Max. time of The maximum time allowed to travel - Check motor drive
- Check the function of floor counters
fast travel at high speed without changing the - Increase the parameter Maximum time
expired current floor number is exceeded. of travel in high speed
Top and bottom Bottom limit switch (817) and top -Check limit switches SKSR1 and
SKSR2 mechanically or electrically.
limits sensed at limit switch (818) are interrupted -Check limit switch inputs 817 and 818
the same time simultaneously on ARL-500 and REVKON.
The manual door can not be closed in -Manual door remains open
the time set by manual door close - Check shaft doors mechanically
Manual door
waiting time parameter. Timer is - Check door contacts.
open error - Check the connection of terminal
started counting after a call is
accepted. 130 on ARL-500
"
! !
Maintenance date has been expired set Maintenance date has been expired
Maintenance
by “Date and Time Settings > Next set by “Date and Time Settings >
date passed Next maintenance date” parameter.
maintenance date” parameter.
#
! !
$
%