7SJ602 OVER CURRENT RELAY SETTINGS.

132/11.5 KV CIRCUIT CHAKWAL – CHOA SAIDEN SHAH

7100 INTEGRATED OPERATION.


7101 Language English

7200 PC AND SYSTEM INTERFACES.


7208 Function type in accord, with IEC 60780-5-103 160
7211 Data format for PC interface. DIGSI V3
7214 Transmission gaps for PC-interface. 1.0 s
7215 Transmission baud rate for PC-interface. 9600 Baud
7216 Parity and stop-bits for PC-interface. DIGSI V3
7221 Data format for system-interface. IEC 60870 Compatible.
7224 Transmission gaps for system-interface. 0.0 s
7225 Transmission baud rate for system-interface. 9600 Baud.
7226 Parity and stop-bits for system-interface. IEC/DIGSI V3/LSA.
7233 Supervision time for system-interface. 10 s
7235 Parameterizing via system-interface. No

7800 SCOPE OF FUNCTIONS.


7801 Characteristics of O/C protection Marshalling. Definite Time.

Settings Parameter Group A


1100 POWER SYSTEM DATA.
1101 Rated system frequency. 50 Hz
1105 Primary rated current. 600
1106 Secondary rated current. 5A
1110 Matching factor Ie/Iph for earth current. 0.15 s
1134 Minimum trip command duration. 1.00 s

1300 O/C PROTECTION PHASE FAULTS.


1301 o/c Protection for phase faults. On
1303 Pick up value of the high set inst. stage I>>> +* I/In block.
1305 Pick up value of the high set stage I>> 6.0 In block.
1307 Trip time delay of the high set stage I>> 0.02 s
1311 Measurement repetition. No
1312 Characteristic of the O/C stage Ip Definite
1313 Trip time delay inverse time O/C stage Ip 0.8 Sec.
1316 Pick up value inverse time O/C stage Ip 1.4 x In
1318 RMS format for inverse time O/c protection. Without harmonics.
1320 Manual close. I >> undelayed.

Setting: Chakwal Choa Saidan


1400 O/C PROTECTION EARTH FAULS.
1401 O/C protection for earth faults. On
1402 Pick up value of the high set stage IE>> 6 I/In block.
1404 Trip time delay of the high set stage IE>> 0.03 s
1408 Measurement repetition. No
1409 Characteristic of the O/C stage IEp Definite
1410 Trip time delay inverse time O/C stage IEp. 0.8 sec
1413 Pickup value inverse time O/C stage IEp. 0.2 In
1415 RMS format for inverse time O/C protection. Without harmonics.
1416 Manual close. IE >> undelayed.

2900 MEASUREMENT VALUE SUPERVISION.


2901 Summation threshold for current monitoring. 0.10 I/In
2902 Factor for current summation monitoring. 0.10 s

3800 ANNUNCIATION DELAY TIMES.


3801 Delay time for 1st user defined annunciation. 0.01 s
3802 Delay time for 1st user defined annunciation. 0.01 s
3803 Delay time for 1st user defined annunciation. 0.01 s
3804 Delay time for 1st user defined annunciation. 0.01 s

Calculated by ________________________ ____________________________


(Khalid Hassan Khan) D.M. (Fasihud Din) D.M.

Checked by
Muhammad Siddique Sindhu, Manager (S.P) North.