H2000
Medium voltage switchgear for
primary distribution
Catalogue
Index
page
■ General description 2
■ Technical data 3
■ Cubicle types 4 - 13
■ Side views standard cubicles 14
■ Compartemented cubicles 15
■ Assembly 16
1
H2000
General information
2
H2000
Technical data
Weight
Cubicle type 03 (630 A), equipped with LF1 630 kg -
Cubicle type 03 (630 A), equipped with SF1 - 700 kg
Cubicle type 10 + 12 (3000 A), equipped with LF3 1700 kg -
■ The ambient air temperature does not exceed 40° C and its average value,
measured over a period of 24 hours, does not exceed 35° C. The minimum ambient
air temperature is -5° C for class ”minus 5 indoor”.
■ The influence of solar radiation may be neglected.
■ The altitude does not exceed 1000 m.
■ The ambient air is not significantly polluted by dust, smoke, corrosive and/or
flammable gases, vapours or salt.
■ The conditions of humidity are as follows;
■ the average value of the relative humidity, measured over a period of 24 hours,
does not exceed 95 %,
■ the average value of the water vapour pressure,over a period of 24 hours, does
not exceed 2,2 kPa,
■ the average value of the relative humidity, over a period of one month, does not
exceed 90 %,
■ the average value of water vapour pressureover a period of one month, does not
exceed 1,8 kPa.
3
H2000
Cubicle types
Basic design:
■ busbar
■ circuit breaker on withdrawable carriage
■ current transformer
■ earth-switch
■ capacitive voltage detecting system
Options:
■ voltage transformers
■ cable current transformer
■ auxiliary contacts
■ relay protection
■ compartement with insulated screens 12 kV ≤ 25 kA
■ door, mechanically interlocked with earthing switch
or switching device
■ motor operated vertical movement of breaker
■ multi contact plug for secondary wiring between
cubicles
Rated voltage 12kV 24kV
Max rated current cubicle 1250A 1250A
Busbar 3000A 2500A
Max short-time withstand current (1s) 40kA 25kA
Cubicle width (mm) 700-800 1000
Cubicle depth (mm) 1435-1525 1670
Cubicle height (mm) 2125 2125
Spare cubicle
Type 01
Basic design:
■ busbar
■ earthing switch
■ door type 03
■ capacitive voltage detecting system
Options:
■ auxiliary contacts
■ compartement with insulated screens 12 kV ≤ 25kA
■ door, mechanically interlocked with earthing switch
or switching device
■ multi contact plug for secondary wiring between
cubicles
Basic design:
■ busbar
■ circuit breaker on withdrawable carriage
■ earthing switch
■ capacitive voltage detecting system
Options:
■ auxiliary contacts
■ relay protection
■ compartement with insulated screens
12kV ≤ 25kA ≤ 1600A
■ door, mechanically interlocked with earthing switch
or switching device
■ motor operated vertical movement of breaker
■ multi-contact plug for secondary wiring between
cubicles
Cable cubicle
Type 12 Rated voltage 12kV 24kV
Max rated current cubicle 3000A 2000A
Basic design:
Busbar 3000A 2500A
■ busbar
Max short-time withstand current 40kA 25kA
Options: Cubicle width (mm) 700-1000 1000-1100
■ voltage transformers Cubicle depth (mm) 1435-1525 1670
■ current transformer Cubicle height (mm) 2125 2125
■ door, mechanically interlocked with earthing switch
or switching device
■ multi-contact plug for secondary wiring between
cubicles
H2000
Cubicle types
Basic design:
■ busbar
■ fuse load break switch with earthing switch and
mechanical trip release
■ earthing switch for cable
■ capacitive voltage detecting system
Options:
■ cable current transformer
■ auxiliary contacts
■ multi-contact plug for secondary wiring between
cubicles
■ motor operated vertical movement of breaker
Basic design:
■ busbar
■ load break switch with earthing switch
■ capacitive voltage detecting system
Options:
■ voltage transformer
■ current transformer
■ cable current transformer
■ auxiliary contacts
■ multi-contact plug for secondary wiring between
cubicles
■ motor operated vertical movement of breaker
6
Cubicle for contactor
Type 04
Basic design:
■ busbar
■ SF6-contactor (Rollarc) on withdrawable carriage
■ current transformer
■ earthing switch
■ capacitive voltage detecting system
Options:
■ fuse holders
■ voltage transformer
■ cable current transformer
■ auxiliary contacts
■ relay protection
■ compartement with insulated screens ≤ 25 kA
