6 Lighting Contactors-Open Control
Description Page
6 Open Control
C30CN Mechanically and Electrically Held . . . . V5-T6-3
6 CN35 Electrically Held. . . . . . . . . . . . . . . . . . . . V5-T6-16
A202 Magnetically Latched. . . . . . . . . . . . . . . . V5-T6-23
6
6
6
6
6
6
6
6 Product Overview Application Description
6 C30CN Mechanically and Magnetically Latched—A202 Electrically Held CN35
Electrically Held Used in applications where it Use in applications where it is
6 Electrically and Mechanically is critical that the contactor not critical that contacts stay
Held C30CN Lighting will not switch to an off closed with loss of control
6 Contactor by Eaton Electrical
delivers unprecedented
position during control power
failure.
power.
● Control power is applied
6 versatility in application,
simplicity in configuration,
30–200A contactors use an continuously during
electrically energized and de- operation
and performance in
6 operation. With a
energized permanent
magnet, while the 300 and
● 10–400A, 600 volt
revolutionary design, rugged maximum rating
6 construction and expansive
400A contactors use a
mechanical latch to hold
● 12 poles maximum for 20
feature set, the C30CN is the and 30A devices
contacts closed during the
6 right solution for effectively
controlling tungsten
operation (no continuous
control current).
6 (incandescent filament),
ballast (fluorescent and
mercury arc), High Intensity
6 Discharge (HID), and non-
motor AC resistive loads.
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Features
6 See figure below.
6 C30CNM Features
6 Contact position indication—
Enclosed contacts resist
contaminants for greater reliability
when button protrudes,
6 contact is closed Common easily-installed power
poles change from NO to NC
Power poles are (or vise versa) simply by
6 available as single or
double poles, creating
unlatching and rotating 180°
Power poles rated
6
74 different circuit
combinations for a range of tasks:
■ 30A rated contacts
Convenient side
6 access for field
■ 15A motor rated
■ Pilot duty rated
power wiring
6 Contact configuration
Auxiliary
contacts, rated
indicator A600, are
6 Robust pole terminals
suitable for
use on low
level circuits
6 accept up to two
8 AWG wires down to
12V, 5 mA
6
6 Standards and Certifications Instructional Leaflets
● UL listed File E1491, 50765 C30CN Lighting
6 UL Category Code/ Contactor Series
Guide NLDX/NLDX7
6
50766 Coil Kit for C30CN
● cUL Lighting Contactors
● CE
6 ● Designed and built to 50767 Power Pole Kit for
C30CN Lighting
NEMA ICS-2 Standards
6 Contactors
50768 Control Module Kit
6 for C30CN Lighting
Contactors
6
6
6
6
6
6
Digit Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Product Selection
6
Two-Wire Mechanically
6 C30CN_ Two-Wire Mechanically Held Lighting Contactors—
Held Lighting Contactors— Standard Assembled Forms
Standard Assembled Forms
6
Number of Poles NO NC Catalog Number 123
The Standard Assembled
Forms in tables on Pages 2 0 2 C30CNM02A02A0
6
4 0 C30CNM40A02A0
5 0 5 C30CNM05A02A0
6 1 4 C30CNM14A02A0
2 3 C30CNM23A02A0
6 3 2 C30CNM32A02A0
4 1 C30CNM41A02A0
6 5 0 C30CNM50A02A0
6 6 0
1
6
5
C30CNM06A02A0
C30CNM15A02A0
6 2 4 C30CNM24A02A0
3 3 C30CNM33A02A0
6 4 2 C30CNM42A02A0
5 1 C30CNM51A02A0
6 6 0 C30CNM60A02A0
6 7 0 7 C30CNM07A02A0
1 6 C30CNM16A02A0
6 2 5 C30CNM25A02A0
3 4 C30CNM34A02A0
6 4 3 C30CNM43A02A0
6
5 2 C30CNM52A02A0
6 1 C30CNM61A02A0
6 7 0 C30CNM70A02A0
8 0 8 C30CNM08A02A0
6 1 7 C30CNM17A02A0
2 6 C30CNM26A02A0
6 3 5 C30CNM35A02A0
6 4
5
4
3
C30CNM44A02A0
C30CNM53A02A0
6 6 2 C30CNM62A02A0
7 1 C30CNM71A02A0
6 8 0 C30CNM80A02A0
6 Notes
1 To change the base coil voltage, replace the content of Position 9 with the appropriate code suffix from the table
on Page V5-T6-7.
