour* Set the difference of “Hour” between UTC and Local time.(0~23hour) 1 9

Min* Set the difference of “Minute” between UTC and Local time. (0~59min) 1 0

Time Syn’ Ref* Set Reference Time Type from GPS (LOCAL, GMT) GMT

*. NOTE ) The default value of settings marked with * can vary according to the option type.

2.Communication
1. Protocol Setup
1. DNP3 Protocol Setup

SLAVE1:
ENABLE
Function Use DNP3 protocol or not (DISABLE, ENABLE)
SLAVE2:
DISABLE
SLAVE1:PORT1
COM Port Select DNP3 communication port (PORT1, PORT2, PORT3)
SLAVE2:PORT2

D/L Confirm Enable data link layer confirm (NO, YES, SOME) SOME

D/L Frame Dly’ Set Data Link frame Delay Time (10~5000msec) 10 100

D/L Retries Data link layer retries (0, 1, 2) 1 0

D/L Timeout Data link layer time-out (1~255 sec) 1 10

A/L Timeout Application layer time-out (1~255 sec) 1 15

Master Addr’ Master station address (0~65534) 1 65534

SLAVE1 : 1
DNP Address Slave address (0~65534) 1
SLAVE2 : 0

SLAVE1 : 15
SBO Time Select before operate time-out (1~255 sec) 1
SLAVE2 : 30

Init Unsol Select Initial Unsolicited Response (DISABLE, ENABLE) ENABLE

Unsol Time The Unsolicited Time (0~60 sec) 1 5

Unsol Type The unsolicited type (NOTRIG, PERIOD) NOTRIG

Unsol Retries The Unsolicited Retries (0, 1, 2) 1 0

Class 1 Enable unsolicited class 1 (DISABLE, ENABLE) ENABLE

Class 2 Enable unsolicited class 2 (DISABLE, ENABLE) ENABLE

Class 3 Enable unsolicited class 3 (DISABLE, ENABLE) ENABLE

TCP/UDP Select TCP or UDP select TCP

TCP Port TCP port number (0~65535) 1 20000

2 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (3/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
UDP Port UDP port number (0~65535) 1 20001

Master IP Oct 1 Select the IP Address for DNP3 Communication (0~255) 1 192

Master IP Oct 2 Select the IP Address for DNP3 Communication (0~255) 1 168

Master IP Oct 3 Select the IP Address for DNP3 Communication (0~255) 1 7

Master IP Oct 4 Select the IP Address for DNP3 Communication (0~255) 1 202

Keep Alive Check Tm Keep alive interval (0(OFF), 1~600 sec) 1 4

Fragment Size Fragment size (64~2048) 1 2048

Time Req(m) Set interval time for synchronization time (0(OFF), 1~30000 min) 1 OFF

2. IEC60870-5-101 Protocol Setup

Function Use IEC60870-5-101 protocol or not (DISABLE, ENABLE) DISABLE

COM Port Select COM Port.(PORT1, PORT2, PORT3) PORT1

Address IEC60870-5-101 Address (1~65535) 1 1

ASDU Addr Application Service Data Unit Address (0~65535) 1 0

Cyclic Period Cyclic Period (1~60000 sec) 1 60

Event Period Event Transmission Period (0~255 sec) 1 15

Set the Data retires number


Retries (Applicable for lower than Ver. 3.6 of ETR300-R : 0~2, 1 0
Applicable for Ver. 3.6 or higher of ETR300-R: 0 ~ 255)
Conf. Timeout The confirm timeout (1~255 sec) 1 10

Max Poll Tim The max poll delay (1~255 sec) 1 10

ADSU Addr Size* Size of common address of ASDU(1~2) 1 2

Link Confirm* Link layer confirm mode (NEVER, ALWAYS) ALWAYS

Link Addr Size* Link Address Size (1~2) 1 1

Rx Frame Size* Maximum size of receive frame (0~261) 1 261

Maximum amount of time to wait for a complete frame after receiving


Rx Frame TO* 1 15
the frame sync (0(OFF), 1~255sec)
Tx Frame Size* Maximum size of transmit frame (0~261) 1 261

COT Size* Size of Cause of transmission (1~2) 1 1

IOA Size* Size of information object address (1~3) 1 2

Allowed to send one character response instead of a fixed length NACK


One Ch Response* NO
when no response data available(NO, YES)
Frame Repet’ TO* The time out for repetition of frames (0(OFF), 1~255sec) 1 30

Select Timeout* The period after a previously received select will timeout (0(OFF), 1~255sec) 1 5

Whether to send Activation Termination upon completion of commands


CMD Termination* NO
other than set point commands(NO, YES)

ENHANCED TECHNOLOGY 3
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (4/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
Whether to send Activation Termination upon completion of set point
CSE Termination* YES
commands(NO, YES).
Clock Sync’ Evt* Whether to generate spontaneous clock synchronization events (NO, YES) YES

MSP Time-Tag** Time tag format for single-point (CP56, CP24) CP56

MIT Time-Tag** Time tag format for integrated totals (CP56, CP24) CP56

Time tag format for measured value and normalized value, in case of
MME Time-Tag** CP56
general event (CP56, CP24)
Time tag format for measured value and normalized value in fault
Flt Time-Tag** CP56
current event (CP56, CP24)
*. NOTE ) 1. The above setting marked with * shall be Ver. 3.6 or higher of ETR300-R to be indicated.
2. In case ETR300 is the standard type, the above setting marked with ** shall be Ver. 3.9 or higher of ETR300-R to be
indicated.
3. In case ETR300 is the External I/O option type, the above setting marked with ** shall be Ver. 4.1 or higher of
ETR300-R to be indicated.
3. IEC60870-5-104 Protocol Setup

Function Use IEC60870-5-104 protocol or not (DISABLE, ENABLE) DISABLE

COM Port It is fixed in PORT3 PORT3

ASDU Addr Application Service Data Unit Address (0~65535) 1 0

Cyclic Period Cyclic Period (1~60000 sec) 1 60

Time Out(t0) Timeout of connection (1~255 sec) 1 120

Time Out(t1) Timeout of send (1~255 sec) 1 15

Time Out(t2) Timeout for acking in case of no data t2<t1 (1~255 sec) 1 10

Time Out(t3) Timeout for sending test frames in case of a long idle state (1~255 sec) 1 20

Event Period Event Transmission Period (0~255 sec) 1 15

TCP Port No TCP port number (0~65535) 1 2404

Rx Frame Size* Maximum size of receive frame (0~255) 1 255

Tx Frame Size* Maximum size of transmit frame (0~255) 1 255

Select Timeout* The period after a previously received select will timeout (0(OFF), 1~255sec) 1 5

Whether to send Activation Termination upon completion of commands


CMD Ternination* YES
other than set point commands(NO, YES)
Whether to send Activation Termination upon completion of set point
CSE Ternination* YES
commands(NO, YES).
Clock Sync’ Evt* Whether to generate spontaneous clock synchronization events (NO, YES) YES

MSP Time-Tag** Time tag format for single-point (CP56, CP24) CP56

MIT Time-Tag** Time tag format for integrated totals (CP56, CP24) CP56

Time tag format for measured value and normalized value, in case of
MME Time-Tag** CP56
general event (CP56, CP24)
Time tag format for measured value and normalized value in fault
Flt Time-Tag** CP56
current event (CP56, CP24)

4 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (5/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
*. NOTE ) 1. The above setting marked with * shall be Ver. 3.6 or higher of ETR300-R to be indicated.
2. In case ETR300 is the standard type, the above setting marked with ** shall be Ver. 3.9 or higher of ETR300-R to be
indicated.
3. In case ETR300 is the External I/O option type, the above setting marked with ** shall be Ver. 4.1 or higher of
ETR300-R to be indicated.
4. MODBUS Protocol Setup

Function Use MODBUS protocol or not (DISABLE, ENABLE) DISABLE

COM Port Select COM Port (PORT1, PORT2, PORT3, PORT4) PORT3

TCP/UDP Select TCP or UDP select TCP

TCP Port TCP port number (1~65535) 1 502

UDP Port UDP port number (0~65535) 1 20001

Slave Address Slave Address number (1~254) 1 1

Tx Delay Set Tx Delay Time (0.00(OFF), 0.01~300.00 sec) 0.01 0.05

2. Port Setup
1. PORT1(232) Setup

Baud Rate Select the baud rate for PORT1 (1200, 2400, 4800, 9600, 19200 bps) 9600

Parity Bit Select whether to use Parity Bit (NONE, ODD, EVEN) NONE

Data Bit Select the Data Bit (7, 8) 8

Stop Bit Select the Stop Bit. (1, 2) 1

Modem Sel Select the type of communication wire (2W, 4W, DIAL, NONE) 4W

CTS Usage Select whether to use CTS signal or not (DISABLE, ENABLE) ENABLE

DCD Usage Set whether to use DCD signal (DISABLE, ENABLE) DISABLE

RTS Usage Select whether to use RTS Usage (OFF, ON, AUTO) AUTO

CTS CheckOut Set a CTS CheckOut time (1~255 sec) 1 2

DCD CheckOut Set a DCD CheckOut time (10~30000 msec) 10 5000

TX PreDelay Set a tx pre-delay time (5~500 msec) 5 10

TX PostDelay Set a tx post-delay time( 10~500 msec) 5 50

2. PORT2(485) Setup

Baud Rate Select the baud rate for PORT2 (1200, 2400, 4800, 9600, 19200 bps) 9600

Parity Bit Set whether to use Parity Bit, and set a type (NONE, ODD, EVEN) NONE

Data Bit Select the Data Bit (7, 8) 8

Stop Bit Select the Stop Bit (1, 2) 1

Line Type Select a physical port for communication (RS422, RS485) RS422

CA Delay Set a CA Delay Time (0.00~240.00) 0.01 1.00

ENHANCED TECHNOLOGY 5
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (6/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
3. PORT3(EHTERNET) Setup
IP Addr Oct1 Set the IP Address (0~255) 1 192

IP Addr Oct2 Set the IP Address (0~255) 1 168

IP Addr Oc3 Set the IP Address (0~255) 1 7

IP Addr Oct4 Set the IP Address (0~255) 1 212

Gateway Oct1 Set the Gateway Address (0~255) 1 192

Gateway Oct2 Set the Gateway Address (0~255) 1 168

Gateway Oct3 Set the Gateway Address (0~255) 1 7

Gateway Oct4 Set the Gateway Address (0~255) 1 1

SubnetMask Oct1 Set the Subnet mask Address (0~255) 1 255

SubnetMask Oct2 Set the Subnet mask Address (0~255) 1 255

SubnetMask Oct3 Set the Subnet mask Address (0~255) 1 255

SubnetMask Oct4 Set the Subnet mask Address (0~255) 1 0

keep Alive Function keep Alive Function use or not (DISABLE, ENABLE) ENABLE

k-Alv Idle T Keep Alive Idle Time (0(OFF),1~600sec) 1 4

k-Alv Interval Keep Alive Interval (0(OFF),1~600 sec) 1 2

k-Alv Retry Keep Alive Retry (0~255) 1 3

4. PORTF(232) Setup

Baud Rate Baud Rate (1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bps) 38400

3. Dialup Modem Setup


1. DIALUP MODEM 1

CALLING STRING AT command for dial (ATD, ATDT, ATDP) ATD

CALLING NUMBER Modem(Master station) phone number


AT&C1 Q1 E0 M0
INITIAL STRING Initial commands for your modem
&D2+CRM=129
2. DIALUP MODEM 2

CALLING STRING AT command for dial (ATD, ATDT, ATDP) ATD

CALLING NUMBER Modem(Master station) phone number


AT&C1 Q1 E0 M0
INITIAL STRING Initial commands for your modem
&D2+CRM=129
3. CONNECTION

Cmd Res’ TO Command response timeout(0~255s) 1 2

Connect TO Connect timeout(0~255s) 1 30

Idle Time Set idle time (0~255) 1 60

6 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (7/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
4. Event & Etc Setup
AEvt Method Select the Analog Event Type (OFF, TH, DB, BOTH) OFF

AEvt Skip at Ft Select DB/TH Event Skip at fault pickup (NO, YES) NO

Daily Max I Set whether to use Daily Max I or not (DISABLE, ENABLE) DISABLE

Flt ‘I’ Evt Select the Fault ‘I’ Event (NO, YES, 1SHOT) YES

Aver. Load Calc T Set the Average Load Calculation Time (1/2/3/4/5/6/10/12/15/20/30 min) 15

BI Queue size* Set the binary queue size (32, 64, 128, 256) 256

BI Evt Mode Set the binary event mode (ALL, LAST) ALL

AI Queue size * Set the analog queue size (32, 64, 128, 256) 256

AI Evt Mode Set the analog event mode (ALL, LAST) ALL

CI Queue size * Set the counter queue size (32, 64, 128, 256) 256

CI Evt Mode Set the counter event mode (ALL, LAST) ALL

Time Syn’ Type Set the time synch type (LOCAL, GMT) LOCAL

Time Tag Type Set the time tag type (LOCAL, GMT) LOCAL

CI Frz Preiod** Set the period to freeze counter by itself. (OFF, 1~60000min.) 1 OFF

*. NOTE )1. Applicable for lower than Ver 3.5 of ETR300-R, the default value of “BI Queue size”, “AI Queue size” and “CI Queue
size” setting is “32”.
2. In case ETR300 is the standard type, the above setting marked with ** shall be Ver. 3.9 or higher of ETR300-R to be indicated.
3. In case ETR300 is the External I/O option type, the above setting marked with ** shall be Ver. 4.1 or higher of
ETR300-R to be indicated.

