Beruflich Dokumente
Kultur Dokumente
Corrosion Fatigue
Introduction
Corrosion fatigue occurs by the Corrosion fatigue in boiler tubes has
combined actions of cyclic loading been a major source of availability
and a corrosive environment. The loss in fossil-fueled power plants for
primary occurrence is on the water- over ten years. It is one of the last
side in waterwall and economizer major boiler tube failure mecha-
tubing, usually located adjacent to nisms to be characterized to the
attachments or restraints. point that root cause analysis and
solutions to prevent recurrence can
be defined. Although not as com-
mon as in subcritical boilers, the
same damage has also been found
in supercritical boilers.
Micro-features
• Multiple, transgranular cracks.
• Cracks usually wide.
• Cracks usually oxide filled and blunt
tipped.
• Crack profiles usually irregular.
• Signs of discontinuous growth,
re-initiations.
Onset of
final fracture
Figure 13-2. Schematic showing the general features of corrosion fatigue cracks.
Source: M.D.C. Moles and H.J. Westwood2
Figure 13-6. Cross-sections of corrosion fatigue cracks showing typical features: oxide coating of the fracture surface, corrosion
within the crack, wide crack mouths and tips, and a transgranular fracture path. Source: S.R. Paterson, et al.10
Penthouse Furnace
floor gas exit
scallop scallop
plate 1
plate
Buckstay Top
attachments 18 windbox
2 (a) Corner casing
10 (b) Tie-bars Rear wall attachment
10 (c) Stirrups arch Burner
throat Windbox
1 region
Bottom
windbox
casing Burner
attachment elevations
9
Windbox Buckstay
extension elevations
22 Gas flat bar
recirculation
duct Slope
19 region
6
attachment Boiler water Side wall
seal buckstay
3 + 4 connection
21 5
to slope wall 15 24 24
Figure 13-7a. Typical locations for tube failures by corrosion fatigue. Locations in tangentially-fired boilers.
Numbers refer to additional description given Table 13-2. Source: D McNabb, et al.1a
13 20 12
Side wall buckstay Upper
connection to gas off-
baffle wall take
gusset
plates
Windbox
and
burners
Lower
windbox Slope
casing region
attachment
23 Side wall/
slope wall 16 6
Furnace floor connection
connection End of waterwall Division wall
between front membrane region penetration
and rear walls of slope wall
Figure 13-7b. Typical locations for tube failures by corrosion fatigue. Locations in front/rear-fired radiant boil-
ers. Numbers refer to additional description given Table 13-2. Source: D. McNabb, et al.1a
2. Buckstay corners* a) Rigid corner scallop plate connected to buckstay B Remove or relieve rigid corner
b) Lug mounted tie-bar connected to tubes at A Same as for case (a)
corner
c) Tangent/membrane wall with filler bar D Remove filler bar
connections
3. Boiler ash hopper seal plate Continuous scallop plate B Change to U-bolt arrangement
4. Boiler seal heat shield a) Continuous scallop plate B Short tangent bar (3-4 tubes),
(slag screen) or a U-bolt arrangement
b) 6-8 tube tangential bar C Same as for case (a)
5. Side wall gusset plate Triangular plate between redirected tubes A Change to peg membrane
6. Division wall penetration a) Refractory box rigidly connected at the top D Remove rigid connections
of slope and bottom
b) Continuous scallop plate B Use refractory box without rigid
connections
7. Burner throat/gas off-take a) Short bars welded between redirected tangent C Replace tube ties with membrane
tube ties tubes bar
b) Short bars welded between tubes in tangent B Weld bar on hot side to restore
tube wall neutral bending axis to geometric
axis of tube
8. Burner barrel mounts Direct connection from burner barrel to waterwall C Use mounting plate between burner
and wall
Increase the number of attachment
lugs
9. Windbox extension vertical Windbox extension duct welded directly to vertical D Install expansion plate between
seal flat bar–flat bar is on outside of windbox, but could windbox casing and flat bar, remove
also be on inside flat bar on inside
10. Buckstay connections to a) Continuous scallop tie-bar C Use stirrups or lugs on membrane
waterwalls walls
Tack weld to alternate tubes on
tangent tube wall
b) Continuous tangent bar tack welded to tubes
• membrane wall D Same as for case (a)
• tangent tube wall B Same as for case (a)
11. Scallop tie-bars Tangent tube waterwalls – most failures at corners D Address source of stress
or associated with abnormally high loads Remove weld from every other tube
