Design Dimensions:
Approximate weights and dimensions: Dimensions are in
inches, weights are in pounds. Dimensions may change
to meet the customer spec.
Top View
B
76" 3" MIN.
MAXIMUM PAD
DIMENSIONS
70"
42"
15.5"
MINIMUM CABLE OPENING
5"
Side View
C
D
Front View
18"
E
ABB 5
X62051-Brochure 8/15/03 10:05 AM Page 6
6 ABB
X62051-Brochure 8/15/03 10:05 AM Page 7
ABB 7
X62051-Brochure 8/15/03 10:05 AM Page 8
Design Dimensions:
Physical data is approximate and is based on single voltage units with or without taps, with standard 19.25" cable
compartment depth. Dimensions are in inches. Weights are in pounds. Dimensions may change to meet specific
customer requirements.
C + 6"
5.0"
6.5"
* Maximum pad dimensions
50.0"
B D
8 ABB
X62051-Brochure 8/15/03 10:05 AM Page 9
Distribution
Transformer Testing
The ABB commitment to manufacture quality distribu- Applied Voltage Test of LV
tion transformers is backed by a series of transformer This dielectric test is similar to the Applied Voltage test
tests used to verify conformance to performance of the high voltage circuitry except that the integrity of
characteristics outlined in the latest revisions of ANSI insulation structures between the low voltage and the
C57.12.00 and ANSI C57.12.90. These identified tests are high voltage, and between the low voltage and ground is
also part of the Quality System which is audited semi- checked. A pass-fail decision is made by monitoring the
annually by DET NOSKE VERITAS (DNV) to ISO Standards. test current intensity. If the resulting current is larger
Testing Program than specified normal leakage and capacitive current,
the unit is rejected.
Factory tests are performed on a transformer to confirm
that it is properly designed and constructed to carry Induced Voltage Test
rated load and that it will withstand the conditions it will The principal purpose of this test is to verify the dielectric
be exposed to in service. strength of turn to turn, layer to layer, phase to phase,
and other insulation structures within the transformer
Each transformer manufactured by ABB must undergo a
windings by inducing an overvoltage condition (at higher
series of tests.
than normal frequency to avoid saturation of the core).
1. Polarity, Phase-Relation, and Ratio The test current is monitored, and if it exceeds limits
2. Demag Test specified for each transformer, the unit is rejected.
3. Applied Voltage Test of the HV
4. Applied Voltage Test of the LV No-Load Loss and Excitation Current
5. Induced Voltage Test This test measures the no-load (excitation) loss and the
6. No-Load (Excitation) Loss and Excitation Current transformer exciting current with rated voltage applied.
If the exciting current and/or the no-load loss exceed the
7. Impedance Voltage and Load Loss
limits specified, the transformer is rejected.
8. Full Wave Impulse
9. Continuity Check Impedance Voltage and Load Loss
This test measures the load loss and the impedance volt-
Test Facilities
age at rated current. The load loss and the impedance
The multi-station, automated test facilities are operated voltage must be within specified limits.
by process control computers. Required interaction with
test floor personnel is minimal with the computers initi- Full Wave Impulse
ating and monitoring each test, and then analyzing the The impulse test is one of several tests designed to verify
test results feedback. The computers are programmed to the dielectric strength of the many insulation structures
conduct tests according to ANSI standards, and accord- within the distribution transformer against line voltage
ing to the ratings of each transformer style, the test floor surges. It is performed to comply with ANSI standards
computers will initiate appropriate test setups, compare and for quality assurance. The change in the ANSI stan-
results with established ANSI standard limits, and deter- dard in 1993 required all manufacturers to install fault
mine acceptance for each tested unit. detection sensitive enough to detect a single turn short.
The test results for each unit are recorded and stored on Continuity Check
computer files for access and analysis. This test is performed on all transformers to verify trans-
Polarity, Phase-Relation, and Ratio Tests former circuit and component integrity. This test is per-
formed with an ohmmeter to verify that the internal
These tests verify proper phase-relation (three phase), wiring is correct.
ratio, and polarity (single phase) of the transformer under
test. To pass, a unit must demonstrate the proper polarity The transformer’s nameplate is compared to manufactur-
or phase-relation and have a turns ratio within one-half of ing information for style, serial number, kVA, HV rating,
one percent of the nominal voltage ratio. LV rating, tap voltages, impedance, conductor materials
and coil BIL rating. The bushings, electrical accessories,
Demag Test
and fuses are verified.
Some transformers require the Demag Test to remove
any residual magnetism in preparation for an impulse Special Tests
test. It also serves as a no-load exciting current test. A Some tests are performed at the option of the customer.
transformer passes this test if the exciting current does Sound Testing
not exceed the limit specified for the design of the trans-
former. ANSI standards define the required sound levels for
transformer but some customers specify reduced sound
Applied Voltage Test of the HV levels. The sound generated by a transformer is affected
This test checks the dielectric integrity of insulation by the core geometry, flux density, tank design, and the
structures between the high voltage and low voltage, and quality of assembly of all the transformer components
between the high voltage and ground. A pass/fail deci- into a completed unit. Sound tests are made with the
sion is made by monitoring the test current intensity. If unit powered at 100% and 110% of rated voltage under
the resulting current is larger than specified normal leak- no-load conditions.
age and capacitive currents, the unit is rejected. This test
is omitted for transformers with a permanently grounded
high voltage winding.
ABB 9
X62051-Brochure 8/15/03 10:05 AM Page 10