6 2 To change auxiliary contact options, replace the content of Position 10 with the appropriate code suffix from the
6 3 To change the control module voltage, replace the content of Positions 12-13 with the appropriate code suffix from
6
11 0 C30CNM110A02A0
code suffix from the table above.
12 4 8 C30CNM48A02A0 3 To change the control module voltage, replace the content of Positions 12-13 with the
6 5 0 5 C30CNM05A03A0
1 4 C30CNM14A03A0
6 2 3 C30CNM23A03A0
3 2 C30CNM32A03A0
6 4 1 C30CNM41A03A0
6
5 0 C30CNM50A03A0
6 0 6 C30CNM06A03A0
6 1 5 C30CNM15A03A0
2 4 C30CNM24A03A0
6 3 3 C30CNM33A03A0
4 2 C30CNM42A03A0
6 5 1 C30CNM51A03A0
6 7
6
0
0
7
C30CNM60A03A0
C30CNM07A03A0
6 1 6 C30CNM16A03A0
2 5 C30CNM25A03A0
6 3 4 C30CNM34A03A0
4 3 C30CNM43A03A0
6 5 2 C30CNM52A03A0
6 6 1 C30CNM61A03A0
7 0 C30CNM70A03A0
6 8 0 8 C30CNM08A03A0
1 7 C30CNM17A03A0
6 2 6 C30CNM26A03A0
6
3 5 C30CNM35A03A0
4 4 C30CNM44A03A0
6 5 3 C30CNM53A03A0
6 2 C30CNM62A03A0
6 7 1 C30CNM71A03A0
8 0 C30CNM80A03A0
6 Notes
6
1 To change the base coil voltage, replace the content of Position 9 with the appropriate code suffix from the table on Page V5-T6-9.
2 To change auxiliary contact options, replace the content of Position 10 with the appropriate code suffix from the table on Page V5-T6-9.
3 To change the control module voltage, replace the content of Positions 12-13 with the appropriate code suffix from the table on Page V5-T6-9.
6
6
6
6
11 0 C30CNM110A03A0
appropriate code suffix from the table above.
12 4 8 C30CNM48A03A0 4 If coil supply is greater than 277V, use CPT.
6 6 C30CNM66A03A0
6
8 4 C30CNM84A03A0
10 2 C30CNM102A03A0 6
12 0 C30CNM120A03A0
6
6
6
6
6
6
6
6
6
6
Components
6
Electrically Held Base Contactor Mechanically Held Module Kits
6 The C30CNE20_0 Electrically Held Base Contactor contains These kits are for converting electrically held contactors to
a 2NO power pole as standard and will allow the addition of mechanically held units. Kits include control module, latch,
6 power poles to build an electrically held contactor up to 12 poles latch cover and auxiliary contacts plus installation instructions.
maximum. A mechanically held module kit can also be added to Conversion kits are suitable for coil voltages of 277V and below.
6 convert the electrically held contactor into a mechanically held
contactor in the field.