5. FTP File Transfer Setup


FTP Mode-R Select the protocol for file transfer (DNP, FTPC, FTPS, USER) DNP

FTP Mode-W Select the protocol for file transfer (DNP, FTPC, FTPS, USER) DNP

FTP Dev Set the Device Type for FTP file classification (Space ~‘z’ ) REC

FTP Dev. No Set the Device Number for FTP file classification (Space ~‘z’ ) REC001

FTP ID Set the ID of the device used for the connection with FTP (Space ~‘z’ ) ENTEC

Password Set the FTP connection password (Space ~‘z’ ) 1234

FTP Passive Select the FTP connecting method (DISABLE, ENABLE) DISABLE

3. Event Recorder
Wave Capture Select whether to use Wave capture or not (ON, OFF) ON

Wave S/R Select a number of sampling for wave capture (16, 32, 64, 128 sample) 64

Wave Pre-Cycle Select a number of Pre-Cycle (1~5 cycle) 1 5

ENHANCED TECHNOLOGY 7
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (8/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
4. Monitoring
1. Synchronism Check
Function Select whether to use Function or not (OFF, ON) OFF

D.V. Max Set the Dead line maximum voltage (0.00~1.25) 0.01 0.50

L.V. Min Set the Live line minimum voltage (0.00~1.25) 0.01 0.85

M.V.D Set the maximum voltage difference (0.00~1.25) 0.01 0.10

Set the maximum angle difference


M.A.D(Deg) (Applicable for lower than Ver. 3.4 of ETR300-R : 0(OFF), 5~80 deg, 1 15
Applicable for Ver. 3.4 or higher of ETR300-R : 1~100 deg)
M.F.D(Hz) Set the maximum frequency difference (0.00~5.00 Hz) 0.01 2.00

Sync Phase Select the synchronism phase (ALL, R(AB), S(CB), T(AC) ) ALL

Time delay Set a delay time of synchronism check (0.0~180.0sec) 0.1 1.0

2.Operation Count
Function Select whether to monitor Recloser operation count (OFF, ON) OFF

Limit Set a number for Recloser alarming. (1~20000) 1 10000

Count set It is to set the same operation number of circuit breaker (0~10000) 1 0

3. Contact Wear
Function Select whether to monitor Recloser contact wear. (OFF, ON) OFF

Pickup (%) Set a number for Recloser alarming. (0.0~50.0 %) 0.1 20.0

Rated Volt(kV) Set the power line nominal voltage (15, 27, 38 kV) 27

Interrupt(kA) Enter the capacity of rated Interrupter (5.0 ~ 50.0 kA) 0.1 12.5

No. Max I Enter the capacity of rated Interrupter (1~999) 1 100

A Wear Set Set Circuit breaker phase A (0.00~100.00 %) 0.01 100.00

B Wear Set Set Circuit breaker phase B (0.00~100.00 %) 0.01 100.00

C Wear Set Set Circuit breaker phase C (0.00~100.00 %) 0.01 100.00

4. Battery Test
Period Set a time period for automatic battery test (0(OFF), 1~720 hour) 1 24

5. Power Quality Monitoring


1.PQM Function

Function Select whether to use PQM function (DISABLE, ENABLE) DISABLE

2.Interrupt

Level Set Interrupt detect level for power quality (0(OFF), 0.10~0.49 pu) 0.01 0.10

Time Set a interrupt detecting time (0.5~10.0 cycle) 0.5 2.0

8 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (9/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
3. Sag

Level Set a voltage sag for power quality (0(OFF), 0.50~0.99 pu) 0.01 0.90

Time Set a time to detect voltage sag (0.5~10.0 cycle) 0.5 2.0

4. Swell

Level Set a detect level of voltage swell (0(OFF), 1.01~1.50 pu) 0.01 1.20

Time Set a time to detect voltage swell. (0.5~10.0 cycle) 0.5 2.0

5.Harmonics

VTHD Pickup Detect level of Voltage THD (0(OFF), 0.5~100.0 %) 0.1 OFF

VTHD Delay Detect time of Voltage THD (0.2~60.0 sec) 0.1 1.0

ITHD Pickup Detect level of Current THD (0(OFF), 0.5~100.0 %) 0.1 OFF

ITHD Delay Detect time of Current THD (0.2~60.0 sec) 0.1 1.0

6. Current Unbalance

Level Detect level of Current Unbalance for Power Quality (0(OFF), 1~100 %) 1 30

Time Set a detect time of current unbalance (0.1~60.0 sec) 0.1 4.0

7. Voltage Unbalance

Level Detect level of Voltage Unbalance for Power Quality (0(OFF), 1~100 %) 1 30

Time Set a detect time of voltage unbalance (0.1~60.0 sec) 0.1 4.0

8. Under Voltage

Level Set an under voltage detect level for power quality (0(OFF), 0.30~0.95pu) 0.01 0.80

Time Set an under voltage detecting time (0.0~180.0 sec) 0.1 4.0

9. Over Voltage

Level Set an over voltage detect level for power quality (0(OFF), 1.05~1.50 pu) 0.01 1.20

Time Set an over voltage detecting time (0.0~180.0 sec) 0.1 4.0

10. Under Frequency

Level Set an under frequency detect level for power quality(0(OFF), 46.00~59.98 Hz) 0.01 59.50

Time Set an under frequency detecting time (0.03~10.00 sec) 0.01 3.00

11. Current Unbalance/THD Detect Limit

Min. I Set the minimum current value to current unbalance and THD (0~630 A) 1 60

6. TD Monitor
TD1 Rate Set Transducer 1(TD1) monitoring range (1~200) 1 40

TD1 Ratio Set Transducer 1(TD1) ratio (1~3000) 1 1

TD1 Offset Set Transducer 1(TD1) ratio (-10000~+10000) 1 0

ENHANCED TECHNOLOGY 9
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (10/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
TD1-1 Type Set Transducer 1(TD1) Under or Over (UNDER, OVER) UNDER

TD1-1 PU Set TD1 pickup value (0(OFF), 0~6000.0) 0.1 21.0

TD1-1 Delay Set a delay time of TD1 (0.01~600.00 sec) 0.01 2.00

TD1-2 Type Set 2nd monitoring element of TD1 (UNDER, OVER) UNDER

TD1-2 PU* Set 2nd pickup value of TD1 (0(OFF), 0~6000.0) 0.1 19.0

TD1-2 Delay Set 2nd delay time of TD1 (0.01~600.00 sec) 0.01 2.00

TD2~5 is the same setting as TD1.

7. Fault Locator*
Function* Fault Locator (OFF,ON) OFF

Length(km)* Length of Feeder (0.1-99.9 km) 0.1 50.0

Z1(RES)* Real impedance of the feeder positive sequence (0.1-6000.0 ohms) 0.1 10.0

Z1(IND)* Imaginary impedance of the feeder positive sequence (0.1-6000.0 ohms) 0.1 10.0

Z0(RES)* Real impedance of the feeder zero sequence (0.1-6000.0 ohms) 0.1 10.0

Z0(IND)* Imaginary impedance of the feeder zero sequence (0.1-6000.0 ohms) 0.1 10.0

*. NOTE ) “Fault Locator” menu is supported from Ver 3.8 of ETR300-R.

5. Loop Control
Type Select Set loop control function (NONE, SEC, MID, TIE) NONE

VRS to S/M The setting values are used in SEC, MID (VS, VL) VS

VRS to Tie The setting value is used in TIE (VS, VL, VS&VL) VS

VS wire Type (3PN,3PP,1PN(A),1PN(B),1PN(C),1PP(AB),1PP(BC),1PP(CA) ) 3PN

VL wire Type (3PN,3PP,1PN(A),1PN(B),1PN(C),1PP(AB),1PP(BC),1PP(CA) ) 3PN

CAS to Mid Select whether to use automatic setting change in MID type (OFF, ON) OFF

CAS to Tie Set value is used in TIE (OFF, VS, VL, BOTH) OFF

LC After Cl Setting value is used in SEC (DISABLE, ENABLE) DISABLE

LC After Op It is applicable to TIE type Recloser.(DISABLE, ENABLE) DISABLE

OT Both DL Setting value is used in TIE (0.01~600.00 sec) 0.01 5.00

AR Time Setting value is used in SEC, MID (0.01~600.00 sec) 0.01 5.00

DLV Max(%) Sense Dead Line Voltage (20.0~70.0 %) 0.1 20.0

LLV Min(%) Sense Live Line Voltage (50.0~85.0 %) 0.1 70.0

DLPT Delay Dead Bus Pickup Time Delay setting (0.01~600.00 sec) 0.01 60.00

*. NOTE ) The default value of settings marked with * can vary according to the option type.

LLPT Delay Live Bus Pickup Time Delay setting (0.01~600.00 sec) 0.01 10.00

10 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (11/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
DLRT Delay Dead Bus Reset Time Delay setting (0.01~600.00 sec) 0.01 5.00

NRT After LA Non Reclose Time After LC Action setting (0.00~600.00 sec) 0.01 15.00

6. Passcode
1.Passcode 1
2.Passcode 2
7. PLC
1.Common
1.Logic Timer

TM1-PU Set a pickup time of Logic timer 1 (0.01~600.00 sec) 0.01 0.05

TM1-DO Set a Dropout Time of Logic timer 1 (0.01~600.00 sec) 0.01 0.05

TM2~16 is the same setting as TM1.

2.Pulse Timer

PTM1 Set a output time of pulse timer 1 (0.01~600.00 sec) 0.01 0.01

PTM2~16 is the same setting as PTM1

3. Pulse Counter

PC1 Set output count value of Pulse counter 1 (1~60000) 1 1

PC2~16 is the same setting as PC1

2. DI/DO
1. Input Debounce Timer
IN101 Set an Input Debounce Time of IN101 (0.005~10.000 sec) 0.001 0.020

IN102~108, IN201~208 is the same setting as IN101

IN301~312 is the same setting as IN101. From Ver 4.00 of ETR300-R, IN301~312 settings indicated.

2. Output Pulse Timer

OUT101 Set an Output pulse time of OUT101 (0(BUFF), 0.01~10.00 sec) 0.01 BUFF

OUT102~108, OUT201~208 is the same setting as OUT101.

OUT301~308 is the same setting as OUT101. From Ver 4.00 of ETR300-R OUT301~308 settings indicated.

8. Others
1. Time Display Type
TIME DISP’ TYPE Set the displays turn (YMD, MDY) MDY

2. Panel Sleep Time


PANEL SLEEP TIME Set a time for sleep mode delay (OFF, 1~100 min) 1 OFF

ENHANCED TECHNOLOGY 11
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (12/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT

3. Vo Select
Vo SELECT* Select the zero sequence voltage (H/W, SEQ) SEQ

*. NOTE ) The default value of settings marked with * can vary according to the option type.

4. Factory Debug: This menu is for Manufacturer’s maintenance purpose.


5. Auto Setting Group Change*
Function* Set whether to use auto setting group change. (DISABLE/ENABLE) DISABLE

Interval* Setting group is changed if power flow changes during the set time.(10~180 sec) 1 30

*. NOTE ) The location of “AUTO SGRP CHANGE” menu. may be different according to the version of ETR300-R firmware.

6. H/W OPTION*
EX-IO?* Select where to install the external I/O unit ETIO10 (NO/YES) NO

GPS/IRIG?* Select where to install the time synchronization module (NO/YES) NO

*. NOTE ) “H/W OPTION” menu is supported from Ver 3.8 of ETR300-R.

2.GROUP SETTING
1.PROTECTION (Primary, Alternate, Editbank Setup)
1.Operation
Lockout-PHA Select the total number of the phase trip operations (1~5) 1 4

Lockout-GND Select the total number of the ground trip operations (1~5) 1 4

Lockout-SEF Select the total number of the SEF trip operations (1~5) 1 4

Lockout-NEG Select the total number of the negative sequence trip operations (1~5) 1 4

Fast Curve-PHA Select the number of the phase fast curve operations (0~5) 1 2

Fast Curve-GND Select a number for the ground fast curve operations (0~5) 1 2

Fast Curve-NEG Select a number for the negative sequence fast curve operations (0~5) 1 2

2.Intervals
PHASE/NEG SEQ’

Set the reclose1 Interval


Reclose 1 (Applicable for lower than Ver 3.4 of ETR300-R : 0.5~600.0 sec, 0.1 0.6
Applicable for Ver 3.4 or higher of ETR300-R : 0.1~600.0 sec)
Reclose 2 Set the reclose2 Interval (1~1800 sec) 1 2

Reclose 3 Set the reclose3 Interval (1~1800 sec) 1 2

Reclose 4 Set the reclose4 Interval (1~1800 sec) 1 15

GROUND and SEF reclose is the same setting as PHASE/NEG SEQ’.