13. Miscellaneous filler bar a) Windbox strut attachment D Replace solid filler bars with formed
attachments* b) Side wall buckstay/baffle wall connection D plate filler bars
c) Slope wall support I-beam at side wall B
15. Side wall/slope wall seal a) Scallop bar D Replace with refractory box
b) Rod welded between tubes B
16. End of membrane More serious adjacent to redirected tube A Cut back membrane
17. Furnace gas exit scallop plate Continuous scallop plate C Move scallop plate further from
• adjacent to redirected tubes redirected tubes and cover with
refractory
18. Rear waterwall arch Continuous scallop bar D Cut scallop bar at intervals to make
• adjacent to separation of hanger tubes discontinuous
19. Side wall buckstay connection a) Tangent bar tack welded to tubes C Replace with scallop bar
to slope wall Evaluate necessity of attachment
b) Scallop bar tack welded on alternate sides of bar D Same as for case (a)
20. Side wall buckstay connection Flat bar connection to baffle wall seal welded with C No modification derived
to baffle wall filler bars at side wall
• lowest connection affected
21. Lower front/rear waterwall Immediately downstream of mud drums, with B Remove scallop bars and replace
S-bends locating scallop bars between tubes affected bends
22. Gas recirculation duct scallop Continuous scallop bar D No modification derived
plate attachment
23. Furnace floor connection Direct connection between nose tubes in opposite C Replace solid filler bars with formed
between nose tubes walls plate filler bars
• filler bars used No other modification derived
• natural gas-fired boiler only
24. Division wall tube ties* First set of tube ties above slope wall D No modification derived
*Listed stress rank applies to locations within the combustion or radiant sections of the boiler.
Source: D. McNabb, et al.1a
-1.0
1 5 10 100 1000 10,000
Oxygen Concentration (ppb)
There is no comprehensive model Figure 13-17. Strain, temperature and cycle chemistry information collected on the
that can predict the effect of various cold start of a 500 MW unit. (CBD) is continuous blowdown. Source: D. Sidey, et al.1d
environmental factors on the rate of
initiation and propagation of corro-
sion fatigue cracks in the boiler envi-
ronment. A number of past experi- dence or extent of corrosion fatigue A knowledge of cycle chemistry par-
mental programs have been con- damage. Unfortunately there has not ticularly during starts and transients
cerned with isolating the effect of been good correlation between what is essential. For example, at one unit
one or more major parameters such was thought to be important in the the major parameters (dissolved
as dissolved oxygen, pH and cation laboratory and what was measured oxygen, pH and cation conductivity)
conductivity. A broad outline of in the field. In the broad outline in were well maintained throughout
those studies and some of the impli- section 2.6.2 is a summary of what transients. This was the result of
cations are presented in the first part is presently known, what is thought specific operating procedures which
of this section (2.6.1) to be correct and is undergoing con- allowed up to 1 ppm free hydroxide
There have also been a few field firmation, and what is presently to counteract a phosphate hideout
studies that have tried to correlate unknown. The discussion here is lim- problem. Prior to making that
the results of the laboratory investi- ited to specific knowledge about change in procedure, pH would
gations with field measurements of boiler tube materials, the boiler envi- drop to around 7 during shutdown
similar factors, and with the inci- ronment and stress levels, and and remain around that level until
actual field investigations in working restart.26 Similar hideout was
boilers. observed during load changes as
Cold Start
Unit C2 (trip) 160 1,750 2,000 — 8.5 - 7.2 > 1,000 to < 1 1 - 11
Warm Start
Hot Start
Load Changing
Notes:
1Pressure/temperature ramp event
2Subcooling correction event.
3Unidentified temperature excursion
3.2.1 Restraint stresses (a). Compare damaged locations to those • Apply Influence Diagram • See guidance in Section 6.2.
at attachments typical of corrosion fatigue. See Figures (Section 3.5) as a tool to • Most effective measures have been
13-7a/b and Table 13-2. identify proper short- modification of attachments to lower
(b). Inspection of susceptible locations and long-term solutions. stresses.
before tube failures occur. • Replace damaged tubes.