Conversion Kits Mechanically Held Module Kits
6 Electrically Held Base Contactor
Coil Volts Control Volts Catalog Number
Electrically Held
Two-Wire
6 Base Contactor Power Poles Catalog Number 1
24–277 Vac 110–120 Vac C320MH2WA0
2NO C30CNE20_0
6 200–277 Vac
24 Vac
C320MH2WH0
C320MH2WT0
6
200–277 Vac C320MH3WH0
Number of Poles NO NC Catalog Number
24 Vac C320MH3WT0
2 2 0 C30CNE20_0
6 1 1 C30CNE11_0
12–24 Vdc C320MH3WT1
6
2 2 C30CNE22_0
0 4 C30CNE04_0
6 6
8
6
8
0
0
C30CNE60_0
C30CNE80_0
6 4
0
4
8
C30CNE44_0
C30CNE08_0
Replacement Parts 6
Wire Specifications
6 Maximum Horsepower Rating
Number Wire Range Wire
Normal Starting Duty Component of Cables (Solid or Stranded) Temperature
6 Volts Horsepower
Power poles 1 14–8 AWG 75°C Cu
6
Single-Pole, Single-Phase
2 14–8 AWG 1 75°C Cu
110–120V 1 Coil 1 or 2 18–14 AWG 60°/75°C Cu
6 220–240V 2
Control module 1 22–12 AWG 60°/75°C Cu
Three-Pole, Three-Phase Auxiliary contacts 1 or 2 22–12 AWG 60°/75°C Cu
6 200–208V 3
Note
220–240V 5
6
1 8 AWG stranded only.
440–480V 10
6 550–600V 15
6 Inrush
Sealed
248 VA
28 VA
6
Control Module
6 Input Voltage
Steady State Current at
Rated Voltage (mA) Maximum VA
6 12–24 Vdc 42 2
24 Vac 80 5
6 115–120 Vac 83 12
6
200–277 Vac 91 30
6
Surge transient peak 6 kV
Frequency range 40–70 Hz
6
6
6
6
6
6
Fuses
Enclosure Type Enclosure Type Enclosure Type 6
AC Service Fuse Size (Standard Size Enclosure) (Standard Size Enclosure) (Standard Size Enclosure)
Voltage 3 and Class Fuse Vendor Type 1 SCCR Value Type 12 SCCR Value Type 3R SCCR Value 6
600 V 30 A, Class J Eaton (Bussmann) Eaton Box 2 or UL 100 kA Eaton Box 5 or UL 100 kA Eaton Box 5A or UL 100 kA
600 V 30 A, Class RK1 or K Eaton (Bussmann)
Listed equivalent 2
50 kA
Listed equivalent 2
50 kA
Listed equivalent 2
50 kA 6
600 V 30 A, Class H Eaton (Bussmann) 10 kA 10 kA 10 kA
6
Fuses 6
Enclosure Type Enclosure Type Enclosure Type
AC Service Fuse Size (Oversized Enclosure) (Oversized Enclosure) (Oversized Enclosure) 6
Voltage 3 and Class Fuse Vendor Type 1 SCCR Value Type 12 SCCR Value Type 3R SCCR Value
600 V 30 A, Class RK5 or K Eaton (Bussmann) Eaton Box F or UL 100 kA Eaton Box I or UL 100 kA Eaton Box L or UL 100 kA 6
Listed equivalent 2 Listed equivalent 2 Listed equivalent 2
600 V 30 A, Class H Eaton (Bussmann) 10 kA 10 kA 10 kA
600 V 40 A, Class J or RK1 Eaton (Bussmann) 100 kA 100 kA 100 kA 6
Notes
1 Any Eaton UL Listed thermal-magnetic circuit breaker may be used provided the breaker interrupting rating meets or exceeds the SCCR values shown above.
6
6
2 Any UL Listed enclosure may be used that meets or exceeds the size of the specified Eaton enclosure.
3 600 V covers all lower voltage values (200 to 600 Vac). Fuse interrupting rating must meet or exceed SCCR value shown above.