OTHERS

Reset T(AR) It is to select Reset time during auto reclosing (3~180 sec) 1 30

12 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (13/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
Reset T(LO) To set Lockout reset time (1.00~600.00 sec) 0.01 10.00

C/P Wait Waiting time to get power supply (1.00 ~ 600.00 sec) 0.01 60.00

3.Pickup Current
Phase Set the pickup current of Phase (OFF,10~1600A) 1 500

Ground Set the pickup current of Ground (OFF,10~1600A) 1 250

SEF Set the pickup current of SEF (OFF,0.1~160.0A) 0.1 OFF

Neg Seq’ Set the pickup current of negative sequence (OFF,10~1600A) 1 500

4.Phase Fast
Curve Select the desired curve type (A(101), B(117), ..., DEF-10S) ANSI-V1

*. NOTE ) Applicable for lower than 3.4 of ETR300-R, the default value of “Curve” setting is “ANSI-NI”.

Time Dial Select Time dial and multiply it to selected curve. (0.05~15.00) 0.01 1.00

Time Add Select Time adder and add it on the curve (0.00~10.00 sec) 0.01 0.00

M.R.T Minimum Response Time setting (0.00~10.00 sec) 0.01 0.00

Reset Method Select the reset method of phase fast protection. (INST, LINEAR) INST

Low Set DT Set trip time to be a definite time. (0(OFF), 1~ 600sec) 1 OFF

5.Phase Delay: The setting is very similarly to the phase fast setting.
6.Ground Fast
1.Ground Fast Setup

Curve Select the desired curve type (A(101), B(117), ..., DEF-10S) ANSI-V1

*. NOTE ) Applicable for lower than 3.4 of ETR300-R, the default value of “Curve” setting is “ANSI-NI”.

Time Dial Select Time dial and multiply it to selected curve (0.05~15.00) 0.01 1.00

Time Add Select Time adder and add it on the curve (0.00~10.00 sec) 0.01 0.00

M.R.T Minimum Response Time setting (0.00~10.00 sec) 0.01 0.00

Reset Method Select the reset method of phase fast protection. (INST, LINEAR) INST

Low Set DT Set trip time to be a definite time. (0(OFF), 1~ 600sec) 1 OFF

7.Ground Delay: The setting is very similarly to the Ground fast setting.
8.SEF Element
SEF delay time set
(Applicable for lower than Ver. 3.94 of ETR300-R : 0.0~180.0 sec,
Time Delay Applicable for Ver. 3.94~3.99 of ETR300-R : 0.0~600.0 sec, 0.1 5.0
Applicable for Ver. 4.00~4.16 of ETR300-R : 0.0~180.0 sec,
Applicable for Ver. 4.17 or higher of ETR300-R : 0.0~600.0 sec)

9.NEG SEQ Function


Function Set NEQ delay protection function.(OFF, TR, AL,TR&AL) OFF

ENHANCED TECHNOLOGY 13
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (14/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
10.NEG SEQ Fast
Curve Select the desired curve type (A(101), B(117), ..., DEF-10S) ANSI-V1

*. NOTE ) Applicable for lower than Ver. 3.4 of ETR300-R, the default value of “Curve” setting is “ANSI-NI”.

Time Dial Select Time dial and multiply it to selected curve (0.05~15.00) 0.01 0.50

Time Add Select Time adder and add it on the curve (0.00~10.00 sec) 0.01 0.00

M.R.T Set minimum response time (0.00~10.00 sec) 0.01 0.00

Reset Method Select the reset method of phase fast protection. (INST, LINEAR) INST

Low Set DT Set trip time to be a definite time. (0(OFF), 1~ 600sec) 1 OFF

11.NEG SEQ Delay: The setting is very similarly to the NEG SEQ Fast setting.
12.Phase High Current Trip (50P-1)
Sequence Active trip(0(OFF),1~5) 1 1

Pickup Set the pickup current of Phase High current Trip(0(OFF), 10~20000 A) 1 4000

Set Time Delay for phase high current trip


(Applicable for lower than Ver. 3.94 of ETR300-R : 0.00~1.00 sec,
Time Delay Applicable for Ver. 3.94~3.99 of ETR300-R : 0.00~10.00 sec, 0.01 0.00
Applicable for Ver. 4.00~4.16 of ETR300-R : 0.00~1.00 sec,
Applicable for Ver. 4.17 or higher of ETR300-R : 0.00~10.00 sec)

13. Ground High Current Trip (50G-1)


Sequence Active trip(0(OFF),1~5) 1 1

Pickup Set the pickup current of Ground High current Trip(0(OFF), 10~20000 A) 1 4000

Set Time Delay for ground high current trip


(Applicable for lower than Ver. 3.94 of ETR300-R : 0.00~1.00 sec,
Time Delay Applicable for Ver. 3.94~3.99 of ETR300-R : 0.00~10.00 sec, 0.01 0.00
Applicable for Ver. 4.00~4.16 of ETR300-R : 0.00~1.00 sec,
Applicable for Ver. 4.17 or higher of ETR300-R : 0.00~10.00 sec)

14. Negative Sequence High Current Trip (46(50)-1)


Sequence Active trip(0(OFF),1~5) 1 1

Pickup Set the pickup current of NEG High current trip(0(OFF), 10~20000 A) 1 4000

Set Time Delay for NEG high current trip


(Applicable for lower than Ver. 3.94 of ETR300-R : 0.00~1.00 sec,
Time Delay Applicable for Ver. 3.94~3.99 of ETR300-R : 0.00~10.00 sec, 0.01 0.00
Applicable for Ver. 4.00~4.16 of ETR300-R : 0.00~1.00 sec,
Applicable for Ver. 4.17 or higher of ETR300-R : 0.00~10.00 sec)

15. Phase High Current Lockout (50P-2)


Function Lockout function is activated (0(OFF),1~5 shot) 1 1

Pickup Set pickup current of Phase High Current Lockout (0(OFF),10~20000 A) 1 8000

14 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (15/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
Set phase high current lockout operation delay time.
(Applicable for lower than Ver. 3.94 of ETR300-R : 0.00~1.00 sec,
Time Delay Applicable for Ver. 3.94~3.99 of ETR300-R : 0.00~10.00 sec, 0.01 1.00
Applicable for Ver. 4.00~4.16 of ETR300-R : 0.00~1.00 sec,
Applicable for Ver. 4.17 or higher of ETR300-R : 0.00~10.00 sec)

16. Ground High Current Lockout (50G-2)


Function Set Lockout function is enable or not.(0(OFF),1~5 shot) 1 1

Pickup Set pickup current of Ground High Current Lockout (0(OFF), 10~20000 A) 1 8000

Set ground high current lockout operation delay time.


(Applicable for lower than Ver. 3.94 of ETR300-R : 0.00~1.00 sec,
Time Delay Applicable for Ver. 3.94~3.99 of ETR300-R : 0.00~10.00 sec, 0.01 0.00
Applicable for Ver. 4.00~4.16 of ETR300-R : 0.00~1.00 sec,
Applicable for Ver. 4.17 or higher of ETR300-R : 0.00~10.00 sec)

17. Negative Sequence High Current Lockout (46(50)-2)


Function Lockout function is activated (0(OFF),1~5 shot) 1 1

Pickup Set pickup current of NEG High Current Lockout (0(OFF), 10~20000 A) 1 8000

Set NEG high current lockout operation delay time.


(Applicable for lower than Ver. 3.94 of ETR300-R : 0.00~1.00 sec,
Time Delay Applicable for Ver. 3.94~3.99 of ETR300-R : 0.00~10.00 sec, 0.01 0.00
Applicable for Ver. 4.00~4.16 of ETR300-R : 0.00~1.00 sec,
Applicable for Ver. 4.17 or higher of ETR300-R : 0.00~10.00 sec)

18. Cold Load Pickup


Func-PHA Select whether to use CLPU Fucntion-PHA or not (OFF, ON) ON

Func-GND Select whether to use CLPU Fucntion-GND or not (OFF, ON) ON

Func-NEG Select whether to use CLPU Fucntion-NEG or not (OFF, ON) ON

Func-SEF Select whether to use CLPU Fucntion-SEF or not (OFF, ON) ON

PHA(A) Set phase inrush current restraint value (0(OFF), 10~20000A) 1 2000

Curve-PHA Select the desired curve type (A(101), B(117), ..., DEF-10S) N3

Time Dial-PHA Set a coefficient to apply to a set curve (0.05~15.00) 0.01 1.00

Time Addr-PHA Adding a time onto a set curve (0.00~10.00 sec) 0.01 0.00

M.R.T-PHA Minimum Response Time setting (0.00~10.00 sec) 0.01 0.00

GND(A) Set ground inrush current restraint value (0(OFF), 10~20000A) 1 2000

Curve-GND Select the desired curve type (A(101), B(117), ..., DEF-10S) N3

Time Dial-GND Set a coefficient to apply to a set curve (0.05~15.00) 0.01 1.00

Time Addr-GND Adding a time onto a set curve (0.00~10.00 sec) 0.01 0.00

M.R.T- GND Minimum Response Time setting (0.00~10.00 sec) 0.01 0.00

NEG(A) Set negative inrush current restraint value (0(OFF), 10~20000A) 1 2000

ENHANCED TECHNOLOGY 15
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (16/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
Curve-NEG Select the desired curve type (A(101), B(117), ..., DEF-10S) N3

Time Dial- NEG Set a coefficient to apply to a set curve (0.05~15.00) 0.01 1.00

Time Addr- NEG Adding a time onto a set curve (0.00~10.00 sec) 0.01 0.00

M.R.T- NEG Minimum Response Time setting (0.00~10.00 sec) 0.01 0.00

SEF(A) Set SEF inrush current restraint value (0(OFF), 0.1~2000.0A) 0.1 20

Outage Time Set a time to disable Cold load pickup (0.00~600.00 sec) 0.01 1.0

RMT Func-PHA Set whether to use Phase Minimum operation current reset function (OFF, ON) ON

Select the restore minimum time required for the inrush load
RMT Time-PHA (Applicable for lower than Ver 3.4 of ETR300-R : 0.00~60.00 sec, 0.01 3.00
Applicable for Ver 3.4 or higher of ETR300-R : 0.00~600.00 sec)
Cold load pickup Reset Time setting on phase inrush current
Rst Time-PHA (Applicable for lower than Ver 3.4 of ETR300-R : 0.00~60.00 sec, 0.01 3.00
Applicable for Ver 3.4 or higher of ETR300-R : 0.00~600.00 sec)
RMT Func-GND Set whether to use ground Minimum operation current reset function (OFF, ON) ON

Select the restore minimum time required for the inrush load
RMT Time-GND (Applicable for lower than Ver 3.4 of ETR300-R : 0.00~60.00 sec, 0.01 3.00
Applicable for Ver 3.4 or higher of ETR300-R : 0.00~600.00 sec)
Cold load pickup Reset Time setting on ground inrush current
Rst Time-GND (Applicable for lower than Ver 3.4 of ETR300-R : 0.00~60.00 sec, 0.01 3.00
Applicable for Ver 3.4 or higher of ETR300-R : 0.00~600.00 sec)
RMT Func-NEG Set whether to use negative Minimum operation current reset function (OFF, ON) ON

Select the restore minimum time required for the inrush load
RMT Time- NEG (Applicable for lower than Ver 3.4 of ETR300-R : 0.00~60.00 sec, 0.01 3.00
Applicable for Ver 3.4 or higher of ETR300-R : 0.00~600.00 sec)
Cold load pickup Reset Time setting on negative inrush current
Rst Time- NEG (Applicable for lower than Ver 3.4 of ETR300-R : 0.00~60.00 sec, 0.01 3.00
Applicable for Ver 3.4 or higher of ETR300-R : 0.00~600.00 sec)
RMT Func-SEF Set whether to use SEF Minimum operation current reset function (OFF, ON) ON

Select the restore minimum time required for the inrush load

RMT Time- SEF (Applicable for lower than Ver 3.4 of ETR300-R : 0.00~60.00 sec, 0.01 3.00

Applicable for Ver 3.4 or higher of ETR300-R : 0.00~600.00 sec)

Cold load pickup Reset Time setting on SEF inrush current

Rst Time- SEF (Applicable for lower than Ver 3.4 of ETR300-R : 0.00~60.00 sec, 0.01 3.00

Applicable for Ver 3.4 or higher of ETR300-R : 0.00~600.00 sec)

Make Use ‘I’ This setting changes the time of cold load pickup actives.(NO,YES) NO

E-CLP Multi’ Set the multiple of cold load. (1.0~5.0) 0.1 2.0

E-CLP Time(m) Set the cold load time. (1~720min) 1 10

16 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (17/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
19. Directional Controls (67)
1. Phase Directional Controls (67P)

Type Set phase direction type (NONE, FORWARE, REVERSE) NONE

M.T.A(V1) Enter the Maximum Torque Angle (0~359 degree) 1 60

M.P.V Set Minimum Polarizing to check Phase disconnect direction (0(OFF), 10~80%) 1 30

BLOCK OC Select whether to block the phase polarizing trip (NO, YES) NO

2. Ground Directional Controls (67G)

Type Set Ground direction type (NONE, FORWARE, REVERSE) NONE

M.T.A(-V0) Enter the maximum torque angle (0~359 degree) 1 60

M.P.V Set Minimum Polarizing Voltage to check ground fault direction. (0(OFF), 10~80%) 1 30

