Sie sind auf Seite 1von 42

Chapter 13 • Volume 2

Corrosion Fatigue

Introduction
Corrosion fatigue occurs by the Corrosion fatigue in boiler tubes has
combined actions of cyclic loading been a major source of availability
and a corrosive environment. The loss in fossil-fueled power plants for
primary occurrence is on the water- over ten years. It is one of the last
side in waterwall and economizer major boiler tube failure mecha-
tubing, usually located adjacent to nisms to be characterized to the
attachments or restraints. point that root cause analysis and
solutions to prevent recurrence can
be defined. Although not as com-
mon as in subcritical boilers, the
same damage has also been found
in supercritical boilers.

Volume 2: Water-Touched Tubes 13-1


1. Features of Failure and Typical Locations
1.1 Features of failure crack is generally associated with
Corrosion Fatigue: Corrosion fatigue failures occur in a discontinuity or stress riser, such
Identification Keys water-touched tubes, usually in as the toe of a weld, whereas the
1. Failures are initiated at the waterwall tubing, but also in econo- ID-initiated corrosion fatigue crack
inside surface, at multiple initia- mizer tubing under some conditions. would only rarely break through to
tion sites, which can be associ- Corrosion fatigue cracks initiate on the outside surface exactly at the
ated with pits or other surface the inside surface. Although they are toe. An exception would be cracks
discontinuities. predominantly located on the cold- that linked—one initiated on the
2. Damage at the outside tube side of the inside surface such dam- inside surface and the other initiated
surface can appear as a pin- age may also form on the fireside. on the outside surface.
hole, a thick-edge crack that is General features of corrosion fatigue Second, when grinding the flaw prior
usually axial but may be cir- cracks are listed in Table 13-1. to weld repair, the outside-surface
cumferential, or a thick-edge initiated damage will decrease with
section “blow-out”. Particular A typical failure is shown in Figure
13-1; key features illustrated here grinding depth into the tube, the
care must be taken to distin-
are the initiation at multiple sites on inside-surface initiated damage will
guish corrosion fatigue from
the inside of the tube, the longitudi- become more widespread. Third,
outside surface-initiated
mechanical fatigue. nal orientation of the cracks and the externally initiated fatigue cracks
association of the failure with an tend to show up earlier in the life of
3. Cracks are usually wide, oxide external tube attachment. Figure the boiler.
filled, with irregular profiles and
13-2 shows schematically the gen- The second damage manifestation,
evidence of discontinuous
growth.
eral features of this damage type; the thick-edged crack such as
these features are shown in actual shown in Figure 13-5. This damage
4. Failures are nearly always asso- tubes in Figures 13-3 and 13-4. As type is generally associated with
ciated with tube attachments or shown, cracks initiate from multiple attachments, but may be of consid-
other locations where significant sites at the inside surface, are ori- erable length and extend beyond
constraint stresses develop. A ented axially, can grow through the the attachment area.
list of 24 generic failure loca- wall, and although they may be
tions has been developed. associated with pits and other inter- The third macroscopic manifestation
nal defects, they are not necessarily of damage is the thick-edge blow-
associated with weld defects. out or rupture and is characterized
Sometimes damage is also seen on by cracking down both sides of the
the outside surface. tube along the weld lines of the
membrane; this causes an entire
Corrosion fatigue cracks have been section of tube to fail (Figure 13-1).
identified with three types of macro- This third form is rare but has the
scopic appearance: (i) a pinhole potential to cause catastrophic dam-
leak, (ii) a thick-edged crack ori- age and can be a safety problem if it
ented axially (usually) or circumfer- occurs on the cold side of the tube in
entially, or (iii) a thick-edge blow-out an area with heavy personnel traffic.
or rupture which usually follows the
membrane weld line either on the Microscopically, corrosion fatigue
hot or cold side. cracks are characterized by features
such as multiple, wide, transgranular
The pinhole leak on the tube outside cracks with irregular profiles, usually
surface is the most commonly filled with oxide and showing signs
observed form. Figure 13-4 would of discontinuous growth such as
be typical of the cross section crack arrest marks. Figure 13-6
through such a defect type. This shows cross sections through corro-
damage manifestation can often be sion fatigue cracks illustrating these
confused with an OD-initiating features.
mechanical fatigue crack. There are
three means to distinguish the two.
First, the surface-initiated fatigue

13-2 Corrosion Fatigue


Table 13-1
Common Features of
Corrosion Fatigue Damage
Macro-features
• Initiation from inside (waterside) of tube.
• “Typical” development on “cold” side of
the tube but can be on fireside.
• Cracks usually oriented longitudinally
with respect to tube axis, i.e., normal to
the predominant stress field, which in the
typical case are tensile hoop stresses.
• Cracks can also be circumferential or any
direction that is normal to the major
applied stress.
• Can be initiated from pits or other surface
discontinuities.
• Not OD-initiated.
• Not specifically related to presence of
weld defects.

Micro-features
• Multiple, transgranular cracks.
• Cracks usually wide.
• Cracks usually oxide filled and blunt
tipped.
• Crack profiles usually irregular.
• Signs of discontinuous growth,
re-initiations.