(c). Selectively sample to identify damage • Do not pad weld.
accumulation. • Determine the extent of
(d). Thermocouple and/or strain gauge test- damage.
ing to confirm high strain • Confirm damage
locations. mechanism is corrosion
(e). Finite element stress analysis to fatigue.
predict high strain locations.
3.2.2 Subcooling (cooling (f). Review operating records. • Same as above. • Install off-line boiler circulation pumps
water stratification) (g). Thermocouple top and bottom of to reduce level of subcooling.
in natural circulation boiler to monitor DT as function of
boilers shutdown time.
(h). Strain gauge to confirm.
3.3 Influence of
Environmental Factors
3.3.1 Poor water chemistry (i). Review water chemistry logs and prac- • Same as above, particu- • Clean up overall cycle and confront
tices, with particular emphasis on pH larly initiating the appli- specific chemistry problems such as
reductions during shutdown and early cation of the Influence condenser leaks, impurity ingress,
startup; if review indicates a problem Diagram to characterize lack of appropriate procedures, lack
then implement a monitoring program. the contribution of the of appropriate monitoring devices, etc.
See discussion of minimum levels of environment. • Apply appropriate guideline procedures
instrumentation in Chapter 3, Volume 1. for specific chemistry, monitoring,
(j). Calculate Environmental Parameter for and instrumentation. See overview of
use in Influence Diagram from informa- recommended practices in Chapter 3,
tion gathered above Section 3.5.2 and Volume 1.
Table 13-5; this will help determine the
contribution of environment to the
corrosion fatigue problem.
(k). Selectively sample tubes from at-risk
areas for evidence of pitting or corro-
sion fatigue damage
3.3.2 Overly aggressive (l). Review chemical cleaning procedures, • Same as above, plus • Optimize chemical cleaning procedures
or improper chemical and correlate chemical cleaning with • Revise chemical clean- and frequency. See overview in
cleaning corrosion fatigue failures. ing procedures, as Chapter 4, Volume 1.
(m). Selective sampling of at-risk tubes. required.
3.3.3 Improper boiler (n). See actions in items (i),(j) above. • Same as above, plus • Optimize shutdown, lay-up procedures.
shutdown and/or • Optimize shutdown, lay- • See overview in Chapter 4, Volume 1.
lay-up procedures up procedures.
3.4.1 Operating procedures (o). Review operating records to determine • Apply Influence Diagram • See guidance in Section 6.2.
that have produced operating hours and boiler starts. as a tool to identify • Reduction of stresses or improvement
high stresses (p). Plot failure history against unit operat- proper short- and in environmental parameter are possible
ing conditions. See Figures 13-13 long-term solutions. actions.
and 13-14. • Replace damaged tubes.
• Do not pad weld.
• Determine the extent of
damage.
• Confirm damage
mechanism is corrosion
fatigue.
3.3 Influence of environmental given to reductions in pH during the If the review indicates a problem,
factors shutdown and early startup periods. then a monitoring effort should be
For phosphate-treated units, the key undertaken. The primary aim of such
3.3.1 Poor water chemistry. A vari- question will be whether phosphate a program would be to confirm any
ety of excursions, including low pH, hideout occurs, which will result in pH reduction. It should also address
high levels of dissolved oxygen, and phosphate return with concurrent pH the possibility that dissolved oxygen
cycle chemistry contaminants, can reductions during shutdown or load in the boiler tube, as monitored at
influence both propagation and initi- reductions. For AVT units, depres- the downcomer, is high during shut-
ation of corrosion fatigue. Poor water sions in pH during shutdown and down, and more importantly,
chemistry will accelerate the corro- early start up can result from conta- remains high (³ 20 ppb) well into the
sion attack in existing cracks or minant ingress, slippage from the startup period (past pressure rais-
breaks in the protective oxide; pit- condensate polisher, or carbon diox- ing).
ting caused by poor shutdown ide ingress. For both chemical treat-
chemistry can provide a preferential (k). Selectively sample tubes from
ments, the pH depressions can
initiation site for starting corrosion high stress areas, or other at-risk
remain during the early startup
fatigue cracks. locations, to determine whether pit-
period. ting has begun, or whether there is
Actions to confirm: (j). Using information gathered evidence of more advanced dam-
(i). A two-pronged approach is above, evaluate the severity of the age such as developing corrosion
required. The first part will be a environmental contribution to the fatigue cracks.
review of the chemistry records and corrosion fatigue problem by calcu-
logs. Particular emphasis should be lating the “environmental parameter”
for the influence diagram. This
process is discussed in more detail
in Section 3.5.2.