■ door, mechanically interlocked with earthing switch
or switching device
■ motor operated vertical movement of breaker
■ multi contact plug for secondary wiring between
cubicles
Rated voltage 12kV
Max rated current cubicle 400A, max fuses 200A
Busbar 3000A
Max short-time withstand current 40kA
Cubicle width (mm) 700-800
Cubicle depth (mm) 1435-1525
Cubicle height (mm) 2125
Basic design:
■ busbar
Options:
■ earthing switch
■ capacitive voltage detecting system
■ current transformer for cubicles ≤ 1600 A
■ voltage transformer for cubicles ≤ 1600 A
■ auxiliary contacts
■ relay protection
■ door, mechanically interlocked with earthing switch
0or switching device
■ multi-contact plug for secondary wiring between
cubicles
7
H2000
Cubicle types
Basic design:
■ busbar
■ disconnector carriage
■ earthing switch
■ capacitive voltage detecting system
Options:
■ fuse holders
■ auxiliary contacts
■ compartement with insulated screens 12 kV ≤ 25 kA
■ door, mechanically interlocked with earthing switch
or switching device
■ motor operated vertical movement of breaker
■ multi contact plug for secondary wiring between
cubicles
■ current transformer ≤ 1250 A
Basic design:
■ earth-switch
Options:
■ auxiliary contacts
■ capacitive voltage detecting system
8
Measuring cubicle
Type 02
Basic design:
■ busbar
Options:
■ current transformer
■ voltage transformer
■ multi contact plug for secondary wiring between
cubicles
Measuring cubicle
Type 09
Basic design:
■ busbar
■ circuit breaker on withdrawable carriage
Options:
■ earthing switch
■ fuse holders
■ auxiliary contacts
■ capacitive voltage detecting system
■ door, mechanically interlocked with earthing switch
or switching device
■ motor operated vertical movement of breaker
■ multi contact plug for secondary wiring between
cubicles
9
H2000
Cubicle types
Basic design:
■ busbar
■ voltage transformer
Options:
■ earthing switch
■ capacitive voltage detecting system
■ auxiliary contacts
■ door, mechanically interlocked with earthing switch
or switching device
■ multi contact plug for secondary wiring between
cubicles
■ fuse holders
Basic design:
■ voltage transformer
10
Busbar coupling Type 10 + 11
Basic design:
■ busbar
■ circuit breaker on withdrawable carriage
Options:
■ capacitive voltage detecting system
■ auxiliary contacts
■ relay protection
■ compartement with insulated screens
12kV ≤ 25kA ≤ 1600A
■ door, mechanically interlocked with earthing switch
or switching device
■ motor operated vertical movement of breaker
■ multi contact plug for secondary wiring between
cubicles
■ earthing switch
11
H2000
Cubicle types
Basic design:
■ busbar
■ loadbreak switch with earthing switch
■ capacitive voltage detecting system
Options:
■ auxiliary contacts
■ multi-contact plug for secondary wiring between
cubicles
■ motor operated load break switch
12
Busbar coupling Type 14 + 11
Basic design:
■ disconnector carriage
■ busbar
Options:
■ earthing switch
■ compartement with insulated screens
12kV ≤ 25kA ≤ 1600A
■ auxiliary contacts
■ door, mechanically interlocked with earth-switch or
switching device
■ motor operated vertical movement of breaker
■ multi contact plug for secondary wiring between
cubicles
■ fuse holders
■ capacitive voltage detecting system
13
H2000
Side views
standard cubicles
12kV
1. busbar with fixed contacts
2. pressure release compartment
3. low voltage compartment
4. channel for secondary cables
5. circuit breaker on withdrawable carriage
6. earthing switch
7. current transformer
8. earth busbar
9. cable current transformer
10. voltage transformer
24kV
1. busbar with fixed contacts
2. pressure release compartment
3. low voltage compartment
4. channel for secondary cables
5. circuit breaker on withdrawable carriage
6. earthing switch
7. current transformer
8. earth busbar
9. cable current transformer
10. voltage transformer
14
H2000
Cubicle with insulated
compartment
12kV
1. busbar with fixed contacts
2. pressure release compartment
3. low voltage compartment
4. channel for secondary cables
5. circuit breaker on withdrawable carriage
6. earthing switch
7. current transformer
8. earth busbar
9. cable current transformer
10. voltage transformer
11. insulating screens
15
H2000
Assembly,
commissioning
Example of switchgear
100* 150*
16