AIR CONDITIONING EQUIPMENT SCHEDULE: NOTES:

WATER COOLED CONDENSING UNIT GENERAL NOTES: LEGENDS 1. FOR SEVERAL DUCT HANGERS, TYPE "B", "C", OR "D"
MAY BE USED, SIZE OF HANGERS WILL BE SELECTED ON
COOLING CAPACITY OPERATING TEMPERATURE COMPRESSOR DATA CONDENSER DATA THE SUM OF DUCT WIDTHS EQUAL TO DUCT SCHEDULE
APPROXIMATE SAD SUPPLY AIR DUCT
UNIT QTY. AREA SERVED
EVAPORATING CONDENSING ELECTRICAL SUPPLY NO. OF OPERATING R E M A R K S 2. SCHEDULES OF ANGLE (IRON) BAR BRACING WITH
KW
TR,HP BTU/ HR NO. PROPELLER DRIVE WEIGHT (KGS) MAXIMUM SPACING OF 2.40 METERS ON CENTER
°C °F °C °F INPUT VOLTS PHASE CYCLE FAN FAG FRESH AIR GRILLE
UNIT SHALL BE SUITABLE FOR OUTDOOR INSTALLATION PROVIDE WITH SAFETY DEVICES,
TYPE "B" 25mm X 25mm X 3mm
WCCU-5.0 TR 1 - 5.0 TR 60,000 4.44 40 48.8 120 1 6.44 230 1 60 2 DIRECT 115
TIMER MOTOR FOR COMPRESSOR, ANTI-CYCLING HIGH & LOW PRESSURE CONTROLS,
VIBRATION ISOLATORS & OTHER STANDARD ACCESSORIES. TYPE "C" 38mm X 38mm X 5mm
CFM CUBIC FEET PER MINUTE
TYPE "D" 50mm X 50mm X 6mm
3. MAXIMUM SPACING FOR TYPE "A" IS 2.40 MTS O.C.
CMH CUBIC METER PER HOUR
4. PROVIDE AIRFLOW CAPACITY IN EVERY DIFFUSER FOR AIR
DISTRIBUTION BALANCE TESTING
FAN COIL UNIT HP HORSE POWER 5. PROVISION OF SPLITTER DAMPER PER BRANCH OF DUCT
6. ALL NEWLY INSTALLED DUCT HANGERS / SUPPORTS MUST BE
COOLING CAPACITY AIR FLOW CAPACITY COIL DATA MOTOR DATA
APPROXIMATE KW KILOWATTS PAINTED WITH DOUBLE COAT OF RUST PROTECTIVE
UNIT QTY. AREA SERVED OPERATING R E M A R K S
NO. OF NO. OF ELECTRICAL SUPPLY
TR,HP BTU/ HR CFM CMH FPI DRIVE HP/TR WATTS
WEIGHT (KGS) PAINT
CIRCUITS ROWS VOLTS PHASE CYCLE
UNIT SHALL BE CEILING CONCEALED MOUNTED DUCTED TYPE, FREE BLOWCOMPLETE WITH WASHABLE
SISW SINGLE INLET SINGLE WIDTH
2 60,000 2000 3400 1 3 12 DIRECT 5.0 230 1 60 230 E
FCU-5.0 TR - 5.0 TR 1,840 TYPE AIR FILTER, SPRING TYPE VIBRATION ISOLATORS AND STANDARD ACCESSORIES. D
B
TR TONS OF REFRIGERATION A
D. SLIDING SEAM
C

C. PITTSBURGH SEAM
L LOUVER

4500 SCHEDULE OF G.I. DUCT GAUGE


GI DUCT WIDTH MILLIMETER (MM) GAUGE: B. INSIDE GROOVE SEAM

PLATE COVER UP TO 300 26

330 TO 750 24

800 TO 1500 22
50mm Ø WCR 1550 TO 2250 20
A. DRIVE CLIP E. STANDING SEAM
& WCS PIPE

ACCESSORIES
10" AIR DUCT 2300 OVER 18

8" DUCT JOINTS & SEAM DETAIL

1950
2000

WELDED
5.0 TR SAD
300x300
NUT
AIR FLOW

HUAWEI ESCUTCHEON PLATE, GALVANIZED STEEL PIPE SLEEVE WITH 1/2" HANDLE
300 CFM LUCKY CHINATOWN MALL STAINLESS STEEL MINIMUM ANNULAR SPACE WITH INSULATION
300x200 SAD

SITE WING NUT


Reina Regente St.,Binondo, Manila
PIPE
DUCT CONCRETE SLAB
1/4"Ø METAL WINGED SCREW EXPANSION BOLT
5.0 TR NUT
AIR FLOW

ASBESTOS GASKET HANGER ROD SPRING VIBRATION


VAPOR BARRIER SEALING COMPOUND 1/2"THICK
NEOPRENE ROD ISOLATOR
BOTH ENDS
300x200 SAD

WALL AIR DUCT


OAKUM PACKING FOR BARE PIPE AND
DETAIL OF SERVICE HOLE (SH)
AIR FLOW

PIPE INSULATION INSULATION FOR INSULATED PIPE


(WHERE REQUIRED)
FLOW
AIR FLOW

FCU
300x200 SAD

SAD
300x300
SAD
300x300
PIPE THRU WALL DETAIL CANVAS CLOTH
AIR FLOW 300x200 SAD AIR FLOW CEILING LINE
300 CFM 300 CFM
N SUPPLY DUCT
CONNECTION FCU
2 VICINITY MAP RETURN AIR
11220

