Name of Project: ISTL Job ref./ Enquiry No.

:
Address: NAGPUR Estimated by: BK Heat load for: Summer
Space used for: CAFETERIA Peak load at: 4.00 PM
Area in sq.ft = 21546 Length in Ft. Height in ft.= 12.0 DESIGN CONDITIONS
Volume in cu.ft 258552 Width in Ft. Contact factor : 0.90 (British Units) DBT % RH WBT Gr/lb
Bypass factor : 0.10 Btu/hour Outside 112 18 76 80
Area x Temp.difFactor = Sensible Load Latent Load Inside 75 55 62 65
SOLAR GAIN-GLASS SOLAR GAIN Difference 37 xxxx xxxx 15
Glass (N) 2832 23 0.5 32568 - Eq. Temp.correction factor 17
Glass (E) 0 12 0.5 0 - OUTDOOR AIR (CFM)
Glass (S) 0 12 0.5 0 - 1450 People x 7.5 CFM/Person = 10875
Glass (W) 0 163 0.5 0 - No. of air changes/hr = 10
Glass (NE) 0 12 0.5 0 - Selected Outdoor Air CFM = 10875
Glass (SW) 0 85 0.5 0 -
Glass (NW) 0 138 0.5 0 - APPARATUS DEW POINT
Glass (SE) 0 12 0.5 0 -
SOLAR & TRANSMISSION GAIN-WALLS & ROOF Effective Sens. Heat Factor (ESHF) = ERSH/ERTH = 0.60
Wall (N) 0 21 0.215 0 -
Wall (E) 1152 31 0.215 7678 - INDICATED ADP = 39 SELECT.ADP= 39
Wall (S) 2263 43 0.215 20921 -
Wall (W) 1152 57 0.215 14118 - DEHUMIDIFIED AIR QUANTITY
Wall (NE) 0 27 0.215 0 -
Wall (SW) 0 31 0.215 0 - Dehum. Rise = Contact Factor x (Rm Temp. - ADP)= 32.4
Wall (NW) 0 23 0.215 0 - Dehum. CFM = ERSH/1.08/Dehum. Rise = 18053
Wall (SE) 0 35 0.215 0 - Dehum CFM /400 = 45.13
Exposed Roof 0 52 0.48 0 - U-factors: Roof Insl 0.12
TRANSMISSION GAIN-EXCEPT WALLS & ROOF Exposed Walls 0.215 Roof Non Insl 0.48
All Glass 0 37 1.13 0 - Partition Walls 1.00 Ceiling 0.48
Partition Wall 0 32 1.00 0 Partition Glass 1.00 Floor 0.48
Partition Glass 0 32 1.00 0 - Factors for Glass: Solar gain 0.5
Ceiling 0 32 0.48 0 - Transm. Gain 1.13
Floor 0 32 0.48 0 - Some typical inside design conditions:
INTERNAL HEAT DBT % RH WBT Gr/lb
People 1450 280 270 406000 391500 0 0 0 0
Lights (I) - W 21546 1 1.5 32319 - 0 0 0 0
Lights (F) - W 0 3.41 1.25 0 - 0 0 0 0
DESIGN CONDITIONS
Equip.Load -W Vending Machine 1 3275.0 3275 - 0 0 0 0
-do- in HP 0 2545 1.0 0 - 0 0 0 0
Others Water Cooler 5 1200.0 6000 0 0 0 0 0
Subtotals 522879 391500 0 0 0 0
Safety Factors (12.5% & 5% respectively) 65360 19575 0 0 0 0
Room Sensible & Latent Loads 588239 411075 0 0 0 0
0 0 0 0
Outdoor Air cfm = 10875 43457 11093 0 0 0 0
Effective Room Sensible Heat (ERSH) 631696 - 0 0 0 0
Effective Room Latent Heat (ERLH) - 422168 0 0 0 0
Effective Room Total Heat (ERTH) 1053863 0 0 0 0
OUTDOOR AIR (O.A.)
Sensible Load 391109 - Air on Coil in deg F: Check figures:
Latent Load - 99833 DBT : 97 sq.ft/TR = #VALUE!
Effective Room Total Heat + O.A Heat WBT : 70 cfm/sq.ft = 0.8
Other Heat Gains @ 5% #VALUE! cfm/TR = #VALUE!
GRAND TOTAL HEAT #VALUE! TMBH = ###
TR #VALUE! SMBH = 1022.8 Sheet No.
SUMMARY OF HEATLOAD FOR INDIRA GAHDI INSTITUTE.
DATE : 09.04.2014 AREA / TR
Area in sq.ft = 935 TR 12.13
Height in ft.= 22.00 Dehum CFM 4753.48
SEMINAR HALL No 1 12.13 77.10
People 90 Dehum CFM /400 = 11.88
Equip.Load -W 750
Area in sq.ft = 935 TR 12.13
TOTAL People 90 Dehum CFM 4753.48 12.13 77.10
Equip.Load -W 750 Dehum CFM /400 = 11.88