Excursions
3 How many hydrogen damage or caustic gouging events None One More than one
resulting in tube failures have occurred over the life 3 6 9
of the boiler?
1 (1a) Boiler water pH at blowdown 9.0 - 9.6 8.0 - 10.0 < 8, > 10
1 2 3
2 (1a) Boiler water pH at blowdown 9.0 - 9.6 8.0 - 10.0 < 8, > 10
2 4 6
2 (2) Feedwater at the economizer inlet, < 50 < 200 > 200
dissolved oxygen (ppb) 2 4 6
Chemical cleans
1 How many chemical cleans using a hydrochloric None One More than one
acid solution has the boiler been exposed to? 1 2 3
2 What actions are taken for shutdown corrosion protection: Actions Actions No action
(a) N2 cap on drum and treat water if boiler not drained. (a) to (d) (a) and (b)
(b) Refill drained boiler with chemically treated water to 2 4 6
control pH and oxygen
(c) Ensure dry storage if drained.
(d) Monitor and adjust pH and oxygen in boiler water
during wet lay-up.
Total Value: __________ (total for questions answered) Total Score: _______
Environment Parameter: = E1, for Total Score/Total Value = 1.0 to 1.5; = E2, for Total Score/Total Value = 1.5 to 2.0; = E3, for Total Score/Total Value = 2.0 to 2.5
= E4, for Total Score/Total Value = 2.5 to 3.0
Source: D. Sidey, et al.1d
6.2 Guidelines for the use of 4. Any analysis of stresses via finite Iteration may be required to refine
stress analysis and field mea- element methods should be sup- boundary conditions and symme-
surements ported by a field test program. try assumptions until agreement
A combination of stress analysis, Field testing alone may be is obtained.
using finite element methods, and enough. 2. A 3-D model should be formu-
field confirmation using strain lated to accommodate the triaxial
6.2.2 Evaluation of the subject
gauges, is useful for determining the stress state. Mesh size and num-
boiler. Analysis of the boiler should
contribution of strain to a location ber of elements should be such
precede any analytical program and
experiencing corrosion fatigue. It will as to allow convergence in a 2D
include identifying critical locations,
also be helpful to (i) determine thermal analysis: apply a thermal
identifying the major anticipated
whether proposed modifications will load to one side of the model and
loads, and reviewing tube failure
lower the applied strains, and (ii) add elements until there is no
history. This evaluation should result
confirm that, after modification, the change in the thermal distribution.
in a prioritized list of sites for evalua-
local condition did improve. Utilities A maximum aspect ratio of 7:1 for
tion. Tables 13-2 and Figures 13-
seeking to apply these methods elements has been recom-
7a/b provide a starting point for
should do so with a full understand- mended.
identifying those locations which
ing of the benefits to be gained and
have generally been a concern. 3. Detail of attachment is important.
the costs to execute such detailed
It was found, for example, that
evaluations. 6.2.3 Field testing. Field testing the assumption of a point attach-
is required to confirm major loads, ment for tack welds was not
6.2.1 Overall guidance
help define applicable boundary appropriate.
1. An analytical and experimental conditions for the stress analysis,
determination of applicable 4. When it is necessary to consider
and relate operating changes to
stresses is only one part of the structural loads, an orthogonal
load and cycle chemistry changes.
overall approach to corrosion plate extension to a local model
Instrumentation for a test program
fatigue. It is important to under- was recommended; however, a
might include temperature and
stand how it fits into that ap- global model was not considered
strain instrumentation, heat flux
proach and what the limitations of cost-effective.
meters, cycle chemistry analyzers,
the stress analysis methods are. and data acquisition equipment. 5. The cost of the analysis is related
2. A consistent and fully predictive to the complexity of the model,
6.2.4 Finite element analysis. which will cause tradeoffs to be
finite element stress analysis
Evaluation of model choice, degree made.
method is desirable as it would
of detail, boundary and symmetry
provide a way to assess potential 6. A sensitivity analysis is necessary
conditions are critical; simplifying
design changes prior to their to identify major applied loads at
assumptions must be made with
introduction and to predict their a given location.
care and confirmed. The following
efficacy.
key aspects are important1c: 7. Results should be presented in a
3. Modeling of a waterwall tube with form (polar coordinates, a nodal
1. Boundary and symmetry condi-
attachment requires careful con- map, etc.) that allow for the iden-
tions must be formulated from a
sideration of actual field loading, tification of high stress locations.
detailed evaluation of field test
geometry, and local constraint; A deformation map was also
results to include all critical field
simplification of model, boundary deemed to be useful.
conditions and loads.
conditions and/or symmetry
Subsequently, boundary and
choices can compromise the
symmetry conditions must be ver-
results.
ified. Measured and calculated
strains should be compared.