BLOCK OC Select whether to block the ground polarizing trip (NO, YES) NO

3. SEF Directional Controls

Type Set SEF direction type (NONE, FORWARE, REVERSE) NONE

M.T.A(-V0) Enter the maximum torque angle. (0~359 degree) 1 45

M.P.V Set Minimum Polarizing Voltage to check Negative Sequence direction.(0(OFF), 10~80%) 1 30

BLOCK OC Select whether to block the NEG polarizing trip. (NO, YES) NO

4. Negative Sequence Directional Controls (67(46))

Type Set NEG direction type. (NONE, FORWARE, REVERSE) NONE

M.T.A(-V2) Enter the maximum torque angle. (0~359 degree) 1 60

M.P.V Set Minimum Polarizing Voltage to check Negative Sequence direction.(0(OFF), 10~80%) 1 30

BLOCK OC Select whether to block the NEG polarizing trip. (NO, YES) NO

20.Voltage
1. Under/ Over voltage1 (27)

UV1 Function Under voltage function setting .(OFF, TR, AL, TR&AL) OFF

UV1 Pickup Set pickup voltage for UV1(0.10~1.40pu) 0.01 0.80

UV1 Delay Set time delay for UV1 (0.00~600.00 sec) 0.01 5.00

OV1 Function Over Voltage function setting (OFF, TR, AL, TR&AL) OFF

OV1 Pickup Pickup Voltage for OV1 (0.10~1.40pu) 0.01 1.10

OV1 Delay Time Delay for OV1 (0.00~600.00 sec) 0.01 5.00

Voltage Type Type (1P, 2P, 3P) 1P

Min. V Minimum Voltage (0.10~1.40 x VT)) 0.01 0.10

NVCL Func’ Select whether to close when normal voltage inputs.(OFF, ON) OFF

ENHANCED TECHNOLOGY 17
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (18/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
NVCL TD Set a delay time to close when normal voltage inputs.(0~60000sec) 1 30

NVCL Rst TD Set a delay time for NVCL function reset.(0~60000sec) 1 30

UV1 NVCL Lv Set the normal voltage based on under voltage(0.10~1.40xVT) 0.01 0.95

OV1 NVCL Lv Set the normal voltage based on over voltage(0.10~1.40xVT) 0.01 1.05

2. Under /Over voltage2 (27): It is the same setting as 1. Under/ Over voltage1 (27)

21.Frequency
1.Under / Over frequency

UF Pickup Under frequency pickup (0(OFF), 40.00~65.00 Hz) 0.01 OFF

UF TD Time Delay for under frequency detected. (0.00~600.00 sec) 0.01 2.00

OF Pickup Over frequency pickup (0(OFF), 40.00~65.00 Hz) 0.01 OFF

OF TD Time Delay for over frequency detected. (0.00~600.00 sec) 0.01 2.00

Min. V Minimum Voltage for frequency protection actives.(0.00~1.25 x VT) 0.01 0.10

Min. I Minimum Current for frequency protection actives.((0(OFF),1~630A) 1 OFF

NFCL Func’ Select whether to close when normal voltage inputs.(OFF, ON) OFF

NFCL TD Set a delay time to close when normal frequency inputs.(0~60000sec) 1 30

NFCL Rst TD Set a delay time for NFCL function reset.(0~60000sec) 1 30

UF NFCL Lv Set the normal frequency based on under frequency.(40.00~65.00Hz) 0.01 59.80

OF NFCL Lv Set the normal frequency based on over frequency.(40.00~65.00Hz) 0.01 60.20

22.User Curve
1.User Curve1

Factor a User defined curve factor α (0.0000~150.9999) 0.0001 59.5000

Factor b User defined curve factor β (0.0000~150.9999) 0.0001 2.0200

Factor c User defined curve factor γ (0.0000~150.9999) 0.0001 1.8000

Factor rt User defined curve factor rt (0.0000~150.9999) 0.0001 59.5000

2.User Curve2~4 : The same setting as 1.User Curve1.

23.Live Load Block


Function Select whether to use Live load block (OFF, REC, CLOSE, BOTH) OFF

Live Level Set pickup level of live line (0.10~0.90pu) 0.01 0.80

*. NOTE ) The default value of settings marked with * can vary according to the option type.

Detect Time Set a time to detect live line in load side (0~60000msec) 5 5

24.Hotline Tag : Refer to “PHASE FAST”, “GROUND FAST”, “SEF ELEMENT”


and “NEG SEQ FAST” menu.

18 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (19/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
25.Live Line
Live Line Lv Set the live line level (0.10~0.90pu) 0.01 0.30

Live Line Tm Set the delay time of live detect element (0.0~18 0.0sec) 0.1 4.0

26.Demand
Function Demand setting (OFF, TR, AL, TR&AL) TRIP

Interval Set the interval to calculate Demand current (5, 10, 15, 20, 30, 60 min) 5

PHA Pickup Set the Pickup current of phase Demand. (0(OFF), 10~1600A) 1 600

PHA Time Delay Set the detect delay time of phase Demand. (0.00~600.00 sec) 0.01 10.00

GND Pickup Set the Pickup current of ground Demand. (0(OFF), 10~1600A) 1 300

GND Time Delay Set the detect delay time of ground Demand.(0.00~600.00 sec) 0.01 10.00

NEQ Pickup Set the Pickup of NEQ Demand.(0(OFF), 10~1600A) 1 600

NEQ Time Delay Set the detect time of NEQ-PHA Demand. (0.00~600.00 sec) 0.01 10.00

27. Other Element


Seq' Coordi' Select whether to use Sequence Coordination or not (OFF, ON) OFF

L.O Priority Set the Lockout priority (PHA, GND) GND

F/I Reset Faulted Indicator reset method (AUTO, MANUAL) AUTO

D/T M-Close Time delay for manual close (0.00~600.00 sec) 0.01 0.00

28. ON/OFF Level


On Level Set normal voltage level (0.70~0.85pu) 0.01 0.80

Off Level Set phase open/loss level (0.30~0.75pu) 0.01 0.50

Detect Time Set delay time of phase open or loss (0.0~180.0sec) 0.1 4.0

29. Alarm Current


PHA-Pickup Set the pickup value of phase Alarm Current.(0(OFF), 10~1600A) 1 OFF

*. NOTE ) Applicable for lower than Ver. 3.4 of ETR300-R, the default value of “PHA-Pickup” setting is “400A”.

PHA-Time Set the detect time of phase alarm Current.(0.0~180.0 sec) 0.1 2.0

GND-Pickup Set the pickup value of ground Alarm Current. (0(OFF), 10~1600A) ) 1 OFF

*. NOTE ) Applicable for lower than Ver. 3.4 of ETR300-R, the default value of “GND-Pickup” setting is “70A”.

GND-Time Set the detect time of ground Alarm Current.(0.0~180.0 sec) 0.1 2.0

NEG-Pickup Set the pickup value of NEG Alarm Current.(0(OFF), 10~1600A) 1 OFF

*. NOTE ) Applicable for lower than Ver. 3.4 of ETR300-R, the default value of “NEG-Pickup” setting is “400A”.

NEG-Time Set the detect time of NEG alarm Current. (0.0~180.0 sec) 0.1 2.0

ENHANCED TECHNOLOGY 19
APPENDIX http://www.entecene.co.kr

Table A-1. Menu Description & Default Setting (20/20)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
30. Loss of Phase
Function Loss of Phase function enable or disable.(OFF, TR, AL, TR&AL) OFF

Pickup Pickup Voltage(0.00~1.25pu) 0.01 0.30

Time Delay Set the delay time for loss of phase detected.(0.10~100.00) 0.01 20.00

2.Select Setbank
Primary Select a Bank of Primary setting group. (BANK 1~6) BANK1

Alternate Select a bank of Alternate setting group. (BANK 1~6) BANK2

Edit Select a bank of Edit. (BANK 1~6) BANK3

20 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Appendix B. Logic Bit Attribute & Description

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (1/14)


NOTE

1) DIAG: Checked Logic bit can be used with Diagnostic Event.


2) SYS: Checked Logic bit can be used with System Event.
3) OPE: Checked Logic bit can be used with Operation Event.
4) SCH: Checked Logic bit can be used with Set Change Event.
5) PQM: Checked Logic bit can be used with PQM Event.

NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

0 ACFAIL      AC POWER FAIL - INST

1 ACTSG1      SETTING GROUP1 ACTIVE

2 ACTSG2    SETTING GROUP2 ACTIVE

3 ACTSG3   SETTING GROUP3 ACTIVE

4 ACTSG4   SETTING GROUP4 ACTIVE

5 ACTSG5   SETTING GROUP5 ACTIVE

6 ACTSG6   SETTING GROUP6 ACTIVE

7 ADBUSY    AD CONVERSION BUSY OCCURRED

8 ADCPUERR   AD CPU ERROR

9 ADREFERR    AD REF' VOLT ERROR

10 BATBAD   BATTERY BAD

11 BTCGBAD    BATTERY & CHARGE BAD

12 BTCMD   BATTERY TEST COMMAND

13 BTING   BATTERY TESTING

14 CF   RELAY CLOSE FAIL OCCURRED

15 CHGBAD   CHARGE BOARD BAD

16 CLASS1  CLASS 1 ENABLED

17 CLASS2   CLASS 2 ENABLED

18 CLASS3   CLASS 3 ENABLED

19 CLBLK   CLOSE BLOCK STATUS

20 CLDRST   COLD RESTART(DNP)

21 CLPGACT   CLPU ACTIVE - GND

22 CLPPACT   CLPU ACTIVE - PHA

ENHANCED TECHNOLOGY 21
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (2/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

23 CLPQACT   CLPU ACTIVE - NEQ

24 CLST   CLOSE STATUS

25 CPULINK   CPU MODULE LINK STATUS

26 DACFAIL   AC POWER FAIL - DELAY

27 DC11T   DC1-1 TIMEOUT

28 DC12T   DC1-2 TIMEOUT

29 DC21T  DC2-1 TIMEOUT

30 DC22T  DC2-2 TIMEOUT

31 DC31T  DC3-1 TIMEOUT

32 DC32T  DC3-2 TIMEOUT

33 DC41T   DC4-1 TIMEOUT

34 DC42T   DC4-2 TIMEOUT

35 DC51T   DC5-1 TIMEOUT

36 DC52T   DC5-2 TIMEOUT

37 DCTRLK   CONTROL UNLOCK

38 DEMTR   DEMAND TRIP

39 DGPROT   GROUND PROTECTION DISABLED

40 DHLTAG   HOT-LINE TAG DISABLED

41 DIGADC   DIAGNOSTIC ADC (A/D Converter)

42 DIGALM    DIAGNOSTIC ALARM

43 DIGASET   DIAGNOSTIC ALTERNATE SETTING

44 DIGCL   DIAGNOSTIC CLOSE COIL

45 DIGCNT   DIAGNOSTIC COUNT

46 DIGCONT   DIAGNOSTIC CONTACT WEAR

47 DIGCPU   DIAGNOSTIC COMM' MODULE

48 DIGDO   DIAGNOSTIC DO

49 DIGERR   DIAGNOSTIC ERROR

50 DIGEVT   DIAGNOSTIC EVENT

51 DIGFROM   DIAGNOSTIC FLASH-ROM

52 DIGGSET   DIAGNOSTIC GLOBAL SETTING

53 DIGLOG   DIAGNOSTIC PLC SETTING

54 DIGMEM   DIAGNOSTIC MEMORY

55 DIGOP   DIAGNOSTIC TRIP COIL

22 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (3/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

56 DIGPSET   DIAGNOSTIC PRIMARY SETTING

57 DIGRTC   DIAGNOSTIC RTC

58 DIGSPM5   SYSTEMP POWER(-5V) ALARM

59 DIGSPOW   DIAGNOSTIC SYSTEM POWER

60 DIGSPP5   SYSTEMP POWER(+5V) ALARM

61 DIGSPU   DIAGNOSTIC SIGNALPROCESSING UNIT

62 DIGTCNT   DIAGNOSTIC OPERATE COUNTER

63 DIGTEMP   CONTROLLER TEMP' ALARM

64 DO0C  DO 0 - CLOSE

65 DO0T  DO 0 - TRIP

66 DO10C  DO 10 - CLOSE

67 DO10T  DO 10 - TRIP

68 DO11C  DO 11 - CLOSE

69 DO11T  DO 11 - TRIP

70 DO12C  DO 12 - CLOSE

71 DO12T  DO 12 - TRIP

72 DO13C  DO 13 - CLOSE

73 DO13T  DO 13 - TRIP

74 DO14C  DO 14 - CLOSE

75 DO14T   DO 14 - TRIP

76 DO15C   DO 15 - CLOSE

77 DO15T   DO 15 - TRIP

78 DO16C   DO 16 - CLOSE

79 DO16T   DO 16 - TRIP

80 DO17C    DO 17 - CLOSE

81 DO17T   DO 17 - TRIP

82 DO18C   DO 18 - CLOSE

83 DO18T   DO 18 - TRIP

84 DO19C   DO 19 - CLOSE

85 DO19T   DO 19 - TRIP

86 DO1C  DO 1 - CLOSE

87 DO1T  DO 1 - TRIP

88 DO20C   DO 20 - CLOSE

ENHANCED TECHNOLOGY 23
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (4/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

