Digital thermostat PCV2-2

Introduction

Picture

Introduction In this Packo Flash we introduce the temperature controller PCV2-2, the new
execution of the PCV2 controller.

Contents PCV2-2 versus PCV2..................................................................................................2


Technical data ..............................................................................................................3
The control panel .........................................................................................................4
Circuit diagram ............................................................................................................5
Parameters and how to set them...................................................................................6
Configuration and how to adjust settings.....................................................................7
Error messages .............................................................................................................9
FLASH
Nr. : 126
Datum / Date: 08/02/1999
Pag./page: 2/9

PCV2-2 versus PCV2

Functions The PCV2-2 has the same functions as the PCV2 controller:
• digital thermometer
• temperature controller;
• interval agitation..

Building in The PCV2-2 is built in in the same way as the PCV2.

Replacing PCV2 Mind following connections:


with PCV2-2
Step Action
1 Connect the wire, connected to terminal L1 on PCV2, to terminal P on
PCV2-2.
2 Connect the wire, connected to terminal P on PCV2, to terminal L1 on
PCV2-2.

The sensor
The sensor of the PCV2-2 is NOT the same as for the PCV2. When a PCV2-
2 is ordered, the correct sensor is delivered. The PCV2-2 sensor can also be
ordered separately.
Remark: the PCV2-2 cable carries a label with the mention S10-6P.

Part Order number


PCV2-2: 111391
Sensor for PCV2-2, cable length 7 metre 115615
FLASH
Nr. : 126
Datum / Date: 08/02/1999
Pag./page: 3/9

Technical data

Overview Below you will find an overview of the technical date of the PCV2-2:

Description Value
Tension 230 V AC, 50/60 Hz
Relay contact 2
Maximum current 16A AC1 / 250V ~
Display 13 mm LED, 3 positions
Type of controller two point controller
Measurement range -30°C/ +70°C
Length of the sensor cable 2 metre
Cut away for front panel 90 x 42 mm
Degree of protection (front panel IP64
housing)
Connection clamping screw
Working temperature 0°C/+ 50°C
Maximum humidity 75% (no vapour)
FLASH
Nr. : 126
Datum / Date: 08/02/1999
Pag./page: 4/9

The control panel

Photo Below you will find a picture of the control panel:

1
6
2
3 7
4

5 8

Parts Below you will find an overview of the parts of the control panel:
Nr Part Function
1 LED Is lit when the agitator is running.
2 LED Is lit when the cooling unit (DX) or the ice water pump (IB)
is running.
3 LED Is lit when temperature setpoint T1 is selected.
4 LED Is lit when temperature setpoint T2 is selected.
5 Button Modification of the temperature setpoints T1/T2, in

combination with and .


6 Button Manual agitation:
• short stirring: press the buttons until the display shows
"sho" (±1 second);
• long stirring: press the buttons until the display shows
"lon" (±3 seconds);
When this button is pressed in combination with the SET
button, the selected temperature setpoint is raised.
7 Display Shows the temperature in the tank.
8 Button Selection of the temperature setpoint T1 or T2 (press for ±
3 seconds).
When this button is pressed in combination with the SET
button, the selected temperature setpoint is lowered.
FLASH
Nr. : 126
Datum / Date: 08/02/1999
Pag./page: 5/9

Circuit diagram

Drawing Below you will find the circuit diagram

Parts
Below you will find an overview of the parts of the circuit diagram:
Part Function
RW Agitator
Vo Sensor
O1 Option 1: external switch for the selection of the
temperature setpoint T1/T2.
O2 Option 2: external button for manual agitation.
S Tension
K Cooling
FLASH
Nr. : 126
Datum / Date: 08/02/1999
Pag./page: 6/9