6
6
6
6
6
6
6
6
6
Wiring Diagrams
6
6 C30CNE
6
C30CNE Electrically Held View B
Optional Pilot Devices for Electrically Held Contactor
Line Load * If Used
1
6 OFF
ON
Pushbutton
ON
2 Pushbutton
6 L1
*
Fuse Coil Fuse
*
L2
3 A2 A1
6 Remote
OFF
4 Auxiliary
6 Contact
Remote Auxiliary
5 ON Contact
6 OFF
6
ON and OFF Pushbuttons
6
6 View A
OFF
SS
AUTO
ON
A1 A2
6 Optional Coil Optional L1 L2
Auxiliary Auxiliary * *
Fuse Coil Fuse
Contacts Contacts A2 A1
6
Coil Remote
Voltage Device Auxiliary
Contact
CONTROL OFF
6 Refer to View “B” for Control Connections
OFF/ON or OFF/AUTO Selector Switch
6
6
ON
L1 L2
6 *
Fuse
ON
OFF A2
Coil
A1
Fuse
*
6 Remote
AUTO
Auxiliary
Device Contact
6 OFF
2
Fuse 6
Coil
3
Control
Voltage OFF ON
Coil Fuse
Voltage
* 6
A2 A1
4
OFF/ON or OFF/AUTO Selector Switch 6
Electronic-Module
5
ON
OFF
P1 P2 P3 P4 P5
Fuse
*
6
6
Coil
Control OFF ON AUTO
Voltage
6 Voltage *
Remote Fuse
Device Coil
View A
A2 A1
HAND/OFF/AUTO or ON/OFF/AUTO Selector Switch 6
Electronic-Module
Not Used
P1 P2 P3 P4 P5 View C
Optional Pilot Devices for 3-Wire Control 6
C Remote ”NO“ * If Used
Optional A1 A2 Optional
OFF Auxiliary
Electronic-Module 6
“N/O” Coil “NC” P1 P2 P3 P4 P5 *
OFF
Aux.
Contacts Coil
Aux.
Contact
ON
Fuse
Coil
6
Voltage Control Voltage
L
2-WIRE CONTROL
Refer to View “B” for Control Connections
Voltage OFF ON
Remote ”NC“ Coil Fuse
* 6
Auxiliary A2 A1
ON
Electronic-Module
P1 P2 P3 P4 P5
ON & OFF Pushbuttons 6
Electronic-Module
6
”NO“
L Auxiliary P1 P2 P3 P4 P5 *
Fuse
Optional A1 A2 Optional OFF
“N/O”
Aux.
Coil “NC”
Aux. Control
ON
Coil
Voltage 6
Contacts Coil Contact Voltage *
Fuse
6
O OFF ON ”NC“ Coil
Voltage Auxiliary A2 A1
C
3-WIRE CONTROL
Refer to View “C” for Control Connections OFF/ON Selector Switch with Spring Return to Center
6
Dimensions
6
Approximate Dimensions in Inches (mm) 6
C30CN
6
.35 SIDE VIEW TOP VIEW END VIEW
(9.0)
Power 2 “NO” 2 “NC” 6
Pole Aux P1 P2 P3 P4 P5 Aux
ON ON ON ON ON ON
Contacts
1 “NO”
Contacts
1 “NC” 3.86
6
Aux (98.0)
6
Aux
Contact Contact
Optional
Power 6.50
Pole (165.1) 6
Optional “NC” 7.39
Aux Contacts (187.6) NOTES:
1 Mounting dimensions remain the same
6
6
Optional “NO” for 1 to 12 poles.
Aux Contacts P1 P2 P3 P4 P5 2 Line and Load terminals are interchangeable.
3 Up to 2NO and 2NC auxiliary contacts can be
added onto the base product.
Mounting Holes
4 Same power pole can be configured as
NO type or NC type in pole positions 1 – 4;
6
Accept A1 A2
NO type only in positions 5 – 6.