89 DO20T   DO 20 - TRIP

90 DO21C   DO 21 - CLOSE

91 DO21T   DO 21 - TRIP

92 DO22C   DO 22 - CLOSE

93 DO22T    DO 22 - TRIP

94 DO23C    DO 23 - CLOSE

95 DO23T    DO 23 - TRIP

96 DO24C   DO 24 - CLOSE

97 DO24T   DO 24 - TRIP

98 DO25C   DO 25 - CLOSE

99 DO25T   DO 25 - TRIP

100 DO26C   DO 26 - CLOSE

101 DO26T   DO 26 - TRIP

102 DO27C   DO 27 - CLOSE

103 DO27T   DO 27 - TRIP

104 DO28C  DO 28 - CLOSE

105 DO28T  DO 28 - TRIP

106 DO29C  DO 29 - CLOSE

107 DO29T  DO 29 - TRIP

108 DO2C  DO 2 - CLOSE

109 DO2T  DO 2 - TRIP

110 DO30C  DO 30 - CLOSE

111 DO30T  DO 30 - TRIP

112 DO31C   DO 31 - CLOSE

113 DO31T     DO 31 - TRIP

114 DO3C     DO 3 - CLOSE

115 DO3T   DO 3 - TRIP

116 DO4C   DO 4 - CLOSE

117 DO4T   DO 4 - TRIP

118 DO5C   DO 5 - CLOSE

119 DO5T  DO 5 - TRIP

120 DO6C   DO 6 - CLOSE

121 DO6T   DO 6 - TRIP

24 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (5/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

122 DO7C   DO 7 - CLOSE

123 DO7T   DO 7 - TRIP

124 DO8C   DO 8 - CLOSE

125 DO8T   DO 8 - TRIP

126 DO9C   DO 9 - CLOSE

127 DO9T  DO 9 - TRIP

128 DPROG1  PROGRAM 1 DISABLED (LOOP DISABLED)

129 DPROG2  PROGRAM 2 DISABLED (LOOPAUTO RESTORE DISABLED)

130 DPROT  PROTECTION DISABLED

131 DREC   RECLOSED DISABLED

132 DRMT   REMOTE DISABLED

133 DROPEN   DOOR OPEN STATUS

134 DSPLINK   DSP MODULE LINK STATUS

135 DSPROT   SEF PROTECTION DISABLED

136 E52A   CLOSE/OPEN STATUS

137 EALTSG   ALT' SET GROUP ENABLED

138 ECAPW   EXTERNAL WAVEFORM CAPTURE

139 ECTRLK   CONTROL LOCK

140 EFTRIP   FAULT TRIP LOGIC

141 EGPROT   GROUND PROTECTION ENABLED

142 ENGRCMD   ENERGY RESET COMMAND

143 EPRISG   PRI' SET GROUP ENABLED

144 EPROG1   PROGRAM 1 ENABLED (LOOP ENABLED)

145 EPROG2   PROGRAM 2 ENABLED (LOOPAUTO RESTORE ENABLED)

146 EPROT   PROTECTION ENABLED

147 EREC    RECLOSE ENABLED

148 ERMT   REMOTE ENABLED

149 ESPROT   SEF PROTECTION ENABLED

150 EXTRCMD   EXTERNAL TRIP COMMAND

151 EXTRIP   EXTERNAL TRIP OPERATE

152 FIFOR   FAULT CURRENT FORWARD DIRECTION

153 FIRCMD    FI RESET COMMAND

154 FIREV   FAULT CURRENT REVERSE DIRECTION

ENHANCED TECHNOLOGY 25
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (6/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

155 FORPFT   FORWARD POWER FLOW TIMEOUT

156 FWCCMD   FAULT WAVE CLEAR COMMAND

157 GASHIGH   GAS HIGH STATUS

158 GASLOW   GAS LOW STATUS

159 GDEMA   DEMAND CURRENT ALARM - GND

160 GDEMT   DEMAND CURRENT TIMEOUT - GND

161 GPDCMD  GROUND PROTECTION DISABLE COMMAND

162 GPECMD  GROUND PROTECTION ENABLE COMMAND

163 GPSFAIL  GPS LINK FAIL

164 HLTAG  HOT-LINE TAG

165 HLTDCMD   HOT-LINE TAG DISABLE COMMAND

166 HLTECMD  HOT-LINE TAG ENABLE COMMAND

167 IHARM02T   CURRENT HARMONIC 2ND-FREQ' TIMEOUT

168 IHARM03T    CURRENT HARMONIC 3RD-FREQ' TIMEOUT

169 IHARM04T    CURRENT HARMONIC 4TH-FREQ' TIMEOUT

170 IHARM05T   CURRENT HARMONIC 5TH-FREQ' TIMEOUT

171 IHARM06T   CURRENT HARMONIC 6TH-FREQ' TIMEOUT

172 IHARM07T   CURRENT HARMONIC 7TH-FREQ' TIMEOUT

173 IHARM08T    CURRENT HARMONIC 8TH-FREQ' TIMEOUT

174 IHARM09T    CURRENT HARMONIC 9TH-FREQ' TIMEOUT

175 IHARM10T    CURRENT HARMONIC 10TH-FREQ' TIMEOUT

176 IHARM11T    CURRENT HARMONIC 11TH-FREQ' TIMEOUT

177 IHARM12T    CURRENT HARMONIC 12TH-FREQ' TIMEOUT

178 IHARM13T    CURRENT HARMONIC 13TH-FREQ' TIMEOUT

179 IHARM14T    CURRENT HARMONIC 14TH-FREQ' TIMEOUT

180 IHARM15T    CURRENT HARMONIC 15TH-FREQ' TIMEOUT

181 IHARM16T    CURRENT HARMONIC 16TH-FREQ' TIMEOUT

182 IHARM17T   CURRENT HARMONIC 17TH-FREQ' TIMEOUT

183 IHARM18T   CURRENT HARMONIC 18TH-FREQ' TIMEOUT

184 IHARM19T   CURRENT HARMONIC 19TH-FREQ' TIMEOUT

185 IHARM20T   CURRENT HARMONIC 20TH-FREQ' TIMEOUT

186 IHARM21T   CURRENT HARMONIC 21TH-FREQ' TIMEOUT

187 IHARM22T   CURRENT HARMONIC 22TH-FREQ' TIMEOUT

26 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (7/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

188 IHARM23T   CURRENT HARMONIC 23TH-FREQ' TIMEOUT

189 IHARM24T   CURRENT HARMONIC 24TH-FREQ' TIMEOUT

190 IHARM25T   CURRENT HARMONIC 25TH-FREQ' TIMEOUT

191 IHARM26T   CURRENT HARMONIC 26TH-FREQ' TIMEOUT

192 IHARM27T   CURRENT HARMONIC 27TH-FREQ' TIMEOUT

193 IHARM28T    CURRENT HARMONIC 28TH-FREQ' TIMEOUT

194 IHARM29T   CURRENT HARMONIC 29TH-FREQ' TIMEOUT

195 IHARM30T   CURRENT HARMONIC 30TH-FREQ' TIMEOUT

196 IHARM31T   CURRENT HARMONIC 31TH-FREQ' TIMEOUT

197 IN101   INPUT PORT1-01

198 IN102   INPUT PORT1-02

199 IN103   INPUT PORT1-03

200 IN104   INPUT PORT1-04

201 IN301*   INPUT PORT3-01

202 IN302*   INPUT PORT3-02

203 IN303*   INPUT PORT3-03

204 IN304*   INPUT PORT3-04

205 IN305*   INPUT PORT3-05

206 IN306*   INPUT PORT3-06

207 IN307*   INPUT PORT3-07

208 IN308*   INPUT PORT3-08

209 IN309*   INPUT PORT3-09

210 IN310*   INPUT PORT3-10

211 IN311*   INPUT PORT3-11

212 IN312*   INPUT PORT3-12

213 INRUSH   INRUSH OCCURED

214 ITHDTA   CURRENT THD TIMEOUT - A

215 ITHDTB   CURRENT THD TIMEOUT - B

216 ITHDTC   CURRENT THD TIMEOUT - C

217 ITHDTT   CURRENT THD TIMEOUT - T

218 LASCHG1    ALTERNATE SETTING CHANGED - LOCAL

219 LCLOSE      CLOSE BY LOCAL


*. NOTE ) Above * marked Logic Bit "IN301 ~ IN312" are available from Ver 4.00 of ETR300-R and also applicable if
the external I/O unit ETIO10 is installed.

ENHANCED TECHNOLOGY 27
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (8/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

220 LGSCHG    GLOBAL SETTING CHANGED : LOCAL

221 LKCMD   LOCK COMMAND

222 LOPEN    OPEN BY LOCAL

223 LPSCHG1    PRIMARY SETTING CHANGED - LOCAL

224 M3POT    THREE-POLE OPEN TIMEOUT

225 MCLOSE    CLOSE BY MANUAL

226 MDRCMD   MAX DEMAND RESET COMMAND

227 MLOCK   MECHENISM LOCK

228 MOPEN    OPEN BY MANUAL

229 NALTSG   INTERFACE SW ALTSG COMMAND

230 NBACHK   INTERFACE SW BATT TEST COMMAND

231 NCLOSE   INTERFACE SW CLOSE COMMAND

232 NCTRLK   INTERFACE SW CTRLK COMMAND

233 NDCTRLK   INTERFACE SW DISABLE CTRLK COMMAND

234 NFIRST  INTERFACE SW FI RESET COMMAND

235 NGPROT   INTERFACE SW GPROT COMMAND

236 NHLTAG  INTERFACE SW HLT COMMAND

237 NOBATT  BATTERY NO EXIST

238 NOPEN   INTERFACE SW OPEN COMMAND

239 NPROG1  INTERFACE SW PROG1 COMMAND

240 NPROG2  INTERFACE SW PROG2 COMMAND

241 NPROT  INTERFACE SW PROT COMMAND

242 NREC   INTERFACE SW REC COMMAND

243 NSPROT   INTERFACE SW SPROT COMMAND

244 OPBLK   OPEN BLOCK STATUS

245 OPST   OPEN STATUS

246 OUT101   OUTPUT PORT1-01

247 OUT102   OUTPUT PORT1-02

248 OUT103   OUTPUT PORT1-03

249 OUT104   OUTPUT PORT1-04

250 OUT301*   OUTPUT PORT3-01

251 OUT302*   OUTPUT PORT3-02


*. NOTE ) Above * marked Logic Bit "OUT301 ~ OUT308" are available from Ver 4.00 of ETR300-R and also
applicable if the external I/O unit ETIO10 is installed.

28 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (9/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

252 OUT303*   OUTPUT PORT3-03

253 OUT304*   OUTPUT PORT3-04

254 OUT305*   OUTPUT PORT3-05

255 OUT306*   OUTPUT PORT3-06

256 OUT307*   OUTPUT PORT3-07

257 OUT308*   OUTPUT PORT3-08

258 OVCAT   OVER-CURRENT - A PHA

259 OVCBT   OVER-CURRENT - B PHA

260 OVCCT   OVER-CURRENT - C PHA

261 OVCGT   OVER-CURRENT - GND

262 PASCHG1    ALTERNATE SETTING CHANGED - PROGRAM

263 PCRCMD   PEAK CURRENT RESET COMMAND

264 PDCMD   PROTECTION DISABLE COMMAND

265 PDEMA   DEMAND CURRENT ALARM - PHA

266 PDEMT   DEMAND CURRENT TIMEOUT - PHA

267 PECMD   PROTECTION ENABLE COMMAND

268 PFIA   PERMANENT FAULT INDICATOR - A PHA

269 PFIB   PERMANENT FAULT INDICATOR - B PHA

270 PFIC   PERMANENT FAULT INDICATOR - C PHA

271 PFIG   PERMANENT FAULT INDICATOR - GND

272 PFIN   PERMANENT FAULT INDICATOR - SEF

273 PFIQ   PERMANENT FAULT INDICATOR - NEQ

274 PFIS   PERMANENT FI SET

275 PG1DCMD  PROGRAM 1 DISABLE COMMAND

276 PG1ECMD   PROGRAM 1 ENABLE COMMAND

277 PG2DCMD  PROGRAM 2 DISABLE COMMAND

278 PG2ECMD  PROGRAM 2 ENABLE COMMAND

279 PGSCHG    GLOBAL SETTING CHANGED : PROGRAM

280 PPSCHG1   PRIMARY SETTING CHANGED - PROGRAM

281 PQCAPW  PQM WAVEFORM CAPTURE

282 PQCCCMD  PQM COUNT CLEAR COMMAND

283 PQCUBT   UNBALANCE TIMEOUT - CURRENT

284 PQINTAT   INTERRUPTION TIMEOUT - A PHA

ENHANCED TECHNOLOGY 29
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (10/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

