ETAP Page: 1
12.6.0H
Location: Date: 07-02-2018
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: COCBA Config.: Normal
Short-Circuit Analysis
ANSI Standard
3-Phase, LG, LL, & LLG Fault Currents
1/2 Cycle Network
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
2 Buses Total
Grounding
Branch Connections
Gen1 Turbo 151.000 10.500 1800 20.00 1.000 20.00 0.0 28.00 Wye Solid 20.00 0.500 10.00
Imp.
Lumped Load Rating % Load Loading X/R Ratio (Machine Base) Grounding
ID kVA kV MTR STAT kW kvar X"/R X'/R %R % X" % X' Conn. Type Amp.
Lump2 153750.0 512.500 80 20 110700.0 53614.5 10.00 10.00 1.692 16.92 34.62 Delta
Bus4 Total 0.00 1.349 0.00 102.27 99.22 1.332 1.332 6.36E-001 8.34E+000 1.86E-001 7.80E+000
Bus3 Bus4 37.05 0.535 69.32 70.64 105.40 0.768 1.332 * 8.48E-001 2.10E+001 1.86E-001 7.80E+000
Lump2 Bus4 99.90 0.814 99.90 99.90 99.90 0.564 0.000 1.38E+000 1.38E+001
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 9
12.6.0H
Location: Date: 07-02-2018
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: COCBA Config.: Normal
Bus4 512.00 0.103 -1.345 1.349 0.080 -1.330 1.332 1.107 0.085 1.110 1.097 0.813 1.365
All fault currents are symmetrical momentary (1/2 Cycle network) values in rms kA
* LLG fault current is the larger of the two faulted line currents
Project:
ETAP Page: 10
12.6.0H
Location: Date: 07-02-2018
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: COCBA Config.: Normal
Bus Positive Sequence Imp. (ohm) Negative Sequence Imp. (ohm) Zero Sequence Imp. (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance
Bus4 512.000 16.66424 218.54560 219.18000 18.54419 241.46390 242.17500 4.87005 204.54220 204.60020