Figure 13-1. An example of corrosion fatigue cracking in SA-210 A1 waterwall tubing.


Note that the main failure is coincident with an attachment welded onto the tube and
that there are multiple longitudinal cracks on the tube inside surface. Source: G.I.
Ogundele, et al.1b

Volume 2: Water-Touched Tubes 13-3


Protective Fe 3O4 Water/steam
Secondary side
crack
Deposited
particles

Slip band Extensive


activity oxidation
Spherical Deformed
corrosion particles
pits

Onset of
final fracture

Figure 13-2. Schematic showing the general features of corrosion fatigue cracks.
Source: M.D.C. Moles and H.J. Westwood2

Figure 13-4. Throughwall penetration of


a corrosion fatigue crack. Note how the
crack decreases in width towards the
outside surface. Source: H.J. Westwood
and W.K. Lee3

Figure 13-3. Typical multiple corrosion fatigue cracks in a boiler


waterwall tube. Source: D. Sidey, et al.1d

13-4 Corrosion Fatigue


Figure 13-5. Thick-edged failure by corrosion fatigue. Source: D. Sidey, et al.1d

Figure 13-6. Cross-sections of corrosion fatigue cracks showing typical features: oxide coating of the fracture surface, corrosion
within the crack, wide crack mouths and tips, and a transgranular fracture path. Source: S.R. Paterson, et al.10

Volume 2: Water-Touched Tubes 13-5


Steam
drum
17

Penthouse Furnace
floor gas exit
scallop scallop
plate 1
plate
Buckstay Top
attachments 18 windbox
2 (a) Corner casing
10 (b) Tie-bars Rear wall attachment
10 (c) Stirrups arch Burner
throat Windbox
1 region
Bottom
windbox
casing Burner
attachment elevations

9
Windbox Buckstay
extension elevations
22 Gas flat bar
recirculation
duct Slope
19 region
6
attachment Boiler water Side wall
seal buckstay
3 + 4 connection
21 5
to slope wall 15 24 24

Front wall Side wall Side (a) (b)


S-bends gusset plate wall/slope Division Lower
wall wall division
connection penetration wall tube
of slope ties
Note: Buckstay corner failures occur at Buckstay elevation ( )
other than in Slope region and Burner elevation

Figure 13-7a. Typical locations for tube failures by corrosion fatigue. Locations in tangentially-fired boilers.
Numbers refer to additional description given Table 13-2. Source: D McNabb, et al.1a

1.2 Locations of failure factors: size, mode of operation, fuel


A major effort has gone into identify- type, quality of cooling water and
ing the most common initiation sites cycle chemistry. Table 13-2 presents
for corrosion fatigue. The predomi- those locations in order of the fre-
nant locations are near tube attach- quency with which corrosion fatigue
ments: locations where large was found for the units surveyed.
stresses develop during transient These locations are illustrated
operating conditions as thermal schematically in Figures 13-7a and
expansion has been constrained by 13-7b for two generic boiler designs
the attachment. Typical locations - a tangentially-fired radiant boiler
include windbox casing attach- and a front/rear fired radiant boiler,
ments, buckstay attachments, and respectively. As a general rule, any
scallop bar attachments. In econo- failure associated with constraint
mizer tubing, failures have been (attachment) should be examined
reported in bends or the heat- carefully for evidence of a corrosion
affected zone of welds. fatigue mechanism.
A list of twenty-four susceptible loca- Table 13-2 summarizes the key
tions was developed following the aspects of corrosion fatigue at each
detailed survey of ten operating location including: a description of
units with a history of corrosion the design, nature of the failures,
fatigue failures.1a The units were all and recommended modifications.
subcritical drum units but otherwise Table 13-2 also presents a “stress
were chosen to reflect a variety of

13-6 Corrosion Fatigue


14
Scallop plate penthouse
floor connection

13 20 12
Side wall buckstay Upper
connection to gas off-
baffle wall take
gusset
plates

Gas Gas off-


outlet takes
7
Upper
windbox 8
casing (a) Burner throat region
attachment (b) Burner mount

Windbox
and
burners

Lower
windbox Slope
casing region
attachment

23 Side wall/
slope wall 16 6
Furnace floor connection
connection End of waterwall Division wall
between front membrane region penetration
and rear walls of slope wall

Figure 13-7b. Typical locations for tube failures by corrosion fatigue. Locations in front/rear-fired radiant boil-
ers. Numbers refer to additional description given Table 13-2. Source: D. McNabb, et al.1a

rank” for the location, and possible A common denominator among


modifications that can be used in nearly all of the most common fail-
corrective strategies; these two top- ure locations is the presence of sig-
ics are discussed in considerably nificant thermal gradients, induced
more detail in sections that follow. by either (i) high heat flux typical, for
example, of the sites in the combus-
The problem can also arise in econ-
tion zone of the furnace, or (ii) a
omizer tubing. The general industry
variety of other causes such as
experience has indicated the most
where tubing carrying different
likely failure locations are (i) at
media (e.g. steam and water) are
bends, (ii) in welds with the potential
connected.
for high residual stresses such as fin
welds, and (iii) at attachments simi- Failures have also been found at may be verified
lar in nature to those outlined above locations without significant thermal
for waterwalls. Parts of economizer gradient. These are generally the
circuits can form walls of the back result of: (i) poor boiler water chem-
pass. istry conditions, (ii) an unusual
structural loading, or both.