Corrosion Fatigue
Case Study I: Application of Influence Diagram
This case study illustrates how the Typical On-Line Chemical Operating The boiler is fired and pressurized to
influence diagram approach might Ranges: Typical on-line ranges for approximately 3 MPa to purge any
be used to determine locations with critical chemistry parameters (post- air in the steam and water circuits.
a potential for corrosion fatigue prob- 1984) are: Score “4”, for actions “a” and “b” on
lems and how the evaluation of the form.
stress rank and environmental para- • Boiler water pH: 9.1-9.8. Score “1”
on the form. The assessed environmental para-
meter might influence that analysis. meter is the total score “23”, divided
Unit Background: The unit is rated at • Boiler water cation conductivity: by the value of the questions
163 MW. The boiler is a subcritical, < 12 mS/cm minus a phosphate answered “18” or E = 1.3 in this
drum-type unit with natural circulation correction gives about 8mS/cm. case. As shown in the form, the
and reheat. It is fired on lignite. The Score “2” on the form. result falls in the range of E1 (good).
boiler has 68,000 firing hours and 728 • Feedwater dissolved oxygen: Equivalent Operating Hours: For
starts. Although the boiler has experi- < 5 ppb. Score “1” on the form. 68,000 firing hours, (H) and 728 total
enced serious sootblower erosion boiler starts (Ns) the equivalent
problems, there have been no report The cation conductivity required for
the form is corrected to typical phos- operating hours are derived from the
of BTF by corrosion fatigue to date. equation:
phate concentrations. Unit records
Stress Rank Evaluation: The first indicated a normal phosphate level of EOH = (H/1000) + (Ns/(H/1000))
step in the evaluation process is to 1 ppm, for a correction of 4.1 mS/cm. = 78.7
identify sites where the magnitude of Note also that the unit has an all fer-
the stress might be sufficient to Results: The corrosion fatigue
rous feedwater system; that is, there
cause a corrosion fatigue concern. A regime for this situation can now be
are no copper alloy materials in the
detailed inspection of unit was con- determined by plotting the results on
condensate or feedwater systems.
ducted; as a result a boiler ash hop- the influence map. This is shown in
per seal plate attachment was Typical Start-Up Chemical Operating Figure 13-24. Under the assigned
selected for further evaluation. Figure Ranges: Selection of proper ranges conditions, the location is at high
13-23 shows detail of the location. A for start is complicated by variations risk for damage due to corrosion
stress rank of “B” was assigned by in chemistry and stress over the start- fatigue because the point falls to the
noting that this location was similar up period. For the evaluation, typical right of the E1 line. There have been
to that of location #3 in Figure 13-7 ranges at the point of attaining full or no failures yet. It is possible that the
and Table 13-2. target steam drum pressures are actual stress at the location is
used. Defining these ranges will slightly less than the typical “B”
Environmental Parameter: A review require data from several starts of location. However, there should be
of the unit chemistry history allowed each type (cold, warm and hot). The sufficient concern to conduct selec-
a calculation of the environmental subject boiler had these ranges: tive tube sampling for corrosion
parameter as detailed in Table 13-6. fatigue at this location, despite the
The following information served as • Boiler water pH: 9.1-9.8. Score “2” fact that no failures have been
the basis: on the form. observed yet.
