1. DESIGN IS FOR PLANNING PURPOSES ONLY.

2. GIS SWITCHGEAR BASED ON TYPICAL SIZING


REQUIREMENTS FOR ABB ELK-04, 145KV GIS
SYSTEM NOMINAL SIZE OF 0.8M X 4.8M PER BAY.
3. ALL PROTECTION EQUIPMENT IS BASED ON
TYPICAL CUBICLE SIZES OR SIZES WHICH HAVE
43.3m BEEN INDICATED BY EIRGRID.
4. SUFFICIENT SPACE IS PROVIDED AT ALL SIDES OF
THE GIS FOR MAINTENANCE TROLLIES PERSONAL
SCREENED VENT SCREENED VENT AND CABINET DOOR OPENINGS.
AS PER IEC 62485-2 AS PER IEC 62485-2 5. MEZZANINE FLOOR SHOWN BELOW THE CONTROL
ROOM FOR AC CABLING.
6. LVAC AND DC DISTRIBUTION BOARDS ARE GIVEN
FOR NOMINAL SIZING.
10m 22.7m 7. ALL PROTECTION CUBICLES HAVE FRONT AND
EMERGENCY EXIT REAR ACCESS OF A MINIMUM 1.2M.
8. DRAFT FOR CLIENT COMMENT AND IT IS NOT TO

3.2m
BE USED FOR CONSTRUCTION.
9. SCREENED VENTS (2 HIGH LEVEL AND 2 LOW
6.4m

LEVEL) ARE TO BE INSTALLED IN THE BATTERY


RELAY ROOM ROOM AS PER IEC 62485-2.
BATTERY ROOM
F.F.L. 72.90m 10. THERE ARE TO BE NO OBSTRUCTIONS LOCATED
2m DIRECTLY IN FRONT OF THE CABLE DUCTS AND
300mm TO THE SIDE OF THE CABLE DUCT WHERE
THE DUCT ENTRIES THE CABLE ROOM.

12.2m
4m
11. CLEAR AREA ON BOTH SIDES OF THE GIS FOR THE
4m HV TEST EQUIPMENT.
12. THIS DRAWING IS BASED ON EirGRID DRAWING
HOIST AREA XDN-LAY-ELV-STND-F-003 Sht4 Rev 0
FOR LOADING
EQUIPMENT TO

7.4m
FIRST FLOOR

4.8m 32.0m 5.6m


4.6m

CABLE ROOM
1.5m

1.5m
12.2m

PLAN - GROUND FLOOR 10.4m


SCALE 1:100
SELECTED INSULATED

1.2m
ARCHITECTURAL ROOF
1 2 3 4 5 6 7 8 9 10 11 CLADDING
PARAPET WALL
43.3m TO APPROVED COLOUR, LIGHT
GREY OR SIMILAR APPROVED
5.9m 4.6m 4.0m 4.0m 4.0m 4.0m 4.0m 4.0m 4.0m 4.0m
STRUCTURAL FRAME TO
ENGINEERS SPECIFICATION

SELECTED INSULATED
A ARCHITECTURAL WALL
CLADDING
TO APPROVED COLOUR, LIGHT
GREY OR SIMILAR APPROVED
0 2.5 5

14.50m
GIS ROOM REINFORCED CONCRETE
m
FLOOR SLAB TO ENGINEERS
SPECIFICATION
6.3m

F.F.L. 77.50m

12.2m
4m
4m
A Dec. '15 PLANNING ISSUE MN DC
HOIST OPE 4.0m 6.0m RAISED ACCESS FLOORING
110 KV GIS HALL FOR LOADING EXTERNAL FIRE
3.6m EQUIPMENT TO Rev Date Description By Chkd.
F.F.L. 77.50m ESCAPE

3.5m
FIRST FLOOR
RELAY ROOM

CABLE ROOM

F.F.L. 72.90m Client:


G.L.72.75m

1m
EMERGENCY EXIT
B

REINFORCED CONCRETE
Project:
FLOOR SLAB AND
PLAN - FIRST FLOOR SECTION A-A FOUNDATIONS TO ENGINEERS
SCALE 1:100 SCALE 1:100 SPECIFICATION
FIRE ESCAPE
WEST DUBLIN
220 / 110 kV SUBSTATION
43.3m
& ASSOCIATED WORKS

Title:

110kV GIS BUILDING


FLOOR PLANS & SECTION

FALL FALL Scale @ A1: 1:100


Prepared by: Checked: Date:
M. Nolan D. Conneran
Project Director: D. Grehan
12.2m

Drawing Status: Planning

Patrick J. Tobin & Co. Ltd.

FALL FALL TOBIN Consulting Engineers, AECOM,


Block 10-4, Blanchardstown 4th Floor,
Corporate Park, Dublin 15, Adelphi Plaza,
Ireland. George's Street Upper,
tel: +353-(0)1-8030406 Dun Laoghaire,
EMERGENCY EXIT
fax:+353-(0)1-8030409 Ireland.
e-mail: dublin@tobin.ie T +353 (0) 1 238 3100
www.tobin.ie www.aecom.com
TOBIN Consulting Engineers will not be liable for any use of this document for
any purpose other than that for which it was originally prepared and provided.
Except where specifically and explicitly agreed in writing by TOBIN Consulting
Engineers, as copyright holder, no part of this document may be reproduced or
transmitted in any form and this document shall not be relied upon by any third
Revision:
party for any purpose.
PLAN - ROOF
SCALE 1:100
FIRE ESCAPE
Drawing No.: 7568-2103 A