Volume 2: Water-Touched Tubes 13-7


Table 13-2
Corrosion Fatigue Failure Site List with Descriptions, Stress Ranking, and Potential Modifications
Stress Rank
for Use in
Location Description Influence Diagram Applied Modification

1. Windbox casing a) Continuous scallop plate–primarily corner B No modification derived


tubes affected
b) Filler bars B Replace cast filler bars with plate
formed filler bars

2. Buckstay corners* a) Rigid corner scallop plate connected to buckstay B Remove or relieve rigid corner
b) Lug mounted tie-bar connected to tubes at A Same as for case (a)
corner
c) Tangent/membrane wall with filler bar D Remove filler bar
connections

3. Boiler ash hopper seal plate Continuous scallop plate B Change to U-bolt arrangement

4. Boiler seal heat shield a) Continuous scallop plate B Short tangent bar (3-4 tubes),
(slag screen) or a U-bolt arrangement
b) 6-8 tube tangential bar C Same as for case (a)

5. Side wall gusset plate Triangular plate between redirected tubes A Change to peg membrane

6. Division wall penetration a) Refractory box rigidly connected at the top D Remove rigid connections
of slope and bottom
b) Continuous scallop plate B Use refractory box without rigid
connections

7. Burner throat/gas off-take a) Short bars welded between redirected tangent C Replace tube ties with membrane
tube ties tubes bar
b) Short bars welded between tubes in tangent B Weld bar on hot side to restore
tube wall neutral bending axis to geometric
axis of tube

8. Burner barrel mounts Direct connection from burner barrel to waterwall C Use mounting plate between burner
and wall
Increase the number of attachment
lugs

9. Windbox extension vertical Windbox extension duct welded directly to vertical D Install expansion plate between
seal flat bar–flat bar is on outside of windbox, but could windbox casing and flat bar, remove
also be on inside flat bar on inside

10. Buckstay connections to a) Continuous scallop tie-bar C Use stirrups or lugs on membrane
waterwalls walls
Tack weld to alternate tubes on
tangent tube wall
b) Continuous tangent bar tack welded to tubes
• membrane wall D Same as for case (a)
• tangent tube wall B Same as for case (a)

13-8 Corrosion Fatigue


Table 13-2
Corrosion Fatigue Failure Site List with Descriptions, Stress Ranking, and Potential Modifications (continued)
Stress Rank
for Use in
Location Description Influence Diagram Applied Modification

11. Scallop tie-bars Tangent tube waterwalls – most failures at corners D Address source of stress
or associated with abnormally high loads Remove weld from every other tube

12. Miscellaneous waterwall a) Sootblower penetrations D Replace with peg membrane


penetration gusset plates* b) Burner throat and gas off-takes C

13. Miscellaneous filler bar a) Windbox strut attachment D Replace solid filler bars with formed
attachments* b) Side wall buckstay/baffle wall connection D plate filler bars
c) Slope wall support I-beam at side wall B

14. Penthouse floor attachments Continuous scallop plate No modification determined


a) problems most common in corners D
b) more serious if connecting tubes carrying B
different media

15. Side wall/slope wall seal a) Scallop bar D Replace with refractory box
b) Rod welded between tubes B

16. End of membrane More serious adjacent to redirected tube A Cut back membrane

17. Furnace gas exit scallop plate Continuous scallop plate C Move scallop plate further from
• adjacent to redirected tubes redirected tubes and cover with
refractory

18. Rear waterwall arch Continuous scallop bar D Cut scallop bar at intervals to make
• adjacent to separation of hanger tubes discontinuous

19. Side wall buckstay connection a) Tangent bar tack welded to tubes C Replace with scallop bar
to slope wall Evaluate necessity of attachment
b) Scallop bar tack welded on alternate sides of bar D Same as for case (a)

20. Side wall buckstay connection Flat bar connection to baffle wall seal welded with C No modification derived
to baffle wall filler bars at side wall
• lowest connection affected

21. Lower front/rear waterwall Immediately downstream of mud drums, with B Remove scallop bars and replace
S-bends locating scallop bars between tubes affected bends

22. Gas recirculation duct scallop Continuous scallop bar D No modification derived
plate attachment

23. Furnace floor connection Direct connection between nose tubes in opposite C Replace solid filler bars with formed
between nose tubes walls plate filler bars
• filler bars used No other modification derived
• natural gas-fired boiler only

24. Division wall tube ties* First set of tube ties above slope wall D No modification derived

*Listed stress rank applies to locations within the combustion or radiant sections of the boiler.
Source: D. McNabb, et al.1a