.35 (9.0)
#10 Screws
.22 (5.5) 3.75 (95.3)
6
3.86 (98.0) 4.18 (106.2) .59 (14.9)
6
6
Contents
6 CN35 Electrically Held
Description Page
6 C30CN Mechanically and Electrically Held. . . . . . . V5-T6-3
CN35 Electrically Held
6 Product Selection . . . . . . . . . . . . . . . . . . . . . . . V5-T6-17
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . V5-T6-18
6 Renewal Parts . . . . . . . . . . . . . . . . . . . . . . . . . . V5-T6-20
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . V5-T6-21
6 A202 Magnetically Latched . . . . . . . . . . . . . . . . . . V5-T6-23
6
6
6
6
6
6 CN35 Electrically Held
6 Product Description Application Description Features Standards and Certifications
Type CN35 Electrically Held ● Ideal applications include ● Designed and tested ● UL File No. E37317,
6 Lighting Contactors from industrial plants, stadiums, specifically for lighting and Guide LR353
Eaton’s Electrical Sector are parks and any new resistive loads ● CSA File No. LR353
6 designed to handle the
switching of tungsten
construction requiring
lighting control
● Easy to install and maintain ● Designed and built to
● Full line of Freedom snap- NEMA ICS-2 Standards
6 (incandescent) or ballast
(fluorescent and mercury arc)
● Ballast lamps equate to
fluorescent, mercury vapor,
on accessories
lamp loads as well as other
● Standard with 1NO
sodium vapor and quartz
6 non-motor (resistive) loads. loads and will operate at a
auxiliary contact (the 10A
two- and three-pole ship
maximum of 600V
6 ● Filament lamps equate to
standard with the auxiliary
in the fourth power pole
incandescent, infrared, position with no increase in Instructional Leaflets
6 sodium iodine and heating width) 19225 CN35AN (2-, 3-,
loads and will operate at a ● Top and side mounted 4-Pole)
6 maximum of 480V auxiliary contacts available 19227 CN35BN (2-, 3-Pole)
● Resistance heating for 10–60A devices; side
6 equates to radiant and
convection heating,
mounted auxiliaries only 24829 CN35BN (4-, 5-Pole)
available on 100A and
24840 CN35BN (6-, 9-,
6
furnace and oven loads greater
12-Pole)
● Straight-through wiring
6 19227 CN35DN (2-, 3-Pole)
19229 CN35GN (2-, 3-Pole)
6 19874 CN35GN (4-, 5-Pole)
6
6
6
6
Accessories
6
Transient Suppressor Kits Auxiliary Contacts
6 10–60A Contactors CN35 Lighting Contactors contacts are of the bifurcated
These kits limit high voltage on 24–120V, 240V or 480V include a 1NO maintaining design with parallel circuit
6 transients produced in the coils respectively. auxiliary contact mounted paths. This redundant path
control circuit when power is on right hand side (on 10A, provides very high reliability.
These devices mount directly
6 removed from the contactor or
starter coil. There are three to the coil terminals of
two- and three-pole devices,
auxiliary contact occupies
Auxiliary contacts can be
snapped on the side (up to
lighting contactors 10–60A.
6 separate suppressors for use 4th power pole position—
no increase in width). The
two circuits—per auxiliary
contact) and on the top
10–60A devices will accept (up to four circuits). Auxiliary
6 C320TS2 Kits for 10–60A additional auxiliary contacts contacts for larger contactors,
on the top and/or sides. 100–400A sizes, will accept
6 Description
Coil
Voltage
Catalog
Number Auxiliary contact blocks
side mounted auxiliaries only
and easily attach to the
are designed for snap-on
6 Transient suppressor 24 –120V
240V
C320TS1
C320TS2
installation—fast, easy
side of the contactor with
two screws.
installation (no tools required
6 480V C320TS3 up to 60A). All auxiliary
6
Auxiliary Contacts—10–60A Contactors
6 Contact Catalog
Description Configuration Code 1 Number
100–300A Contactors
6 This device mounts on top of Limits high voltage transients Side Mounted Side Mounted
any side mounted auxiliary produced in the circuit when 1NO 10 C320KGS1
6 contact on lighting contactors
100–300A. It connects across
power is removed from
the coil. 1NC 01 C320KGS2
6 2NC 02 C320KGS5
6 2NO 20 C320KGT4
2NC 02 C320KGT5
6 3NO 30 C320KGT9
6
2NO-1NC 21 C320KGT10
1NO-2NC 12 C320KGT11
6 3NC 03 C320KGT12
4NO 40 C320KGT13
6 3NO-1NC 31 C320KGT14
2NO-2NC 22 C320KGT15
6 1NO-3NC 13 C320KGT16
6 4NC 04 C320KGT17
Notes
6 1 For reference only—not part of catalog number. See Page V5-T6-19.
