Sie sind auf Seite 1von 4

N

W E 9

13 8
10
30
19 12 11
7
31
20
6
32 14 15

21 5

4
22 16

17 3

23 29 18
2

24
Road N0 5

1
25

26
Phnom Penh EDC Bus bar
27

28
Loads Distance
Bus bar-1 = 1km 7-8 = 2km 14-15 = 0.75km 21-22 = 2.05km 23-29 =2.3km
1-2 = 1.5km 8-9 = 0.8km 14-16 = 2.3km 21-23 = 2.6km 13-30 = 1.3km
2-3 = 0.7km 8-10 = 1.7km 16-17 = 1.5km 23-24 = 1.2km 30-31 = 2km
3-4 = 2km 10-11 = 1.6km 17-18 = 1.3km 24-25 = 0.65km 31-32 = 1.8km
4-5 = 0.7km 11-12 = 0.9km 19-13 = 0.7km 25-26 = 2km
5-6 = 1.5km 12-19 = 1.55km 19-20 = 1.5km 26-27 = 1.3km
6-7 = 1.2km 12-14 = 2.65km 20-21 = 1.5km 27-28 = 0.5km

Figure 2.5.2: The Map of Loads in Odongk and Ponhea Lueu Districts
Table 4.3.2.2: The loads demand in 2012 and 2017
Number of loads Load in 2012 (kVA) Load in 2017 (kVA)
1 50 70
2 104 145.6
3 65 91
4 55 77
5 96 134.4
6 104 145.6
7 104 145.6
8 88 123.2
9 96 134.4
10 55 77
11 120 168
12 104 145.6
13 104 145.6
14 125 175
15 65 91
16 65 91
17 32.5 45.5
18 25 35
19 96 134.4
20 65 91
21 65 91
22 30 42
23 65 91
24 60 84
25 189 264.6
26 88 123.2
27 96 134.4
28 65 91
29 96 134.4
30 173.25 242.55
31 65 91
32 96 134.4
Total 2706.75 3789.45

Chapter 5
Loads Flow Analysis

5.1. Conductor Calculation

5.1.1 Cable Selection


On the other hand, the additional condition that may be taken in to account to
eliminate any uncertainly in selection of cross-sectional area of conductor is the requirement
of economic density current for the line being constructed.
I Max
FEcono 
J Econo

Where,
I Max Current expressed in ampere flowing on the line conductor under peak load
FEcono Economic cross-sectional area
J Econo Economic current density found by calculation

S Cal 3784.282 99.33


I Cal    99.31 FEcono   124mm 2
3 U n 3  22 0.8

We can selection cable section F=150mm2


5.1.2 Cable Parameter
After we selected the cable section F=150mm2 the parameter are below:
R0  0.196 / Km
X 0  0.3553 / Km

5.2. Transformer Selection


5.2.1 Rate of Power Transformer
We choose power transformer by condition verifies over load
S Tr  1.1  1.4  S Load
S Tr  1.3 * S Load

Table 5.2.1.1: Results of load and selection transformer for year 2017

Power Transformer
No Load in 2017 (kVA) Factor
Calculate Selection
1 70 1.3 91 100
2 145.6 1.3 189.28 200
3 91 1.3 118.3 160
4 77 1.3 100.1 100
5 134.4 1.3 174.72 200
6 145.6 1.3 189.28 200
7 145.6 1.3 189.28 200
8 123.2 1.3 160.16 160
9 134.4 1.3 174.72 160
10 77 1.3 100.1 100
11 168 1.3 218.4 250
12 145.6 1.3 189.28 250
13 145.6 1.3 189.28 250
14 175 1.3 227.5 250
15 91 1.3 118.3 100
16 91 1.3 118.3 100
17 45.5 1.3 59.15 50
18 35 1.3 45.5 50
19 134.4 1.3 174.72 160
20 91 1.3 118.3 100
21 91 1.3 118.3 100
22 42 1.3 54.6 50
23 91 1.3 118.3 100
24 84 1.3 109.2 100
25 264.6 1.3 343.98 350
26 123.2 1.3 160.16 160
27 134.4 1.3 174.72 160
28 91 1.3 118.3 100
29 134.4 1.3 174.72 160
30 242.55 1.3 315.315 350
31 91 1.3 118.3 100
32 134.4 1.3 174.72 160