Volume 2: Water-Touched Tubes 13-9


2. Mechanism of Failure
2.1 Introduction In general, the magnetite layer can
Corrosion Fatigue: Mechanism Corrosion fatigue is one of a number be damaged either by chemical
1. Corrosion fatigue is caused by of failure mechanisms that consist of means (corrosion) or by mechanical
the synergistic effects of stress synergistic effects of stress and means (strain), or by the synergistic
and environment. This leads to environment. Among the boiler tube effect of the two5. Destabilization
a breakdown of the protective failure mechanisms, other combina- primarily by chemical means usually
magnetite on a tube surface by tions have variously been termed occurs at pre-existing active sites,
both mechanical (stress) and stress corrosion cracking and resembles pitting and has some-
chemical (environment) means. times been termed stress-assisted
stress-assisted pitting. In many
2. Corrosion fatigue is a discontin- ways the distinction among various pitting. When the film is destabilized
uous process with cracks stress/environment-driven failure primarily by strain, corrosion paths
initiating and growing during mechanisms is artificial, character- are produced, leading to an array of
transient periods such as ized by whether the stress or the cracks and is generally termed cor-
starts and stops, and full load environmental aspect seems to be rosion fatigue in boiler tubes.
operation. predominant. The end result in any Rupture of the protective oxide film
3. Transient operations result in case is the accumulation of damage leads to more rapid damage by cor-
cyclic strains driven by temper- through the interaction of the two rosion fatigue because (i) additional
ature differences between basic contributors. base metal is exposed to corrosion
attachments and the tube. damage and (ii) the rupture, which
A significant effort has gone into
During peak strain range peri- is a crack or crack-like, acts as a
ods reinitiation or initial crack-
characterizing corrosion fatigue
damage, differentiating it from dam- stress concentrator.
ing of the protective oxide will
occur. Full load operation can age caused by other mechanisms, The critical strain to fracture mag-
result in a corrosive environ- and to targeting solutions specific to netite at high temperatures is gener-
ment which allows crack corrosion fatigue. The balance of ally reported to be between 0.01
growth. this section reviews the following and 0.1% strain.1b, 6-8 That there is a
aspects of corrosion fatigue in boiler lower bound or critical level of strain
4. Both initiation and propagation tubes: (2.2) breakdown of mag-
of the corrosion fatigue are that is required to fracture the pro-
netite, (2.3) overview of mechanistic tective oxide film and begin the cor-
influenced by the interactions
models, (2.4) analysis of trends in rosion fatigue damage process is
of: operating factors, chemical
factors, and strain factors. A
the field experience, (2.5) stress supported by the German field
probabilistic approach, termed effects on initiation and propagation experience and from modeling stud-
the Influence Diagram, has including both field measurements ies of oxide. In the former instance,
been developed to assess the and finite element analysis, and the German design standard TRD
impact of these three factors on (2.6) environmental effects including 301 requires that the strain level in
the accumulation of corrosion laboratory and field results. oxide be kept below a certain limit,
fatigue damage. about 0.1% strain, during operation
2.2 Breakdown of magnetite to avoid rupturing the magnetite
scale. The lower level of damage
during corrosion fatigue from corrosion fatigue in those boil-
The use of carbon steel for boiler ers seems to confirm the effective-
tubes in the high temperature and ness of this limit.
high pressure boiler environment
depends on the formation of the Modeling and analysis of oxide pro-
protective layer of magnetite (Fe3O4) vides another indication of the effect
on the waterside of the tube.2-4 of strain level on the appearance of
Corrosion fatigue presents perhaps corrosion fatigue damage. Damage
the clearest example of the prob-
lems that develop once that film is
damaged.

13-10 Corrosion Fatigue


is often manifested as a surprisingly
regular array of cracks, see Figure d
13-3, for example. Grosskreutz and b
McNeil9 proposed an explanation for w
this phenomenon while analyzing
layers of Al2O3. They suggested that
regularly spaced cracks would form
in a layer under strain, that the sepa- Stress in
Ds ( d2 )
ration between cracks would be a s¦
film (s)
function of the strain level, and that
the separation would decrease until
some minimum was reached. x
o
The stress relaxation model that they
proposed is illustrated in Figure 13-8.
The cracking process will result in Figure 13-8. Schematic representation of the development of a
stress relaxation, with the highest regular array of evenly-spaced cracks caused by corrosion fatigue.
relaxation located immediately adja- (sf) is fracture stress; (Ds(x)) is a measure of stress relaxation.
cent to the crack formed. Therefore, Source: A.G. Crouch and R.B. Dooley4
the maximum remaining (unrelaxed)
stress will be centered between
cracks. With an increasing strain
applied to the coating or oxide layer, Potential (V SHE)
the next crack will then form at the
center between the existing cracks 0.2
assuming a layer with uniform 200°C
properties.
275°C
This model was used to explain the
0
observation of cracks in silica coat-
ings for 9 Cr 1 Mo in experimental
work by Crouch and Dooley4; their
experimental results were used by
Hay and Meadowcroft11 to improve -0.2
upon the original model. The same
model appears to apply to the initia-
250°C
tion of corrosion fatigue cracks and
explains nicely the regular array of -0.4 150°C
parallel cracks on the inner surface.
In addition to the geometry of crack-
ing, the type of oxide that will form
depends on the electrochemical Potentials at 275°C
-0.6
potential of the material, which is in Oxygen Potential
turn controlled by the oxygen con- (ppb) (VSHE)
tent of the water, see Figure 13-9,
5 -0.780
and by the pH. A potential-pH map,
also known as a Pourbaix diagram, -0.8 320 -0.190
is used to identify the stable oxide 1000 -0.090
species for selected conditions.