2 Cannot be added to contactors or starters mounted in Box 1 (NEMA Type 1).
6
6
6
6
6
L1 R1
6
Auxiliary Contact Ratings (Amperes) L1 T1 R1
AC Volts
6
6
Current 120V 240V 480V 600V
T1
NEMA A600 Front View
Make and interrupting 60.0 30.0 15.0 12.0 Top View 6
Break 6.0 3.0 1.5 1.0
Continuous 10.0 10.0 10.0 10.0
100–400A Contactors
6
NEMA P300
Continuous thermal rating: 5A
6
L1 R1
6
DC Volts Make/Break Amperes L2 L3 R3 R2
Rear
Rear
6 Volts AC
Description 120 240 480 600
6 Make 30.0 15.0 7.5 6.0
Break 3.0 1.5 0.75 0.6
6
6 Renewal Parts
6 Contact Kits
Two-pole 4 4 6-65-7 6-43-5 6-44 6-45
6 Three-pole 4 4 6-65-8 6-43-6 6-44-2 6-45-2
Four-pole 4 4 6-65-15 — — —
6 Five-pole 4 4 6-65-16 — — —
6
208V 60 Hz E 9-2875-5 9-2876-5 9-2703-9 9-2756-5 9-1891-13 9-1891-13
277V 60 Hz H 9-2875-12 9-2876-12 9-2703-7 9-2756-9 9-1891-26 9-1891-26
6 550V 50 Hz
24V 60 Hz–24V 50 Hz
N
T
—
9-2875-36
—
9-2876-36
—
—
9-2756-14
—
9-1891-8
—
9-1891-8
—
6 Notes
1 Add operating voltage suffix to catalog number. A = 120V, B = 240V, E = 208V 3 Terminal connections are quick connects only. Two per side.
6 2 Rated 0.5A pilot duty—not to be used on larger contactors. 4 Replace with complete contactor.
Auxiliary Auxiliary
6
6
Contacts Contacts
D Mtg. Holes for #10-32 Screws D Mtg. Holes for (3) #10-32 Screws
D
Contacts
Mtg. Holes for (4) #10-32 Screws 6
6
Dimensions and Shipping Weights
Ampere Number Wide High Deep Mounting Shipping Weight
6
Rating of Poles A B C D1 E F G Lbs (kg)
Open Type
6
10 2–4 2.00 (50.8) 3.88 (98.6) 3.49 (88.6) 1.50 (38.1) 3.38 (85.9) 4.90 (124.5) 0.54 (13.7) 1.4 (0.6)
6
20–30 2–3 2.00 (50.8) 3.88 (98.6) 3.49 (88.6) 1.50 (38.1) 3.38 (85.9) 4.90 (124.5) 0.54 (13.7) 1.5 (0.7)
20–30 4–6 4.20 (106.7) 4.35 (110.5) 3.52 (89.4) 3.50 (88.9) 3.86 (98.0) 4.90 (124.5) 0.54 (13.7) 2.9 (1.3) 6
20–30 9 10.50 (266.7) 5.75 (146.1) 4.52 (114.8) 4.50 (114.3) 5.00 (127.0) — — 4.4 (2.0)
20–30 12 10.50 (266.7) 5.75 (146.1) 4.52 (114.8) 4.50 (114.3) 5.00 (127.0) — — 5.8 (2.6) 6
60
60
2–3
4
2.56 (65.0)
3.46 (87.9)
5.05 (128.3)
5.05 (128.3)
4.44 (112.8)
4.44 (112.8)
2.00 (50.8)
2.00 (50.8)
4.50 (114.3)
4.50 (114.3)
5.80 (147.3)
5.80 (147.3)
0.54 (13.7)
0.54 (13.7)
3.5 (1.6)
3.5 (1.6)
6
60 5 4.36 (110.7) 5.05 (128.3) 4.44 (112.8) 2.00 (50.8) 4.50 (114.3) 5.80 (147.3) 0.54 (13.7) 3.5 (1.6) 6
100 2–3 3.54 (89.9) 7.17 (182.1) 5.94 (150.9) 3.00 (76.2) 6.63 (168.4) — 0.54 (13.7) 9.0 (4.1)
200 2–3 7.05 (179.1) 9.11 (231.4) 7.25 (184.2) 6.00 (152.4) 8.50 (215.9) — — 20.0 (9.1) 6
300 2–3 7.05 (179.1) 13.12 (333.2) 7.78 (197.6) 6.00 (152.4) 12.50 (317.5) — — 23.0 (10.4)