Parameters and how to set them

Overview

Parameter Function Factory


settings
C1 Temperature setpoint T1 (2°C -10°C) 3,2°C
C2 Temperature setpoint T2 (2°C-20°C) 5°C
C10 Differential T1 (0,1°C-10,0°C) 0,8°C
C11 Differential T2 (0,1°C-10,0°C) 0,8°C
C20 Duration of stirring after a cooling cycle (0-999 sec.) 120 sec.
C21 Rest period during interval agitation (0-999 min.) 13 min.
C50 Short manual agitation (0-999 min.) 2 min.
C51 Long manual agitation (0,999 min.) 30 min.
C91 Display calibration (-10°C tot +10°C) -
C99 Locking the buttons for the modification of temperature setpoints T1/T2: 0
0 = NOT locked: the temperature setpoints pressing the SET-buttons +

or .
1 = locked: the temperature setpoints can only be modified by setting
parameters C1 & C2.

How to set Proceed as follows

Step Action
1
Press and simultaneously for ± 3 seconds. The display shows C1.
2 Press the SET button to see the set value on the display.
3
Press the SET button and (to raise the value) or (to lower the value)
simultaneously...
4
Press to proceed with the next parameter.
5 Repeat steps 2 to 4 until all parameters are set.
6
• Press and simultaneously for 5 seconds or
• wait for 60 sec.
to return to the temperature display.
FLASH
Nr. : 126
Datum / Date: 08/02/1999
Pag./page: 7/9

Configuration and how to adjust settings

Parameters Below you will find an overview of the configuration parameters:


Parameter Function Factory settings
P5 Switching off the cooling in case of a breakdown: 0
0 = cooling is switched off
1 = cooling continues
P6 Switching off the agitator in case of a breakdown: 0
0 = agitator is switched off
1 = agitator continues
P10 Differential T1: 1 0 1
0 = symmetrical
1 = unilateral upwards
P11 Differential T2: 1
0 = symmetrical
1 = unilateral upwards

indicative range
P20 Minimum value temperature setpoint T1 0 - 3,1 2,0
P21 Maximum value temperature setpoint T1 3,3 - 50,0 10
P22 Minimum value temperature setpoint T2 0 - 3,1 2,0
P23 Maximum value temperature setpoint T2 3,3 - 50 20
P30 Minimum value differential T1 0,1 - 0,6 0,5
P31 Maximum value differential T1 0,8 - 100 1,5
P32 Minimum value differential T2 0,1 - 0,6 0,5
P33 Maximum value differential T2 0,8 - 100 1,5
P70 Minimum duration of cooling 0 - 999 60 sec.
P71 Minimum rest period between 2 cooling 0 - 999 180 sec.
cycles
P80 Selection T1/T2: 2
0 = not possible

1 = possible with button


2 = possible with external switch
P81 Manual agitation 2
0 = not possible

1 = possible with button


2 = possible with external button

3 = ON/OFF with or external button


FLASH
Nr. : 126
Datum / Date: 08/02/1999
Pag./page: 8/9

P99 Temperature unit 0


1 = °F
0 = °C

How to set Proceed as follows:


Step Action
1
Press and simultaneously for ± 3 seconds. The display
shows C1.
2
Press as many times as necessary until the display shows C99.
3
Press for ± 8 seconds until the display shows Pb.
4
Keep pressed and press simultaneously for ± 3 seconds
until the display shows P5.
5 Press the SET button to see the set value on the display.
6
Press the SET button and (to raise the value) or (to lower
the value) simultaneously...
7
Press to proceed with the next parameter.
8 Repeat steps 2 to 4 until all parameters are set.
9
• Press and simultaneously for 5 seconds or
• wait for 60 sec.
to return to the temperature display.
FLASH
Nr. : 126
Datum / Date: 08/02/1999
Pag./page: 9/9

Error messages

Overview Below you will find an overview of the possible error messages:

Error message Description


F1 Short circuit of the sensor.
F2 The sensor or the sensor cable is faulty and has to be
repaired or replaced.
F3 The thermostat is faulty. Disassemble and have it repaired.
FFF The measurement range (-50°C - +150°C) has been
exceeded.