-1.0
1 5 10 100 1000 10,000
Oxygen Concentration (ppb)

Figure 13-9. Electrochemical potential of carbon steel in water as a function of dis-


solved oxygen content. Source: P.M. Scott and W.H. Bamford12

Volume 2: Water-Touched Tubes 13-11


Figure 13-10 shows a Pourbaix dia-
gram for iron in high temperature Potential (Volt vs. SHE)
water. Plotted on this figure are 2.5
results of laboratory tests using arti-
No corrosion fatigue
ficially high levels of dissolved oxy- 2.0 Corrosion Fatigue
9
gen from a program described
below; corrosion fatigue most readily Fe 3+
1.5
occurs outside the region of mag- 21
netite stability. Once the film is 4
breached, damage accumulates 1.0 Fe42-
Fe(OH) 2+
until the surface is repassivated,
thus repairing the film. 0.5 Fe2+ +
28
Fe(OH) 2
Dissolved salt contaminants such as
chlorides and sulfates are of con- 0 30
cern as they can affect the morphol- Fe2O3
ogy, formation rate, thickness, and -0.5 26
17
23
strength of the surface oxide. As will
13 Fe3O4 29
be described in more detail below, -1.0 27
the contribution to corrosion fatigue Fe HFeO2-
damage in laboratory tests on boiler -1.5 24
tube materials was not as significant
for these environmental variables as -2.0
for either pH or dissolved oxygen -2 0 2 4 6 8 10 12 14 16
levels. pH (e) @ 250°C

2.3 Mechanistic models of cor-


Figure 13-10. Pourbaix diagram showing the stable oxide film as
rosion fatigue a function of electrochemical potential and pH. Stability of a pro-
A review was undertaken of the cur- tective Fe3O4 scale is believed to be related to the severity of
rent thinking on alternative mechanis- corrosion fatigue. Source: C.M. Chen, et al.13
tic models that attempt to predict
from fundamentals the process that
leads to corrosion fatigue damage.1b
A brief description of four such
mechanistic models is included here:
film rupture/stabilization, mechani- Material Active crack tip strain
cal/chemical dissolution, hydrogen assisted dissolution
embrittlement, and/or strain-induced
corrosion cracking. Migra
tion o
f
• Film rupture/stabilization. There are towar vacancies
d c ra c
several variations of this model k tip
which ascribes accelerated crack Corrosive solution
growth to the rupturing of protec- Vacancies
tive films and subsequent re-oxida- Dissolution of metal
tion or corrosion when the bare atoms creates
metal is exposed to the environ- vacancies
ment.5, 14-17 A variation of this
model explains the onset of corro- Atoms
sion fatigue or stress corrosion
cracking as being controlled by
Highly strained region
crack tip effects that can be
explained by the superposition of Vacancies migrate
toward strained region
an environmental effect and a
strain effect.18 Coalescence causes
crack to grow
• Mechanically-assisted chemical
dissolution. Figure 13-11 illus-
trates the basics of this model.
Figure 13-11. Schematic of the mechanical/chemical dissolution model with the
Vacancies, caused by dissolution
feature of the possibility of corrosion-generated surface vacancies migrating to the
of the metal surface in a corrosive crack tip.

13-12 Corrosion Fatigue


environment are driven by a
stress field and accumulate at the Localized corrosion reactions
crack tip; such coalescence (e.g. 3Fe + 4H2O - > Fe3O4 + 4H2)
results in incremental crack Hydrogen generation and
growth.19 absorption into crack tip
Material
• Hydrogen assisted (or embrittle-
ment) cracking. Hydrogen is pro-
duced by reaction of carbon steel Oxide
bare scale or
with water. Absorption of free surfac
e
hydrogen into the tube metal at
the crack tip has been suggested Oxide free
Corrosive solution crack tip
by a number of researchers as
being at the root of corrosion
fatigue and stress corrosion wa l l
s
cracking mechanisms.20-23 A a ck
s i v e cr
schematic of the process is Pas Highly
shown in Figure 13-12. strained
region
• Strain-induced corrosion crack-
ing. Similar to the film rupture Hydrogen migration
into hightly strained
model, this concept involves the region ahead of
local disruption of protective crack tip
oxide.6, 22, 24 Destabilization of the
oxide can occur by the environ-
ment (dissolved oxygen content,
Figure 13-12. Schematic of the hydrogen embrittlement model showing how
conductivity and temperature of hydrogen is generated at an active crack tip and then absorbed into the material.
the water), mechanical means
(strain rate and strain level), or by
material characteristics (such as
sulfur content).24
Tube Failures
2.4 General trends in corro- 140
Individual boilers
sion fatigue failures: result of
120 Range
the analysis of field results.
A number of factors have an influ- 100 Cycling Boilers
ence on the incidence of corrosion
fatigue in boiler tubes: boiler water 80
and feedwater quality, chemical
cleaning, tube replacement, boiler 60
modifications, and operating mode. Peaking Boilers
General observations from field 40
studies include:
1. Unit operation can have a signifi- 20
cant effect on the incidence of
corrosion fatigue as shown in 0
0 200 400 600 800 1000 1200 1400 1600 1800
Figures 13-13 and 13-14. Peaking
units have a large number of Total Starts
starts and relatively few operating
hours; cycling units are those that
tend to load follow and have rela- Figure 13-13. Total boiler starts versus tube failures by corrosion fatigue.
tively few starts and a larger num- Source: D. McNabb, et al.1a
ber of operating hours.