Note
6
1 Center mounting slot at bottom on 10–30A sizes only.
6
6
6
6
6
6
6
6
D Auxiliary D Auxiliary Contacts
6 Contacts
Mtg. Holes for #10-32 Screws
Mtg. Holes for #10-32 Screws
6 A
U
Top A
U E
Top Side
B
A Side Mtd. Mtd. Mtd.
6
B E U Mtd. X Aux. X Aux. Aux.
X Aux.
6 D Auxiliary Contacts
Mtg. Holes for #10-32 Screws
6
6
B E
6
6 Mtg.
Holes
for (3)
6 D Screws
6 20–30
20–30
4–6
9
4.20 (106.7)
10.50 (266.7)
4.35 (110.5)
5.75 (146.1)
3.52 (89.4)
4.52 (114.8)
3.50 (88.9)
4.50 (114.3)
3.86 (98.0)
5.00 (127.0)
4.90 (124.5)
—
0.54 (13.7)
—
2.9 (1.3)
4.4 (2.0)
6 20–30 12 10.50 (266.7) 5.75 (146.1) 4.52 (114.8) 4.50 (114.3) 5.00 (127.0) — — 5.8 (2.6)
60 2–3 2.56 (65.0) 5.05 (128.3) 4.44 (112.8) 2.00 (50.8) 4.50 (114.3) 5.80 (147.3) 0.54 (13.7) 3.5 (1.6)
6 60 4 3.46 (87.9) 5.05 (128.3) 4.44 (112.8) 2.00 (50.8) 4.50 (114.3) 5.80 (147.3) 0.54 (13.7) 3.5 (1.6)
6
60 5 4.36 (110.7) 5.05 (128.3) 4.44 (112.8) 2.00 (50.8) 4.50 (114.3) 5.80 (147.3) 0.54 (13.7) 3.5 (1.6)
100 2–3 3.54 (89.9) 7.17 (182.1) 5.94 (150.9) 3.00 (76.2) 6.63 (168.4) — 0.54 (13.7) 9.0 (4.1)
6 200 2–3 7.05 (179.1) 9.11 (231.4) 7.25 (184.2) 6.00 (152.4) 8.50 (215.9) — — 20.0 (9.1)
300 2–3 7.05 (179.1) 13.12 (333.2) 7.78 (197.6) 6.00 (152.4) 12.50 (317.5) — — 23.0 (10.4)
6 Note
1 Center mounting slot at bottom on 10–30A sizes only.
6
6
6
6
6
6
A202 Magnetically Latched 6
Product Description Application Description Features Standards and Certifications 6
The A202 Lighting Contactor ● The magnetically latched ● Designed and tested ● UL Listed File No. E44424,
from Eaton’s Electrical lighting contactors are specifically for lighting Guide NRNT 6
Sector provides a safe and designed to withstand the and resistive loads ● CSA Certified File No.
convenient means for local or
remote switching of relatively
large initial inrush currents
of tungsten lamp loads
● Easy to install and maintain LR39402, Class 3231-01 6
● No control power ● Designed and built to
large tungsten, fluorescent or
mercury arc lamp loads. ●
without contact welding
The A202 contactors are
necessary to maintain
contact closure
NEMA ICS-2 Standards 6
fully rated devices that do
not require de-rating similar Operation 6
to standard motor control
contactors
A permanent magnet is built
into the contactor structure 6
● The magnetically latched that will maintain the
lighting contactor provides contactor in its energized Instructional Leaflets 6
effective control in state indefinitely without IL16965 30A (2-, 3-, 4-,
applications such as office
buildings, industrial plants,
using control power. When 5-Poles) 6
energized, a DC current is
IL16966 60A (2-, 3-, 4-,
hospitals, stadiums,
airports, and so on
applied to the latch coil,
producing a magnetic field 5-Poles) 6
that reinforces the polarity
of the permanent magnet,
IL17509 100–200A
6
pulling in the contactor.
