Beruflich Dokumente
Kultur Dokumente
ICB, M12
Inductive Sensors
Standard Range, Nickel-Plated Brass Housing
Types ICB, M12
• Sensing distance: 2 to 4 mm
• Flush or non-flush types
• Short or long body versions
• Rated operational voltage (Ub): 10 - 36 VDC
• Output: DC 200 mA, NPN or PNP
• Normally open or Normally closed
• LED indication for output ON
• Protection: reverse polarity, short circuit, transients
• Cable or M12 plug versions
• According to IEC 60947-5-2
• Laser engraved on front cap, permanently legible
• CSA certified for Hazardous Locations
Type Selection
Connec- Body Rated Ordering no. Ordering no. Ordering no. Ordering no.
tion style operating NPN, PNP, NPN, PNP,
distance Sn Normally open Normally open Normally closed Normally closed
Specifications
Rated operational voltage (Ub) 10 to 36 VDC (ripple incl.) Indication for short circuit/
Ripple ≤ 10% overload LED blinking (f = 2 Hz)
Output current (Ie) ≤ 200 mA @ 50°C Assured operating
(≤ 150 mA @ 50-70°C) sensing distance (Sa) 0 ≤ Sa ≤ 0.81 x Sn
OFF-state current (Ir) ≤ 50 μA Effective operating
distance (Sr) 0.9 x Sn ≤ Sr ≤ 1.1 x Sn
No load supply current (Io) ≤ 15 mA
Usable operating distance (Su) 0.9 x Sr ≤ Su ≤ 1.1 x Sr
Voltage drop (Ud) Max. 2.5 VDC @ 200 mA
Repeat accuracy (R) ≤ 10%
Protection Reverse polarity,
short-circuit, transients Differential travel (H)
(Hysteresis) 1 to 20% of sensing dist.
Voltage transient 1 kV/0.5 J
Ambient temperature
Power ON delay (tv) ≤ 20 ms Operating -25° to +70°C (-13° to +158°F)
Operating frequency (f) ≤ 2000 Hz Storage -30° to +80°C (-22° to +176°F)
Indication for output ON Activated LED, yellow Shock and vibration IEC 60947-5-2/7.4
NO version Target present
NC version Target not present
Specifications (cont.)
Housing material Approvals (cont.) CCC is not required for
Body Nickel-plated brass products with a maximum
Front Grey thermoplastic polyester operating voltage of ≤ 36 V
Connection EMC protection According to IEC 60947-5-2
Cable Ø4.1 x 2 m, 3 x 0.25 mm2, IEC 61000-4-2 (ESD) 8 KV air discharge,
grey PVC, oil proof 4 KV contact discharge
Plug M12 x 1 IEC 61000-4-3 3 V/m
Degree of protection IP 67 IEC 61000-4-4 2 kV
IEC 61000-4-6 3V
Weight (cable/nuts included) IEC 61000-4-8 30 A/m
Cable Max. 120 g
Plug Max. 30 g MTTFd 750 years @ 50°C (122°F)
Dimensions See diagrams below
Tightening torque 10 Nm
Approvals cULus (UL508)
cCSAus As Process Control
Equipment for Hazardous
Note: The terminal connector Locations.
(version ...M1) was not - Class I, Division 2,
evaluated. The suitability of Groups A, B, C and D.
the terminal connector should - T5, Enclosure Type 4.
be determined in the end-use Ambient temperature
application. Ta: -25° to +60°C
Dimensions (mm)
LED LED
7.5 7.5
M12x1
M12x1
Short body, flush version, cable Short body, non-flush version, cable
M12x1
4 3 4 3
1 2 1 2
Short body, flush version, plug Short body, non-flush version, plug
M12x1
Long body, flush version, cable Long body, non-flush version, cable
4 3
M12x1
M12x1
4 3
1 2
1 2
Long body, flush version, plug Long body, non-flush version, plug
Installation
Flush sensor, when installed in damping material, must be Non-flush sensor, when installed in damping material, must
according to Picture 1A. be according to Picture 1B.
Picture 1A Picture 1B
Free zone or ≥3xd Free zone or
≥ 3 x Sn non-damping ≥ 3 x Sn non-damping
d d
material material
≥ 2 x Sn
Flush sensors, when installed together in damping material, Non-flush sensors, when installed together in damping
must be according to Picture 2A. material, must be according to Picture 2B.
Picture 2A Picture 2B
d d d d d 2xd d d
Wiring Diagram
1 BN + 1 BN + 1 BN + 1 BN +
4 BK
2 BK 2 BK
4 BK
3 BU 3 BU
- - 3 BU 3 BU
- -
NPN - Normally open NPN - Normally closed PNP - Normally open PNP - Normally closed
Delivery Contents
• Inductive proximity switch ICB.
• 2 nuts NPB
• Packaging: plastic bag