285 PQINTBT   INTERRUPTION TIMEOUT - B PHA

286 PQINTCT   INTERRUPTION TIMEOUT - C PHA

287 PQINTMO   INTERRUPTION MOMENTARY OCCURED

288 PQINTSU   INTERRUPTION LONG TIME OCCURED

289 PQINTTE   INTERRUPTION TEMPORARY OCCURED

290 PQITCCMD   PQM INTERRUPTION TIME CLEAR COMMAND

291 PQOVAT   PQ OVER VOLT TIMEOUT - A PHA

292 PQOVBT   PQ OVER VOLT TIMEOUT - B PHA

293 PQOVCT   PQ OVER VOLT TIMEOUT - C PHA

294 PQOVRT   PQ OVER VOLT TIMEOUT - R PHA

295 PQOVST   PQ OVER VOLT TIMEOUT - S PHA

296 PQOVTT   PQ OVER VOLT TIMEOUT - T PHA

297 PQRCMD   PQM RESET COMMAND

298 PQSAGAT   SAG TIMEOUT - A PHA

299 PQSAGBT   SAG TIMEOUT - B PHA

300 PQSAGCT   SAG TIMEOUT - C PHA

301 PQSAGIN   SAG INSTANTANEOUS OCCURED

302 PQSAGLT   SAG LONG TIME OCCURED

303 PQSAGMO   SAG MOMENTARY OCCURED

304 PQSAGTE   SAG TEMPORARY OCCURED

305 PQSWEAT   SWELL TIMEOUT - A PHA

306 PQSWEBT   SWELL TIMEOUT - B PHA

307 PQSWECT   SWELL TIMEOUT - C PHA

308 PQSWEIN   SWELL INSTANTANEOUS OCCURED

309 PQSWELT   SWELL LONG TIME OCCURED

310 PQSWEMO   SWELL MOMENTARY OCCURED

311 PQSWETE   SWELL TEMPORARY OCCURED

312 PQUNDFT    PQ UNDER FREQUENCY TIMEOUT

313 PQUVAT   PQ UNDER VOLT TIMEOUT - A PHA

314 PQUVBT   PQ UNDER VOLT TIMEOUT - B PHA

315 PQUVCT   PQ UNDER VOLT TIMEOUT - C PHA

316 PQUVRT   PQ UNDER VOLT TIMEOUT - R PHA

317 PQUVST   PQ UNDER VOLT TIMEOUT - S PHA

30 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (11/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

318 PQUVTT   PQ UNDER VOLT TIMEOUT - T PHA

319 PQVUB1T   UNBALANCE TIMEOUT - VOLTAGE1

320 PQVUB2T   UNBALANCE TIMEOUT - VOLTAGE2

321 PQWCCMD   PQM WAVE CLEAR COMMAND

322 PSLEEP   PANEL SLEEP MODE

323 PWDOWN   POWER DOWN SIGNAL

324 QDEMA   DEMAND CURRENT ALARM - NEQ

325 QDEMT   DEMAND CURRENT TIMEOUT - NEQ

326 RASCHG1    ALTERNATE SETTING CHANGED - REMOTE

327 RCLOSE    CLOSE BY REMOTE

328 RECDCMD   RECLOSING DISABLE COMMAND

329 RECECMD   RECLOSING ENABLE COMMAND

330 REVPFT   REVERSE POWER FLOW TIMEOUT

331 RGSCHG    GLOBAL SETTING CHANGED : REMOTE

332 ROPEN    OPEN BY REMOTE

333 RPSCHG1    PRIMARY SETTING CHANGED - REMOTE

334 SBTCMD   SELF BATTERY TEST COMMAND

335 SELFTERR    SELF TEST ERROR

336 SELFTOK    SELF TEST OK

337 SGCACMD   SETTING GROUP CHANGE COMMAND - ALT

338 SGCPCMD   SETTING GROUP CHANGE COMMAND - PRI

339 SPDCMD   SEF PROTECTION DISABLE COMMAND

340 SPECMD   SEF PROTECTION ENABLE COMMAND

341 STTB  TROUBLE STATUS

342 SYSRST    SYSTEM RESTART

343 TFIS  TEMPORARY FI SET

344 TRF   RELAY TRIP FAIL OCCURRED

345 TTCMD   TRIP TEST COMMAND

346 TTING  TRIP TESTING

347 ULKCMD  UNLOCK COMMAND

348 VHARM02T   VOLT HARMONIC 2ND-FREQ' TIMEOUT

349 VHARM03T   VOLT HARMONIC 3RD-FREQ' TIMEOUT

350 VHARM04T   VOLT HARMONIC 4TH-FREQ' TIMEOUT

ENHANCED TECHNOLOGY 31
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (12/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

351 VHARM05T   VOLT HARMONIC 5TH-FREQ' TIMEOUT

352 VHARM06T   VOLT HARMONIC 6TH-FREQ' TIMEOUT

353 VHARM07T   VOLT HARMONIC 7TH-FREQ' TIMEOUT

354 VHARM08T   VOLT HARMONIC 8TH-FREQ' TIMEOUT

355 VHARM09T   VOLT HARMONIC 9TH-FREQ' TIMEOUT

356 VHARM10T   VOLT HARMONIC 10TH-FREQ' TIMEOUT

357 VHARM11T   VOLT HARMONIC 11TH-FREQ' TIMEOUT

358 VHARM12T   VOLT HARMONIC 12TH-FREQ' TIMEOUT

359 VHARM13T   VOLT HARMONIC 13TH-FREQ' TIMEOUT

360 VHARM14T   VOLT HARMONIC 14TH-FREQ' TIMEOUT

361 VHARM15T   VOLT HARMONIC 15TH-FREQ' TIMEOUT

362 VHARM16T   VOLT HARMONIC 16TH-FREQ' TIMEOUT

363 VHARM17T   VOLT HARMONIC 17TH-FREQ' TIMEOUT

364 VHARM18T   VOLT HARMONIC 18TH-FREQ' TIMEOUT

365 VHARM19T   VOLT HARMONIC 19TH-FREQ' TIMEOUT

366 VHARM20T   VOLT HARMONIC 20TH-FREQ' TIMEOUT

367 VHARM21T   VOLT HARMONIC 21TH-FREQ' TIMEOUT

368 VHARM22T   VOLT HARMONIC 22TH-FREQ' TIMEOUT

369 VHARM23T   VOLT HARMONIC 23TH-FREQ' TIMEOUT

370 VHARM24T   VOLT HARMONIC 24TH-FREQ' TIMEOUT

371 VHARM25T   VOLT HARMONIC 25TH-FREQ' TIMEOUT

372 VHARM26T   VOLT HARMONIC 26TH-FREQ' TIMEOUT

373 VHARM27T   VOLT HARMONIC 27TH-FREQ' TIMEOUT

374 VHARM28T   VOLT HARMONIC 28TH-FREQ' TIMEOUT

375 VHARM29T   VOLT HARMONIC 29TH-FREQ' TIMEOUT

376 VHARM30T   VOLT HARMONIC 30TH-FREQ' TIMEOUT

377 VHARM31T   VOLT HARMONIC 31TH-FREQ' TIMEOUT

378 VTHDTA    VOLT THD TIMEOUT - A

379 VTHDTB   VOLT THD TIMEOUT - B

380 VTHDTC   VOLT THD TIMEOUT - C

381 VTHDTT   VOLT THD TIMEOUT - T

382 VTLFAILT   VT FAIL TIMEOUT(LOAD)

383 VTSFAILT   VT FAIL TIMEOUT(SOURCE)

32 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (13/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

384 WCAPCMD   WAVE CAPTURE COMMAND

385 Y25AT   PHA UNBALANCE TIMEOUT - A PHA

386 Y25BT   PHA UNBALANCE TIMEOUT - B PHA

387 Y25CT   PHA UNBALANCE TIMEOUT - C PHA

388 Y25PT   PHA UNBALANCE TIMEOUT

389 Y27LVLT   LIVE VOLTAGE TIMEOUT

390 Y27LVST   LIVE VOLTAGE TIMEOUT

391 Y27P1T   UNDER VOLTAGE 1 TIMEOUT

392 Y27P2T   UNDER VOLTAGE 2 TIMEOUT

393 Y47A2T   OPEN VOLTAGE TIMEOUT - A PHA

394 Y47AT   OPEN VOLTAGE TIMEOUT - A PHA

395 Y47B2T   OPEN VOLTAGE TIMEOUT - B PHA

396 Y47BT   OPEN VOLTAGE TIMEOUT - B PHA

397 Y47C2T   OPEN VOLTAGE TIMEOUT - C PHA

398 Y47CT   OPEN VOLTAGE TIMEOUT - C PHA

399 Y59P1T   OVER VOLTAGE 1 TIMEOUT

400 Y59P2T   OVER VOLTAGE 2 TIMEOUT

401 Y79CY   SEQUENCE CYCLE

402 Y79LO   SEQUENCE LOCKOUT

403 Y79LOLB   SEQUENCE L.O FOR LB

404 Y79RS   SEQUENCE RESET

405 Y81CLL   FREQUENCY ELEMENT NORMAL CLOSE LATCH

406 Y81CLLO   FREQUENCY ELEMENT NORMAL CLOSE LOCKOUT

407 Y81OT  OVER FREQUENCY TIMEOUT

408 Y81TRL   FREQUENCY ELEMENT TRIP LATCH

409 Y81UT  UNDER FREQUENCY TIMEOUT

410 YCLPACT  Extended CLPU Act

411 YHCLO   HIGH CURRENT LOCKOUT

412 YHCTR  HIGH CURRENT TRIP

413 YIOCTR  INST' OC TRIP OCCURED

414 YLOPA  LOSS OF PHA-A

415 YLOPAL   LOSS OF PHA-ALARM

416 YLOPB   LOSS OF PHA-B

ENHANCED TECHNOLOGY 33
APPENDIX http://www.entecene.co.kr

Table B-1. LOGIC BIT ATTRIBUTES & DESCRIPTION (14/14)


NO LOGIC BIT DIAG SYS OPE SCH PQM DESCRIPTION

417 YLOPC   LOSS OF PHA-C

418 YLOPTR   LOSS OF PHA-TRIP

419 YNEQARM   NEQ ALARM

420 YSH0   RECLOSE SEQUENCE 0

421 YSH1   RECLOSE SEQUENCE 1

422 YSH2   RECLOSE SEQUENCE 2

423 YSH3   RECLOSE SEQUENCE 3

424 YSH4   RECLOSE SEQUENCE 4

425 YTMB1A   CLOSE ON TO FAULT LOCKOUT

426 YTOCTR   TIME OC TRIP OCCURED

427 YVTARM   VOLTAGE ALARM

428 YVTCL   VOLTAGE ELEMENT NORMAL CLOSE

429 YVTCLL   VOLTAGE ELEMENT NORMAL CLOSE LATCH

430 YVTCLLO   VOLTAGE ELEMENT NORMAL CLOSE LOCKOUT

431 YVTFAIL   VOLTAGE TR FAIL

432 YVTTRL   VOLTAGE ELEMENT TRIP LATCH

433 YZSVLT   ZERO-SEQUENCE VOLTAGE TIMEOUT(LOAD)

434 YZSVST   FREQUENCY ELEMENT NORMAL CLOSE LOCKOUT

34 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Appendix C. Default User PLC Equation

Table C-1. Default User PLC Equation (1/13)


NOTE

1) 0 : System Logic = OFF, 1 : System Logic = ON


2) Number of available Operand for one Equation : 8
3) Number of available Operator for one Equation : 7 (NOT, BRACKET not included)
4) Available Operator when setting Equation :
5) EQUATION: All of the banks have same equations for each product.
OPERATOR DESCRIPTION

* AND

+ OR

! NOT

( ) BRACKET

NO SYSTEM LOGIC EQUATION DESCRIPTION

1 IOUT101 0 OUTPUT PORT1-01 INPUT

2 IOUT102 0 OUTPUT PORT1-02 INPUT

3 IOUT103 0 OUTPUT PORT1-03 INPUT

4 IOUT104 0 OUTPUT PORT1-04 INPUT

5 BOUT101 0 OUTPUT PORT1-01 BLOCK

6 BOUT102 0 OUTPUT PORT1-02 BLOCK

7 BOUT103 0 OUTPUT PORT1-03 BLOCK

8 BOUT104 0 OUTPUT PORT1-04 BLOCK

9 IOUT201 0 OUTPUT PORT2-01 INPUT

10 IOUT202 CLOSE OUTPUT PORT2-02 INPUT

11 IOUT203 TRIP OUTPUT PORT2-03 INPUT

12 IOUT204 0 OUTPUT PORT2-04 INPUT

13 IOUT205 1 OUTPUT PORT2-05 INPUT

14 IOUT206 0 OUTPUT PORT2-06 INPUT

15 IOUT207 BTING OUTPUT PORT2-07 INPUT

16 IOUT208 TM13 OUTPUT PORT2-08 INPUT

17 BOUT201 0 OUTPUT PORT2-01 BLOCK

ENHANCED TECHNOLOGY 35
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (2/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
18 BOUT202 CLST OUTPUT PORT2-02 BLOCK