The coil clearing interlock 6
disconnects the current to
the coil. In order to drop out
the contactor, it is necessary
6
to apply a field through the
STOP coil in the reverse 6
direction to the permanent
magnet. This momentarily 6
cancels the magnetic
attraction and the contactor 6
drops out.
6
6
6
6
Product Selection
6
When Ordering Specify
6 ● Catalog number with coil suffix code from the Magnet Coil
Selection table
6 ● Any required accessories
6 6 A202K1F_M
220V/50, 240V/60
24V, 60 Hz
W
I4
8 A202K1G_M
6 10 A202K1H_M
6
12 A202K1K_M
Accessories
60 2 A202K2B_M
See A200 NEMA Contactor Accessories, Tab 2, section 2.2 in this
6 3 A202K2C_M volume.
4 A202K2D_M Notes
6 5 A202K2E_M 1 Lighting contactors are not available with DC coils.
2 Contactors rated 300A and 400A are mechanically latched.
6 A202K2F_M
6 8 A202K2G_M
3 Underscore (_) indicates missing code letter for magnet coil selection—see Magnet Coil
Selection table.
4 Available on two- to five-pole, 30 and 60A devices and on two- to three-pole 100 and
6 10
12
A202K2H_M
A202K2K_M
200A devices.
6 100 2 A202K3B_M
3 A202K3C_M
6 4 A202K3D_M
5 A202K3E_M
6 6 A202K3F_M
6 8
10
A202K3G_M
A202K3H_M
6 12 A202K3K_M
200 2 A202K4B_M
6 3 A202K4C_M
6
4 A202K4D_M
5 A202K4E_M
6 6 A202K4F_M
8 A202K4G_M
6 10 A202K4H_M
12 A202K4K_M
6 300 2 A202K5B_M
6
3 A202K5C_M
400 2 A202K6B_M
6 3 A202K6C_M
6
6
6
6
179C755G19 179C755G18 179C755G19 179C755G18
Two-, Three-Pole Four-, Five-Pole 179C755G19 2
Voltage Hz Part Number Part Number
110/120 50/60 7874A93G01 7874A87G01
200A Model K Electrically Held
6
179C755G28 179C755G27 179C755G28 1 179C755G27
208/240 50/60 7874A93G02 7874A87G02
179C755G28 2 6
277 50/60 7874A93G03 7874A87G03 200A Model J Magnetically Latched
440/480 50/60 7874A93G04 7874A87G04 179C755G31 179C755G30 179C755G31 1 179C755G30 6
575 50/60 7874A93G05 7874A87G05
6
179C755G31 2
6
6
6
6
6
6
6
6
6
6
6 Description Specification
Terminals
6
Tungsten lamp loads, maximum volts
Line-to-line 480 Vac
6
Wiring Diagrams
6
Standard Wiring
6 The standard wiring of an A202 contactor can be controlled
by a separate customer supplied single-pole double-throw
controlling station.
6
6
Control Line Line
L2
6 (+)
6 ON OFF
6
(+)
6
Black Auxiliary
Contact
Typical Close 3 Red AC Red (Option)
6
Control
Station White AC
Close (–)
6
Open 2 Red
Open
6
Load
6 Two-Wire Control
Two-wire control can be accomplished with a customer supplied
relay with 1NO/1NC auxiliary contacts, wire as shown.
6
6
Line Line
or
Neutral L2
6 (+)
6 ON OFF
6 Switch
Line
(+)
Black Auxiliary
6 CM
3 Red AC Red
Contact
(Option)
6 CM White AC
Control CM
2 (–) Red
6 CM
Load
6
6