M/s BORL – BINA 3X275 TPH CFBC BOILER

WRITE UP ON BOILER INTERLOCKS


FUNCTION GROUP : PURGE &SEAL AIR BLOWER -1

1. Reference P & ID : PID OF AIR & FLUE GAS


DRG.NO. 0-97-400-80039

2 EQUIPMENTS APPLICABLE

The PURGE&SEAL AIR BLOWER-1 system consists essentially the following


equipments

A. PURGE&SEAL AIR BLOWER-1


B. PURGE&SEAL AIR BLOWER-1 OUTLET DAMPER
C. Blower inlet Fiter DP Switch.

3. OPERATING LOGIC

3.1 Start up Operation

Before starting the system all the following conditions should be satisfied.

3.1.1 Permissives

- ID FAN should be in service.


- Boiler protection 1 not acted.
- P &S blower 1 selected for running
(P&S blower-2 in standby)
- Blower inlet filter DP not high

3.1.2 Sequence

Following actions will happen when start command issued by


manual/auto.

 Open outlet gate of P&S blower-1(4-ZSC-5338).

 Switch on P&S blower-1.

DOC.NO:5308:394805996.doc REV00 DT 08.05.07 Page 1 of 2


M/s BORL – BINA 3X275 TPH CFBC BOILER
WRITE UP ON BOILER INTERLOCKS
FUNCTION GROUP : PURGE &SEAL AIR BLOWER -1

3.2 SHUT DOWN OPERATION

3.2.1 Permissives
 None

3.2.2 Sequence

 Switch off P&S blower-1.


 Close outlet gate of P &S blower-1 (4-ZSC-5338).

3.3 Protection

Running P&S Blower-1 will trip, when any one of the following occurs.

 Emergency push buttons activated.


 Inlet filter DP high.
 Boiler Protection 1 acted.
 ID FAN tripped .
 P&S blower-1 on & its zero speed switch acted (4-SS-5301).
 P&S blower-1 safety relief valve not closed for >2 sec (4-ZSC-5337).
 P&S blower-1 out let damper closed (4-ZSC-5338).
 P&S blower-1 Motor protection acted.
 P&S blower-1 Motor winding temp v. high (4-TE-5325 TO 5330).
 P&S blower-1 Motor bearing temp v. high (4-TE-5323 & 5324).
 Local stop PB pressed.

3.4 Note
1. H.T. Motor winding, motor bearing temp. very high trip signals shall
be derived from respective signals.
2. Out of two PURGE & SEAL AIR Blowers one is standby, which will be
started automatically in case of the running blower tripped.
3. Provision will be provided for selecting any one as standby /
running.