19 BOUT203 OPST OUTPUT PORT2-03 BLOCK

20 BOUT204 0 OUTPUT PORT2-04 BLOCK

21 BOUT205 0 OUTPUT PORT2-05 BLOCK

22 BOUT206 0 OUTPUT PORT2-06 BLOCK

23 BOUT207 ACFAIL OUTPUT PORT2-07 BLOCK

24 BOUT208 0 OUTPUT PORT2-08 BLOCK

25 LB01 0 LOGIC BIT-1

26 LB02 0 LOGIC BIT-2

27 LB03 0 LOGIC BIT-3

28 LB04 0 LOGIC BIT-4

29 LB05 0 LOGIC BIT-5

30 LB06 0 LOGIC BIT-6

31 LB07 0 LOGIC BIT-7

32 LB08 0 LOGIC BIT-8

33 LB09 0 LOGIC BIT-9

34 LB10 0 LOGIC BIT-10

35 LB11 0 LOGIC BIT-11

36 LB12 0 LOGIC BIT-12

37 LB13 DIGTEMP+DIGRTC+DIGFROM+DIGEVT+DIGCNT LOGIC BIT-13

38 LB14 DIGGSET+DIGPSET+DIGASET+DIGDO+DIGCPU+DIGCL+DIGOP LOGIC BIT-14

39 LB15 DIGSPP5+DIGSPM5+DIGADC+DIGSPU+DIGSPOW LOGIC BIT-15

40 LB16 !ERMT+ECTRLK LOGIC BIT-16

41 LSET01 0 LATCH-1 SET

42 LSET02 0 LATCH-2 SET

43 LSET03 0 LATCH-3 SET

44 LSET04 0 LATCH-4 SET

45 LSET05 0 LATCH-5 SET

46 LSET06 0 LATCH-6 SET

47 LSET07 0 LATCH-7 SET

48 LSET08 0 LATCH-8 SET

49 LSET09 0 LATCH-9 SET

50 LSET10 0 LATCH-10 SET

36 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (3/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
51 LSET11 0 LATCH-11 SET

52 LSET12 0 LATCH-12 SET

53 LSET13 0 LATCH-13SET

54 LSET14 TM14*OS16 LATCH-14 SET

55 LSET15 TM15 LATCH-15 SET

56 LSET16 (TM14+TM15)*OS16 LATCH-16 SET

57 LRST01 0 LATCH-1 RESET

58 LRST02 0 LATCH-2 RESET

59 LRST03 0 LATCH-3 RESET

60 LRST04 0 LATCH-4 RESET

61 LRST05 0 LATCH-5 RESET

62 LRST06 0 LATCH-6 RESET

63 LRST07 0 LATCH-7 RESET

64 LRST08 0 LATCH-8 RESET

65 LRST09 0 LATCH-9 RESET

66 LRST10 0 LATCH-10 RESET

67 LRST11 0 LATCH-11 RESET

68 LRST12 0 LATCH-12 RESET

69 LRST13 0 LATCH-13 RESET

70 LRST14 !TM14*OS16 LATCH-14 RESET

71 LRST15 !TM15 LATCH-15 RESET

72 LRST16 !(TM14+TM15)*OS16 LATCH-16 RESET

73 CLSET01 0 USER COUNTER LATCH-1 SET

74 CLSET02 0 USER COUNTER LATCH-2 SET

75 CLSET03 0 USER COUNTER LATCH-3 SET

76 CLSET04 0 USER COUNTER LATCH-4 SET

77 CLSET05 0 USER COUNTER LATCH-5 SET

78 CLSET06 0 USER COUNTER LATCH-6 SET

79 CLSET07 0 USER COUNTER LATCH-7 SET

80 CLSET08 0 USER COUNTER LATCH-8 SET

81 CLRST01 0 USER COUNTER LATCH-1 RESET

82 CLRST02 0 USER COUNTER LATCH-2 RESET

83 CLRST03 0 USER COUNTER LATCH-3 RESET

ENHANCED TECHNOLOGY 37
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (4/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
84 CLRST04 0 USER COUNTER LATCH-4 RESET

85 CLRST05 0 USER COUNTER LATCH-5 RESET

86 CLRST06 0 USER COUNTER LATCH-6 RESET

87 CLRST07 0 USER COUNTER LATCH-7 RESET

88 CLRST08 0 USER COUNTER LATCH-8 RESET

89 IOS01 0 ONE-SHOT-1 INPUT

90 IOS02 0 ONE-SHOT-2 INPUT

91 IOS03 0 ONE-SHOT-3 INPUT

92 IOS04 0 ONE-SHOT-4 INPUT

93 IOS05 0 ONE-SHOT-5 INPUT

94 IOS06 0 ONE-SHOT-6 INPUT

95 IOS07 0 ONE-SHOT-7 INPUT

96 IOS08 0 ONE-SHOT-8 INPUT

97 IOS09 0 ONE-SHOT-9 INPUT

98 IOS10 0 ONE-SHOT-10 INPUT

99 IOS11 0 ONE-SHOT-11 INPUT

100 IOS12 0 ONE-SHOT-12 INPUT

101 IOS13 0 ONE-SHOT-13 INPUT

102 IOS14 0 ONE-SHOT-14 INPUT

103 IOS15 0 ONE-SHOT-15 INPUT

104 IOS16 TM16 ONE-SHOT-16 INPUT

105 ITM01 0 TIMER-1 INPUT

106 ITM02 0 TIMER-2 INPUT

107 ITM03 0 TIMER-3 INPUT

108 ITM04 0 TIMER-4 INPUT

109 ITM05 0 TIMER-5 INPUT

110 ITM06 0 TIMER-6 INPUT

111 ITM07 0 TIMER-7 INPUT

112 ITM08 0 TIMER-8 INPUT

113 ITM09 0 TIMER-9INPUT

114 ITM10 0 TIMER-10 INPUT

115 ITM11 CLST*OPST+!CLST*!OPST TIMER-11 INPUT

116 ITM12 ACFAIL TIMER-12 INPUT

38 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (5/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
117 ITM13 PWDOWN TIMER-13 INPUT

118 ITM14 DC11T TIMER-14 INPUT

119 ITM15 DC21T TIMER-15 INPUT

120 ITM16 BTING TIMER-16 INPUT

121 IPTM01 0 PULSE TIMER-1 INPUT

122 IPTM02 0 PULSE TIMER-2 INPUT

123 IPTM03 0 PULSE TIMER-3 INPUT

124 IPTM04 0 PULSE TIMER-4 INPUT

125 IPTM05 0 PULSE TIMER-5 INPUT

126 IPTM06 0 PULSE TIMER-6 INPUT

127 IPTM07 0 PULSE TIMER-7 INPUT

128 IPTM08 0 PULSE TIMER-8 INPUT

129 IPTM09 0 PULSE TIMER-9 INPUT

130 IPTM10 0 PULSE TIMER-10 INPUT

131 IPTM11 0 PULSE TIMER-11 INPUT

132 IPTM12 0 PULSE TIMER-12 INPUT

133 IPTM13 0 PULSE TIMER-13 INPUT

134 IPTM14 0 PULSE TIMER-14 INPUT

135 IPTM15 0 PULSE TIMER-15 INPUT

136 IPTM16 0 PULSE TIMER-16 INPUT

137 LED25 (LED31+Y27P1T+Y27P2T)*!FIRCMD PANEL LED 25

138 LED26 (LED30+Y59P1T+Y59P2T)*!FIRCMD PANEL LED 26

139 LED27 Y25PT PANEL LED 27

140 LED28 (LED28+Y81UT+Y81OT)*!FIRCMD PANEL LED 28

141 LED29 Y47AT PANEL LED 29

142 LED30 Y47BT PANEL LED30

143 LED31 Y47CT PANEL LED 31

144 LED33 MLOCK PANEL LED 33

145 LED34 GASLOW+GASHIGH PANEL LED 34

146 LED35 DSPLINK PANEL LED 35

147 LED36 CPULINK PANEL LED 36

148 DROPEN IN204 DOOR OPEN STATUS

149 ACFAIL !IN208 AC POWER FAIL

ENHANCED TECHNOLOGY 39
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (6/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
150 BATBAD LT14 BATTERY BAD

151 CHGBAD LT15 CHARGE BOARD BAD

152 GASLOW DC31T GAS LOW STATUS

153 GASHIGH DC32T GAS HIGH STATUS

154 PWDOWN DC12T*ACFAIL POWER DOWN SIGNAL

155 NOBATT DC12T BATTERY NO EXIST

156 DACFAIL TM12 AC POWER FAIL(DNP)

157 BTCGBAD LT16 BATTERY & CHARGE BAD

158 DIGALM (DIGALM+LB13+LB14)*!FIRCMD DIAGNOSTIC ALARM

159 DIGERR (DIGERR+LB15)*!FIRCMD DIAGNOSTIC ERROR

160 CLST IN202 CLOSE STATUS

161 OPST IN201 OPEN STATUS

162 E52A CLST*!OPST CLOSE/OPEN STATUS

163 MLOCK !IN203 MECHENISM LOCK


Applicable for lower than Ver 3.8 of ETR300-R :
ECTRLK+MLOCK+Y25PT
164 CLBLK CLOSE BLOCK STATUS
Applicable for Ver 3.8 or higher of ETR300-R :
MLOCK+Y25PT
Applicable for lower than Ver 3.8 of ETR300-R :
165 OPBLK ECTRLK+MLOCK OPEN BLOCK STATUS
Applicable for Ver 3.8 or higher of ETR300-R : 0
166 STTB TM11 TROUBLE STATUS

167 MDRCMD DO15C*ERMT MAX DEMAND RESET COMMAND

168 PCRCMD DO16C*ERMT PEAK CURRENT RESET COMMAND

169 FIRCMD (KFIRST+DO2C*ERMT)*!ECTRLK*!Y79CY FI RESET COMMAND

170 BTCMD KBACHK+DO0C BATTERY TEST COMMAND

171 TTCMD KTRTEST*!TTING TRIP TEST COMMAND

172 PQRCMD DO7C*ERMT PQM RESET COMMAND

173 WCAPCMD DO1C*ERMT WAVE CAPTURE COMMAND

174 FWCCMD DO3C*ERMT FAULT WAVE CLEAR COMMAND

175 PQCCCMD DO8C*ERMT PQM COUNT CLEAR COMMAND

176 PQITCCMD DO9C*ERMT PQM INTERRUPTION TIME CLEAR COMMAND

177 PQWCCMD DO10C*ERMT PQM WAVE CLEAR COMMAND

40 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (7/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
Applicable for lower than Ver 3.8 of ETR300-R :
(KCLOSE+DO21C*ERMT)*!CLBLK
178 CLCMD CLOSE COMMAND
Applicable for Ver 3.8 or higher of ETR300-R :
(KCLOSE+DO21C*ERMT)*!CLBLK*!ECTRLK
Applicable for lower than Ver 3.8 of ETR300-R :
(KOPEN+DO21T*ERMT)*!OPBLK
179 OPCMD OPEN COMMAND
Applicable for Ver 3.8 or higher of ETR300-R :
(KOPEN+DO21T*ERMT)*!OPBLK *!ECTRLK
180 LKCMD (KCTRLK+DO22C*ERMT)*!ECTRLK LOCK COMMAND

181 ULKCMD (KCTRLK+DO22T*ERMT)*ECTRLK UNLOCK COMMAND

182 PECMD (KPROT+DO23T*ERMT)*!ECTRLK*DPROT PROTECTION ENABLE COMMAND

183 PDCMD (KPROT+DO23C*ERMT)*!ECTRLK*EPROT PROTECTION DISABLE COMMAND

184 GPECMD (KGPROT+DO24T*ERMT)*!ECTRLK*DGPROT GROUNDPROTECTIONENABLE COMMAND

185 GPDCMD (KGPROT+DO24C*ERMT)*!ECTRLK*EGPROT GROUNDPROTECTIONDISABLE COMMAND

186 SPECMD (KSPROT+DO27T*ERMT)*!ECTRLK*DSPROT SEF PROTECTION ENABLE COMMAND

187 SPDCMD (KSPROT+DO27C*ERMT)*!ECTRLK*ESPROT SEF PROTECTION DISABLE COMMAND

188 RECECMD (KREC+DO26T*ERMT)*!ECTRLK*DREC RECLOSING ENABLE COMMAND

189 RECDCMD (KREC+DO26C*ERMT)*!ECTRLK*EREC RECLOSING DISABLE COMMAND

190 SGCPCMD (KALTSG+DO25C*ERMT)*!ECTRLK*EALTSG*!Y79CY SETTING GROUP CHANGE COMMAND - PRI

191 SGCACMD (KALTSG+DO25T*ERMT)*!ECTRLK*NC3809*!Y79CY SETTING GROUP CHANGE COMMAND -ALT

192 ENGRCMD DO17C*ERMT ENERGY RESET COMMAND

193 PG1ECMD (KPROG1+DO29C*ERMT)*!ECTRLK*DPROG1 PROGRAM 1 ENABLE COMMAND

194 PG1DCMD (KPROG1+DO29T*ERMT)*!ECTRLK*EPROG1 PROGRAM 1 DISABLE COMMAND

195 PG2ECMD (KPROG2+DO30C*ERMT)*!ECTRLK*DPROG2 PROGRAM 2 ENABLE COMMAND

196 PG2DCMD (KPROG2+DO30T*ERMT)*!ECTRLK*EPROG2 PROGRAM 2 DISABLE COMMAND

197 HLTECMD (KHLTAG+DO28C*ERMT)*!ECTRLK*NC3808 HOT-LINE TAG ENABLE COMMAND

198 HLTDCMD (KHLTAG+DO28T*ERMT)*!ECTRLK*HLTAG HOT-LINE TAG DISABLE COMMAND

199 EXTRCMD 0 EXTERNAL TRIP COMMAND

200 BDO0C ACFAIL DO 0 - CLOSE BLOCK

201 BDO0T 1 DO 0 - TRIP BLOCK

202 BDO1C LB16 DO 1 - CLOSE BLOCK

203 BDO1T 1 DO 1 - TRIP BLOCK

204 BDO2C LB16+Y79CY DO 2 - CLOSE BLOCK

205 BDO2T 1 DO2 - TRIP BLOCK

206 BDO3C LB16 DO 3 - CLOSE BLOCK

207 BDO3T 1 DO 3 - TRIP BLOCK

ENHANCED TECHNOLOGY 41
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (8/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
208 BDO4C LB16 DO 4 - CLOSE BLOCK

