Beruflich Dokumente
Kultur Dokumente
“Hose stream demand” is the amount of water that must be added to the sprinkler sys-
tem hydraulic calculations so there is adequate supply to operate the sprinklers for effec-
tive fire control, and fill the hoses for fire extinguishment.
NFPA 13, Standard for the Installation of Sprinkler Systems, includes the following table for hose
stream demands:
Why are there three values in the “Inside Hose” column; and how are they applied?
“Inside Hose” generally is defined as 1- to 1-1/2-inch standpipe hose that may be con-
nected to the sprinkler system for initial fire attack by trained persons or during mop-up.
These may be called Class II standpipes.
If a sprinkler system has no inside hose stations connected to it, the applied
value is “0”. If the sprinkler system has one inside hose station, the designer
must add 50 gallons per minute to the water supply requirements for the
sprinkler system.
When the sprinkler system has two or more small hose stations attached to
it, the designer must add 100 gpm to the water supply requirement for the
sprinkler system. There are no additional requirements for more than two
hose stations.
The flow values must be added into the calculations where the hose stations
are connected to the sprinkler system. This is intended to assure that adequate water flow
will reach the sprinklers even though the standpipe hoses may be in use simultaneously.
For additional information, refer to NFPA 13, Standard for the Installation of Sprinkler Systems,
Chapter 11.