Volume 2: Water-Touched Tubes 13-13


2. Chemical cleans by hydrochloric
acid were shown to aggravate
corrosion fatigue as illustrated in Tube Failures
Figure 13-15. For example, boiler 140
1 shows a step function increase Range
120 Peaking Boilers Individual boilers
in the number of tube failures by
corrosion fatigue directly follow-
ing hydrochloric acid cleans. No 100
such dramatic increase in corro-
sion fatigue failures was found 80
after cleans done with EDTA or Cycling Boilers
citric acid. Two competing effects 60
are in progress: crack tip blunting
caused by acid cleaning may 40
slow propagation of modest sized
cracks, but in the case of pre- 20
existing severe damage may lead
to through-wall failure in a much 0
shorter period. 0 20 40 60 80 100 120 140 160 180
Operating Hours (thousands)
3. Boilers that have had problems
maintaining boiler water and
feedwater limits generally experi-
Figure 13-14. Operating hours versus tube failures by corrosion fatigue.
ence more boiler tube failures by
Source: D. McNabb, et al.1a
corrosion fatigue. Units that have
experienced extensive corrosion
fatigue have had indications that
large swings in pH may have
occurred in the boiler. Such indi- Tube Failures
cators include: hydrogen dam- 140
age, or caustic gouging, or, for HCL clean
those units using congruent Boiler 8 EDTA or citric
phosphate boiler water treatment, 120 acid clean
evidence of phosphate hideout.
Particularly important are pH 100
depressions during shutdown Boiler 1
and startup where pH drops to 80
less than 8 such as caused (i) in
phosphate treatment units when
there is a phosphate hideout 60
return, or (ii) in AVT units caused
by CO2 ingress and slippage 40
through the condensate polish-
ers. It is interesting that corrosion Boiler 7
fatigue occurs much less fre- 20
quently in caustic-treated boilers;
these units do not usually experi- 10
ence a pH depression during 0 10 20 30 40 50 60 70 80 90 100
shutdown or early startup. Operating Hours (thousands)
Hideout and hideout return analy-
sis of sulfate can be very informa-
tive for boilers on AVT. Up to 1500 Figure 13-15. Operating hours versus corrosion fatigue tube failures illustrating the
ppb of sulfate has been observed effects of different chemical cleaning solutions. Source: D. McNabb, et al.1a
during the overnight shutdown of
boilers.25

13-14 Corrosion Fatigue


4. Boiler layup conditions were also expansion, and (iv) weight of the oratory investigations, to be needed
suspected to aggravate damage attachment (for some locations). to develop corrosion fatigue dam-
by corrosion fatigue, particularly if Field tests have identified two major age. Refinements to the measure-
the pH was depressed and dis- sources of cyclic strain: strains ment process have been made and
solved oxygen levels were not resulting from the pressure and tem- subsequently applied to other units
controlled. perature ramp during boiler starts, and have resulted in measured
and strains from subcooling in nat- strain levels on the order of 0.2 to
ural circulation boilers. 0.3%, more consistent with that
2.5 Stress effects on initiation needed for the accumulation of cor-
and propagation of corrosion An idealized view of the levels of
rosion fatigue damage.
fatigue cracks strain that would be expected dur-
ing various load changes are shown The second largest level of strains
in Figure 13-16. The results of strain developed as a result of subcooling
Corrosion Fatigue: Summary of gauge tests performed on three dif- during warm starts. Subcooling
Key Stress Factors ferent types of units confirmed that occurs in natural circulation boilers
1. Local stresses and water cold starts resulted in the highest when there is a top to bottom tem-
chemistry are considered to be measured tube strains; warm starts, perature stratification during “bot-
the two major factors that pro- hot starts, and load changes, both tled” cool down periods. The magni-
mote corrosion fatigue. sliding pressure and constant pres- tude of the subcooling effect first
2. A methodology is not yet fully sure, resulted in lesser levels. The increases, peaks at about 50 hours
established that can (i) predict typical trends for a cold start are after shutdown for most natural cir-
stress levels at locations sus- shown in Figure 13-17. The peak culation units, then starts to decline
ceptible to corrosion fatigue, strain occurs at the point when the as temperatures over the height of
(ii) predict the rate at which boiler reaches full operating pres- the boiler start to equalize. The
damage will accumulate, or sure. This peak strain corresponds largest thermal transient in the sub-
(iii) confirm, a priori the degree to the maximum thermal gradient sequent start was observed in the
to which a proposed attach- through the tube as shown by the lower furnace. It is believed that
ment modification will result in difference between the tube temper- strains resulting from subcooling
lower tube stresses. ature and the attachment tempera- may not be an important contributor
3. However, guidelines for the ture shown in the top part of Figure to corrosion fatigue in boiler tubes
application of finite element 13-17. Hoop strains then decline to although a more important factor in
analysis and field confirmation steady state levels as the thermal thicker walled components. The
have been developed and con- gradient decreases. strains associated with subcooling
firmed in field testing. These occur early in the start of a unit
The strains measured in units were
should guide utilities in the when boiler pressure and heat
lower than expected and lower than
careful use of such techniques. fluxes are low, and thus overall tube
those which were thought, from lab-
stresses are low.