Phosphate Boiler Water Alkalinity • Boiler water cation conductivity, 20 It is also easy to see how, given a
Control: Until about mid-1984 the mS/cm - correction of 4 mS/cm = 16 currently marginal situation, a slight
unit used congruent phosphate treat- mS/cm. Score “4” on the form. deterioration in the operating prac-
ment. A review of the level of phos- tices for cycle chemistry control
phate consumption indicates that the • Feedwater dissolved oxygen < 50
ppb. Score “2” on the form. could push the situation into consid-
boiler had a severe hideout problem, erably more severe problems. It is
which would be a factor of “9” on the Chemical Cleans: There had been no interesting to note that the earlier
form. However, the unit switched to chemical cleans since commission- operation with congruent phosphate
equilibrium phosphate treatment in ing. Score “1” on the form. treatment and a severe hideout
late 1984 and has not had a hideout problem would have been charac-
problem since that time. Therefore Boiler Shutdown/Lay-Up Procedures:
On shutdown a nitrogen blanket is terized by a calculated environmen-
the form shows “3” for this entry. tal parameter of E2; almost certainly
introduced once the boiler reaches
Excursions: The boiler had experi- atmospheric levels. If the boiler is a severe corrosion fatigue problem
enced no excursions causing hydro- drained and refilled, the water is would have resulted.
gen damage (low pH events). Score treated during the refilling process.
“3” on the form.
Scallop
bar
Windbox Fillet
casing weld
CL furnace
O.D.front or rear
wall tubes
Mud drum
Seal
Slag screen: stainless plates
steel type 430 woven
wire space cloth Water Water
level trough
Figure 13-23. Schematic of the boiler ash hopper seal plate attachment.
Source: D. Sidey, et al.1d
(B)
Low High
risk risk
(C)
Environment
parameter (E)
E4 E3 E2 E1
Low
Stress (D)
0 30 60 79 90 120 150
Equivalent Operating Hours (EOH)
Figure 13-24. The case study results are plotted onto the influence map to determine
the appropriate corrosion fatigue susceptibility. Source: D. Sidey, et al.1d
Excursions
3 How many hydrogen damage or caustic gouging events resulting None One More than one
in tube failures have occurred over the life of the boiler? 3 6 9 3
1 (1a) Boiler water pH at blowdown 9.0 - 9.6 8.0 - 10.0 < 8, > 10
1 2 3 1
2 (1a) Boiler water pH at blowdown 9.0 - 9.6 8.0 - 10.0 < 8, > 10
2 4 6 2
2 (2) Feedwater at the economizer inlet, dissolved oxygen (ppb) ² 50 ² 200 > 200
2 4 6 2
Chemical cleans
1 How many chemical cleans using a hydrochloric acid solution None One More than one
has the boiler been exposed to? 1 2 3 1
2 What actions are taken for shutdown corrosion protection: Actions Actions No action
(a) N2 cap on drum and treat water if boiler not drained. (a) to (d) (a) and (b)
(b) Refill drained boiler with chemically treated water to 2 4 6 4
control pH and oxygen
(c) Ensure dry storage if drained.
(d) Monitor and adjust pH and oxygen in boiler water
during wet lay-up.
24Kussmaul, K. and B. Iskluth, “Environmentally Assisted Chemistry Guidelines for Fossil Plants: Phosphate
Crack Growth in a Low Alloy Boiler Steel in High Treatment for Drum Units, Final Report TR-103655,
Electric Power Research Institute, Palo Alto, CA,
Temperature Water Containing Oxygen”, Nuclear
December, 1994.
Engineering and Design, Vol. 119, Elsevier Science
Publishers, B.V., North Holland, 1990, pp. 415-430. 31Dooley, R.B., A. Aschoff, and F. Pocock, Cycle
25Personal Communication from T. Healy, (ESB Ireland) to Chemistry Guidelines for Fossil Plants: All-Volatile
R.B. Dooley, February, 1995. Treatment for Drum Units, TR-105041, Electric Power
Research Institute, Palo Alto, CA, to be published 1996.
26Sidey,D., et al., “Lambton TGS Unit 4, Investigation 32Dooley, R.B. and L.D. Paul, “Phosphate Chemistry and
Into Lower Waterwall Header and Steam Drum
Corrosion Fatigue”, International Water Conference,
Cracking”, Ontario Hydro Internal Report CTS-31020-5,
Pittsburgh, PA, October, 1995, IWC-95-17.
August, 1983.
27Stodola, J., “Review of Boiler Water Alkalinity Control”,
International Water Conference, 47th Annual Meeting,
held in Pittsburgh, Pennsylvania, October 27-29, 1986.