209 BDO4T 1 DO 4 - TRIP BLOCK

210 BDO5C LB16 DO 5 - CLOSE BLOCK

211 BDO5T 1 DO 5 - TRIP BLOCK

212 BDO6C LB16 DO 6 - CLOSE BLOCK

213 BDO6T 1 DO 6 - TRIP BLOCK

214 BDO7C LB16 DO 7 - CLOSE BLOCK

215 BDO7T 1 DO 7 - TRIP BLOCK

216 BDO8C LB16 DO 8 - CLOSE BLOCK

217 BDO8T 1 DO 8 - TRIP BLOCK

218 BDO9C LB16 DO 9 - CLOSE BLOCK

219 BDO9T 1 DO 9 - TRIP BLOCK

220 BDO10C LB16 DO 10 - CLOSE BLOCK

221 BDO10T 1 DO 10 - TRIP BLOCK

222 BDO11C LB16 DO 11 - CLOSE BLOCK

223 BDO11T 1 DO 11 - TRIP BLOCK

224 BDO12C LB16 DO 12 - CLOSE BLOCK

225 BDO12T 1 DO 12 - TRIP BLOCK

226 BDO13C LB16 DO 13 - CLOSE BLOCK

227 BDO13T 1 DO 13 - TRIP BLOCK

228 BDO14C LB16 DO 14 - CLOSE BLOCK

229 BDO14T 1 DO 14 - TRIP BLOCK

230 BDO15C LB16 DO 15 - CLOSE BLOCK

231 BDO15T 1 DO 15 - TRIP BLOCK

232 BDO16C LB16 DO 16 - CLOSE BLOCK

233 BDO16T 1 DO 16 - TRIP BLOCK

234 BDO17C LB16 DO 17 - CLOSE BLOCK

235 BDO17T 1 DO 17 - TRIP BLOCK

236 BDO18C LB16 DO 18 - CLOSE BLOCK

237 BDO18T 1 DO 18 - TRIP BLOCK

238 BDO19C LB16 DO 19 - CLOSE BLOCK

239 BDO19T 1 DO 19 - TRIP BLOCK

240 BDO20C LB16 DO 20 - CLOSE BLOCK

42 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (9/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
241 BDO20T 1 DO 20 - TRIP BLOCK

242 BDO21C LB16+CLBLK DO 21 - CLOSE BLOCK

243 BDO21T LB16+OPBLK DO 21 - TRIP BLOCK

244 BDO22C !ERMT DO 22 - CLOSE BLOCK

245 BDO22T !ERMT DO 22 - TRIP BLOCK

246 BDO23C LB16 DO 23 - CLOSE BLOCK

247 BDO23T LB16 DO 23 - TRIP BLOCK

248 BDO24C LB16 DO 24 - CLOSE BLOCK

249 BDO24T LB16 DO 24 - TRIP BLOCK

250 BDO25C LB16 DO 25 - CLOSE BLOCK

251 BDO25T LB16 DO 25 - TRIP BLOCK

252 BDO26C LB16 DO 26 - CLOSE BLOCK

253 BDO26T LB16 DO 26 - TRIP BLOCK

254 BDO27C LB16 DO 27 - CLOSE BLOCK

255 BDO27T LB16 DO 27 - TRIP BLOCK

256 BDO28C LB16 DO 28 - CLOSE BLOCK

257 BDO28T LB16 DO 28 - TRIP BLOCK

258 BDO29C LB16 DO 29 - CLOSE BLOCK

259 BDO29T LB16 DO 29 - TRIP BLOCK

260 BDO30C LB16 DO 30 - CLOSE BLOCK

261 BDO30T LB16 DO 30 - TRIP BLOCK

262 BDO31C LB16 DO 31 - CLOSE BLOCK

263 BDO31T LB16 DO 31 - TRIP BLOCK

264 CDO0C BTING DO 0 - CLOSE CHECK

265 CDO0T 0 DO 0 - TRIP CHECK

266 CDO1C 0 DO 1 - CLOSE CHECK

267 CDO1T 0 DO 1 - TRIP CHECK

268 CDO2C 0 DO 2 - CLOSE CHECK

269 CDO2T 0 DO 2 - TRIP CHECK

270 CDO3C 0 DO 3 - CLOSE CHECK

271 CDO3T 0 DO 3 - TRIP CHECK

272 CDO4C 0 DO 4 - CLOSE CHECK

273 CDO4T 0 DO 4 - TRIP CHECK

ENHANCED TECHNOLOGY 43
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (10/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
274 CDO5C 0 DO 5 - CLOSE CHECK

275 CDO5T 0 DO 5 - TRIP CHECK

276 CDO6C 0 DO 6 - CLOSE CHECK

277 CDO6T 0 DO 6 - TRIP CHECK

278 CDO7C 0 DO 7 - CLOSE CHECK

279 CDO7T 0 DO 7 - TRIP CHECK

280 CDO8C 0 DO 8 - CLOSE CHECK

281 CDO8T 0 DO 8 - TRIP CHECK

282 CDO9C 0 DO 9 - CLOSE CHECK

283 CDO9T 0 DO 9 - TRIP CHECK

284 CDO10C 0 DO 10 - CLOSE CHECK

285 CDO10T 0 DO 10 - TRIP CHECK

286 CDO11C 0 DO 11 - CLOSE CHECK

287 CDO11T 0 DO 11 - TRIP CHECK

288 CDO12C 0 DO 12 - CLOSE CHECK

289 CDO12T 0 DO 12 - TRIP CHECK

290 CDO13C 0 DO 13 - CLOSE CHECK

291 CDO13T 0 DO 13 - TRIP CHECK

292 CDO14C 0 DO 14 - CLOSE CHECK

293 CDO14T 0 DO 14 - TRIP CHECK

294 CDO15C 0 DO 15 - CLOSE CHECK

295 CDO15T 0 DO 15 - TRIP CHECK

296 CDO16C 0 DO 16 - CLOSE CHECK

297 CDO16T 0 DO 16 - TRIP CHECK

298 CDO17C 0 DO 17 - CLOSE CHECK

299 CDO17T 0 DO 17 - TRIP CHECK

300 CDO18C 0 DO 18 - CLOSE CHECK

301 CDO18T 0 DO 18 - TRIP CHECK

302 CDO19C 0 DO 19 - CLOSE CHECK

303 CDO19T 0 DO 19 - TRIP CHECK

304 CDO20C 0 DO 20 - CLOSE CHECK

305 CDO20T 0 DO 20 - TRIP CHECK

306 CDO21C E52A DO 21 - CLOSE CHECK

44 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (11/13)


SYSTEM
NO EQUATION DESCRIPTION
LOGIC
307 CDO21T !E52A DO 21 - TRIP CHECK

308 CDO22C ECTRLK DO 22 - CLOSE CHECK

309 CDO22T DCTRLK DO 22 - TRIP CHECK

310 CDO23C DPROT DO 23 - CLOSE CHECK

311 CDO23T EPROT DO 23 - TRIP CHECK

312 CDO24C DGPROT DO 24 - CLOSE CHECK

313 CDO24T EGPROT DO 24 - TRIP CHECK

314 CDO25C !EALTSG DO 25 - CLOSE CHECK

315 CDO25T EALTSG DO 25 - TRIP CHECK

316 CDO26C DREC DO 26 - CLOSE CHECK

317 CDO26T EREC DO 26 - TRIP CHECK

318 CDO27C DSPROT DO 27 - CLOSE CHECK

319 CDO27T ESPROT DO 27 - TRIP CHECK

320 CDO28C HLTAG DO 28 - CLOSE CHECK

321 CDO28T !HLTAG DO 28 - TRIP CHECK

322 CDO29C EPROG1 DO 29 - CLOSE CHECK

323 CDO29T !EPROG1 DO 29 - TRIP CHECK

324 CDO30C EPROG2 DO 30 - CLOSE CHECK

325 CDO30T !EPROG2 DO 30 - TRIP CHECK

326 CDO31C 0 DO 31 - CLOSE CHECK

327 CDO31T 0 DO 31 - TRIP CHECK


Applicable for lower than Ver 3.8 of ETR300-R :
0
328 CLB1 COMMUNICATION LOGIC BIT 1
Applicable for Ver 3.8 or higher of ETR300-R :
PFIA+PFIB+PFIC
Applicable for lower than Ver 3.8 of ETR300-R :
0
329 CLB2 COMMUNICATION LOGIC BIT 2
Applicable for Ver 3.8 or higher of ETR300-R :
PFIG+PFIN
Applicable for lower than Ver 3.8 of ETR300-R :
0
330 CLB3 COMMUNICATION LOGIC BIT 3
Applicable for Ver 3.8 or higher of ETR300-R :
TRF+CF
331 CLB4 0 COMMUNICATION LOGIC BIT 4

332 CLB5 0 COMMUNICATION LOGIC BIT 5

333 CLB6 0 COMMUNICATION LOGIC BIT 6

334 CLB7 0 COMMUNICATION LOGIC BIT 7

ENHANCED TECHNOLOGY 45
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (12/13)


NO SYSTEM LOGIC EQUATION TYPE

335 CLB8 0 COMMUNICATION LOGIC BIT 8

336 CLB9 0 COMMUNICATION LOGIC BIT 9

337 CLB10 0 COMMUNICATION LOGIC BIT 10

338 CLB11 0 COMMUNICATION LOGIC BIT 11

339 CLB12 0 COMMUNICATION LOGIC BIT 12

340 CLB13 0 COMMUNICATION LOGIC BIT 13

341 CLB14 0 COMMUNICATION LOGIC BIT 14

342 CLB15 0 COMMUNICATION LOGIC BIT 15

343 CLB16 0 COMMUNICATION LOGIC BIT 16

344 CLB17 0 COMMUNICATION LOGIC BIT 17

345 CLB18 0 COMMUNICATION LOGIC BIT 18

346 CLB19 0 COMMUNICATION LOGIC BIT 19

347 CLB20 0 COMMUNICATION LOGIC BIT 20

348 CLB21 0 COMMUNICATION LOGIC BIT 21

349 CLB22 0 COMMUNICATION LOGIC BIT 22

350 CLB23 0 COMMUNICATION LOGIC BIT 23

351 CLB24 0 COMMUNICATION LOGIC BIT 24

352 CLB25 0 COMMUNICATION LOGIC BIT 25

353 CLB26 0 COMMUNICATION LOGIC BIT 26

354 CLB27 0 COMMUNICATION LOGIC BIT 27

355 CLB28 0 COMMUNICATION LOGIC BIT 28

356 CLB29 0 COMMUNICATION LOGIC BIT 29

357 CLB30 0 COMMUNICATION LOGIC BIT 30

358 CLB31 0 COMMUNICATION LOGIC BIT 31

359 CLB32 0 COMMUNICATION LOGIC BIT 32

360 ECAPW 0 EXTERNAL WAVEFORM CAPTURE

361 PQCAPW WCAPCMD PQM WAVEFORM CAPTURE

362* IOUT301 0 OUTPUT PORT3-01 INPUT

363* IOUT302 0 OUTPUT PORT3-02 INPUT

364* IOUT303 0 OUTPUT PORT3-03 INPUT

365* IOUT304 0 OUTPUT PORT3-04 INPUT

366* IOUT305 0 OUTPUT PORT3-05 INPUT

367* IOUT306 0 OUTPUT PORT3-06 INPUT

46 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table C-1. Default User PLC Equation (13/13)


NO SYSTEM LOGIC EQUATION TYPE

368* IOUT307 0 OUTPUT PORT3-07 IPUT

369* IOUT308 0 OUTPUT PORT3-08 INPUT

370* BOUT301 0 OUTPUT PORT3-01 BLOCK

371* BOUT302 0 OUTPUT PORT3-02 BLOCK

372* BOUT303 0 OUTPUT PORT3-03 BLOCK

373* BOUT304 0 OUTPUT PORT3-04 BLOCK

374* BOUT305 0 OUTPUT PORT3-05 BLOCK

375* BOUT306 0 OUTPUT PORT3-06 BLOCK

376* BOUT307 0 OUTPUT PORT3-07 BLOCK

377* BOUT308 0 OUTPUT PORT3-08 BLOCK

*. NOTE ) The above setting marked with * shall be Ver. 4.0 or higher of ETR300-R to be indicated.