As noted above, the state of stress


is a primary consideration in the
analysis of corrosion fatigue.
Predicting where corrosion fatigue
will occur, predicting how quickly
damage will accumulate, and pre- Peak
dicting the effectiveness of pro-
posed modifications to mitigate a Strain
Steady state
»
»

high stress condition will all ulti- (me)


Partial sliding
mately require a knowledge of how pressure
to measure or analyze the relevant Cold Steady Sliding shutdown
start state pressure Shutdown
state of stress. This section reviews load change
Zero pressure
recent work toward that goal. shutdown
»

Sources of loads acting on tubes Time


include (i) boiler pressure, (ii) ther-
mal gradient through the tube (heat
flux), (iii) constraint during thermal Figure 13-16. Schematic of an idealized strain cycle for a cold start, sliding pressure
load change and shutdown. Source: D. Sidey, et al.1c
loads on boiler
tubes

Volume 2: Water-Touched Tubes 13-15


Guidelines for utility application of
stress analysis in attacking corrosion 500
fatigue problems are presented in Hoop strain (me)
Section 6 below on long-term 400
actions to deal with corrosion fatigue
damage. 300 Tube
temperature (°C)
Attachment temperature (°C)
200
2.6 Environment effects on the
initiation and propagation of 100 Axial strain (me)
corrosion fatigue cracks
0

Corrosion Fatigue: Summary of -100


Key Environment Factors
500
1. There is a clear effect of envi- Unit load (MW)
ronmental parameters on the 400
Coal fires
Feedwater flow (kg/s)
severity of corrosion fatigue ini- 300 Roll turbine
tiation and propagation. The Lost coal fires Unit
effects are independent of the 200 synchronization
Purge Coal fires
basic treatment chosen, for 100 Oil Drum pressure (MPa X 10)
fires
example AVT compared to 0
congruent phosphate treat-
ment. 80
CBD O2
10.8
(ppb) CBD phosphate (ppm x 10)
2. Most obvious effects are for pH
excursions and the presence of 60 10.2
high levels of dissolved oxy- CBD - pH
gen. 40 9.8 pH
3. pH is particularly important as CBD cation
low pH excursions, such as 20
conductivity(mS/cm)
9.4
associated with phosphate
hideout, can occur concur-
rently with high strain in sus- 0 9.0
ceptible tubes. 22 0 2 4 6 8 10
Time (hours)

There is no comprehensive model Figure 13-17. Strain, temperature and cycle chemistry information collected on the
that can predict the effect of various cold start of a 500 MW unit. (CBD) is continuous blowdown. Source: D. Sidey, et al.1d
environmental factors on the rate of
initiation and propagation of corro-
sion fatigue cracks in the boiler envi-
ronment. A number of past experi- dence or extent of corrosion fatigue A knowledge of cycle chemistry par-
mental programs have been con- damage. Unfortunately there has not ticularly during starts and transients
cerned with isolating the effect of been good correlation between what is essential. For example, at one unit
one or more major parameters such was thought to be important in the the major parameters (dissolved
as dissolved oxygen, pH and cation laboratory and what was measured oxygen, pH and cation conductivity)
conductivity. A broad outline of in the field. In the broad outline in were well maintained throughout
those studies and some of the impli- section 2.6.2 is a summary of what transients. This was the result of
cations are presented in the first part is presently known, what is thought specific operating procedures which
of this section (2.6.1) to be correct and is undergoing con- allowed up to 1 ppm free hydroxide
There have also been a few field firmation, and what is presently to counteract a phosphate hideout
studies that have tried to correlate unknown. The discussion here is lim- problem. Prior to making that
the results of the laboratory investi- ited to specific knowledge about change in procedure, pH would
gations with field measurements of boiler tube materials, the boiler envi- drop to around 7 during shutdown
similar factors, and with the inci- ronment and stress levels, and and remain around that level until
actual field investigations in working restart.26 Similar hideout was
boilers. observed during load changes as