A failure has occurred which the ➠ Confirm that damage location is May still be corrosion fatigue, con-
BTF team has tentatively identi- consistent with corrosion fatigue. tinue through flowchart; however,
fied as being caused by corro- Is damage associated with a review for indications of mechani-
sion fatigue (Action 1a). Action 2 susceptible location? See cal fatigue, see distinctions dis-
should clearly identify corrosion Figures 13-7a/b and Table 13-2. cussed in main text, Section 1.1.
fatigue as the primary mecha-
nism or point to another cause.
The actions listed will be exe-
cuted by removing representative ➠ Determine location of damage If OD-initiated, mechanism is more
tube sample(s), followed by initiation. Is damage initiated likely to be mechanically-induced
from the inside (waterside) of fatigue. Review main text Section
visual examination and detailed
the tube? 1.1 for distinctions.
metallographic analysis. One of
the primary aims is to establish
that damage is not OD-initiated
fatigue. ➠ Evaluate nature of cracking. Is If damage is of a more ‘gouging”
there evidence of multiple initia- nature check to see if an underde-
tion sites, with wide cracks, of a posit corrosion mechanism (hydro-
transgranular nature? gen damage, caustic gouging or
acid phosphate corrosion) is active.
3.3.1 Poor water chemistry ➠ i). Review water chemistry logs and prac-
tices, with particular emphasis on pH
reductions during shutdown and early
startup; if review indicates a problem then
implement a monitoring program. See dis-
cussion of minimum levels of instrumenta-
tion in Chapter 3, Volume 1.
➠ j). Calculate Environmental Parameter for
use in Influence Diagram from information
gathered above; this will help determine
the contribution of environment to the cor-
rosion fatigue problem.
➠ k). Selectively sample tubes from at-risk
areas for evidence of pitting or corrosion
fatigue damage.
3.3.2 Overly aggressive or improper chemical ➠ l). Review chemical cleaning procedures
cleaning and correlate chemical cleaning with cor-
rosion fatigue failures. See Chapter 4,
Volume 1 for additional information about
chemical cleaning.
➠ m). Selectively sample at-risk tubes.
3.3.3 Improper boiler shutdown and/or ➠ (n). See actions in items (i, j) above.
lay-up procedures
3.4.1 Operating procedures that have pro- ➠ (o). Review operating records to deter-
duced high stresses mine operating hours and boiler starts.
➠ (p). Plot failure history against unit oper-
ating conditions. See Figures 13-13 and
13-14.
The correction of the underlying Major Root Cause Influences ➠ Long-Term Actions
problem(s) and the prevention of
repeat failures are priorities for Influence of Excessive Stresses
the BTF team. The proper
choice of long-term actions will Restraint stresses at attachments ➠ See guidance in main text for this mecha-
be based on clear identification nism, Section 6.2.
of the underlying root cause(s), ➠ Most effective measures have been modifi-
guided by the influence dia- cation of attachments to lower stresses.
gram. The most effective long-
term solution has been lowering Subcooling (cooling water stratification) in ➠ Install off-line boiler circulation pumps to
the applied stresses by modify-
natural circulation boilers reduce level of subcooling.
ing attachment designs; how-
ever, improper modifications
have intensified the problem. Influence of Environmental Factors
Improper boiler shutdown and/or lay-up ➠ Optimize shutdown, lay-up procedures. See
procedures Chapter 4, Volume 1.
Operating procedures that have produced high ➠ See guidance in main text for this
stresses mechanism, Section 6.2, and references
provided there.
➠ Reduction of stresses or improvement in
environmental parameter are possible actions.
The final step for the BTF team is Corrosion Fatigue Alert for Other Cycle ➠ Actions
to review the possible ramifica- Aspect Components
tions to other cycle components Problems with boiler • Potential for boiler tube ➠Implement stricter cycle chemistry
implied by the presence of corro- water or feedwater damage by other mech control program, instrumentation. See
sion fatigue or its precursors. chemistry control. anisms such as acid phos- Chapter 3, Volume 1 for an overview of
phate corrosion, if underly- the issues.
ing problem is phosphate ➠Alert to potential problems
hideout, or hydrogen dam- throughout cycle.
age such as via condenser
leakage.
• Potential for carryover
in steam to reheater.
Excessive or overly Potential for boiler tube ➠Apply guidelines for chemical
aggressive chemical damage by other mecha- cleaning as summarized in Chapter 4,
cleans. nisms Volume 1.