11220
AIR FLOW

SERVICE OPENING
7520

COOLING COIL
M-1 SCALE N.T.S.
AIR DUCT RETURN AIR CONNECTION
DUCTED TYPE FCU DETAIL
300x200 SAD
9220

W/ AIR FILTER

ACCESS DOOR ON SECONDARY DRAIN


SAD SAD
300x300 300x300 BOTRH SIDES PAN WITH 1"THICK INSULATION
AIR FLOW AIR FLOW FIELD FABRICATED
DRAIN P - TRAP
300 CFM 300 CFM
25 MM. @ CONDENSATE
AIR FLOW

DRAIN PIPE MIN. SIZE 16mm PLASTIC


CEILING LINE RUBBER TYPE VIBRATION
STRAPPING BOND
ISOLATOR
48 kg / m3 FIBERGLASS
DUCT SCHEDULE:
INSULATION, 50mm THK
STEEL BASE DRAIN PLUG
DUCT WIDTH (MM) DUCT GAUGE HANGER TYPE
FCU SECONDARY DRAIN PAN DETAIL
300x200 SAD

UP TO 305 24 A PLATFORM
355 TO 890 24 B TO THE NEAREST
FLOOR DRAIN
915 TO 1525 22 C
MECHANICAL CLIP
OVER 1525 20 D

FCU DRAIN CONNECTION DETAIL


750

AIR SPLITTER
AIR SPLITTER
AIR FLOW

DAMPER SLOPE 1" FLOW DAMPER


SAD FLOW IN 7"
300x300 D1
D1
CURVED FOR
D+3/4D
SPLITTER HEEL SPLITTER 45°
1000

300 CFM ROD 3/4D


RADIUS ROD 3/4D
D+3/4D
HEEL
D STRAIGHT D
RADIUS
WATER COOLED RETURN WATER COOLED SUPPLY THROAT THROAT
RADIUS A RADIUS B
MAIN WCS PIPE
DOUBLE THICNESS ALUMINUM FOIL
MAIN WCR PIPE VANES
SPLITTER VAPOR BARRIER
4500 AIR
(VERIFY LOCATION)
TO OTHER AREA

FLOW DAMPER
SHEET METAL AIR
BRANCH CHW PIPE
BRANCH CHW PIPE DUCT B.I. Ga 16
CURVED FOR
B.I. PIPE SCHEDULE PIPE INSULATION 2" THK. STYROPHOR,
SPLITTER 45°
B.I. PIPE SCHEDULE 1" THICK RUBBER PIPE INSULATION WITH 40 SEAMLESS 3lbs/FT. DENSITY WITH POLYETHELENE ROD 3/4D
D+3/4D
HEEL
40 SEAMLESS POLYETHELENE TAPE OR APPROVED STRAIGHT
TAPE OR APPROVED EQUAL D
RADIUS SPLITTER SPLITTER
EQUAL
THROAT
RADIUS
DAMPER ROD EXHAUST DUCT INSULATION DETAIL
GATE VALVE GATE VALVE C
D
AIR
1 AIR CONDITION DUCTING LAYOUT DIFFUSER DETAIL FLOW

M-1 SCALE 1: 50 MTS WATER COOLED PIPING CONNECTION DETAIL


TYPICAL DUCT TAKE OFF DETAIL
R.A - 545 PROJECT TITLE : OWNER : R E V I S I O N S: SHEET CONTENTS:
RA. 9266 ( ART. 4, SEC. 33 ) SHEET NO.
This drawing as an instrument of service,is the
OWNERSHIP OF PLANS, SPECIFICATION and other property of and document of Architect and the
DATE MARK / DESCRIPTION GENERAL NOTES
Gen. Contractor. It shall be unlawful for any person
CONTRACT DOCUMENTS. without the written consent of JOHYAJA Builders
AIR CONDITIONING DUCTING LAYOUT
Drawings ans specifications and other contract documents duly
signed ans sealed, as instruments of service, are the intellectual ELIEZER J. LAO
to copy or duplicate said document .
LEGEND & SYMBOLS M
property and documents of the architect, whether the object for which VICINITY MAP
P.D - NO.49
they are made is executed or not. It shall be unlawful for any person
to duplicate or to make copies of the said document for use in the
PROF. MECHANICAL ENGINEER "Protection of intellectual Property" works of
HUAWEI
DRAWN BY: KRISSELLE DATE: 08-16-18 PROJECT NO.: 1
MISCELLANEOUS DETAILS 1
repitition of and for other projects or buildings, whether executed
Art,Architecture,Models and Designs are creative
work and considered as part of the intellectual
LUCKY CHINATOWN MALL
PRC NO.: 1735 PTR.NO.: 5520274 C property of the author .
partly or in whole, without the written consent of architect. LOCATION: Reina Regente St.,Binondo, Manila 1006 Metro Manila REVISED BY: DATE:
DATE ISSUED:JANUARY 3, 2018 PLACED ISSUED: QUEZON CITY

Das könnte Ihnen auch gefallen