13-16 Corrosion Fatigue


well. This hideout phenomenon has
Cycles to Initiation been well documented27, 28 and has
important implications for units on
104
congruent phosphate control. See
additional discussion on this topic in
Chapter 3, Volume 1.
103 In the final part of this section (2.6.3)
a brief note clarifies the use of oxy-
genated feedwater treatment, and
how its use in drum boilers can be
102 consistent with the observation that
increased levels of dissolved oxy-
gen have increased the propensity
for corrosion fatigue damage in lab-
10 Air Data (274°C) oratory tests.
Clean AVT water at 274°C
2.6.1 Laboratory results. The follow-
Contaminated AVT water at 274°C ing results have been obtained from
laboratory studies1b; it is important
1 to note that there have been some
10-5 10-4 10-3 10-2 10-1 1 10
differences from those obtained in
Frequency (Hz)
field tests:
1. The number of cycles to crack
initiation by corrosion fatigue are
Figure 13-18. Effect of cycle chemistry and frequency on the lower in simulated boiler water,
initiation of corrosion fatigue cracking.
either high-quality or contami-
Source: G.I. Ogundele, et al.1b
nated, than in air. Figure 13-18
shows this result. The number of
cycles to initiation is markedly
influenced by the presence of
Dissolved Oxygen (DO) ppb contaminants (lower curve).
104 However, there is very little differ-
LOG (N) = 3.3883 - 0.5256 LOG (DO) ence in these results between the
R = -0.9842 normal base chemistries for AVT
Phosphate test data and phosphate.
AVT test data
103 2. Figure 13-18 also indicates that
the frequency of strain reversal is
important for initiation. Lower fre-
quencies increase the corrosion
102 fatigue initiation potential.
Frequency effects are also evi-
dent for propagation rates.
Higher frequency tests in labora-
10 tory experiments are not thought
to allow the full effects of the cor-
rosion aspect of the damage
mechanism to influence the crack
1 growth. Long periods at lower
10 102 103 104 strains between cycles allow full
Cycles to Initiation, N influence of corrosion effects.
3. Dissolved oxygen was shown to
have a strong influence on cycles
Figure 13-19. Effect of oxygen on corrosion fatigue initiation at to initiate corrosion fatigue as
274°C (525°F) and a frequency of 0.0005 Hz.
illustrated in Figure 13-19.
Source: G.I. Ogundele, et al.1b

Volume 2: Water-Touched Tubes 13-17


4. pH level was also shown to have
a strong effect. A series of speci-
mens was tested in solutions with Cycles to Initiate Cracks
a constant levels of 5 ppb dis- 1200
solved oxygen and with varying
phosphates to simulate acidic 400°F (204°C)
phosphate hideout return. The 1000
number of cycles to initiation was 525°F (274°C)
reduced to about 1/3 at both
204°C (400°F) and 274°C (525°F) 800
when the pH level was approxi-
mately 6 as compared to the base
condition of pH 9. Figure 13-20 600
illustrates this important result.
5. The presence of chlorides and
sulfate had less noticeable 400
effects, with the effect of chlorides
up to 3000 ppb the most signifi-
cant in reducing cycles to initia- 200
tion.

2.6.2 Implications of laboratory tests 0


to operating boilers and comparison 4 6 8 10
to field results. What are the impli-
cations of laboratory test results, pH @ 25°C
particularly for dissolved oxygen lev-
els and pH on the potential for cor-
rosion fatigue in boilers? The effect Figure 13-20. The influence of pH on cycles to initiate corrosion fatigue cracks in
of oxygen levels are reviewed first. deaerated boiler water (< 5 ppb oxygen). The pH was controlled with phosphate solu-
tions of different Na:PO4 molar ratios. Source: R.B. Dooley and L.D. Paul32
It is clear that in the laboratory envi-
ronment an increase in dissolved
oxygen levels from 5 to 1000 ppb
will significantly decrease the num- This situation is contrasted with that conditions in three units that had his-
ber of cycles to initiate corrosion for pH depressions on shutdown/ torical problems with corrosion
fatigue cracks (Figure 13-19). There startup. Such depressions can be fatigue-induced tube failures.1c At
is also no doubt that during a shut- caused by phosphate hideout the time of testing, as shown in the
down period the oxygen level in return, leakage from condensers, or table, boiler water chemistry for
boiler water can reach high, per- ingress of carbon dioxide. In these units A and B was generally well
haps saturation, levels; but upon first cases, particularly the first, the pH within acceptable values when tube
firing and circulation of the boiler level does not return to the normal strains were highest during both
water the dissolved oxygen levels range until the unit pressure has cold starts and during warm starts.
decrease once the deaerator and risen considerably and/or phosphate What then was at the root of the
drum start to separate oxygen. As a or caustic has been added to the problem with corrosion fatigue?
result, the experience from field test- unit. Thus, the pH of the boiler water Subsequent investigation indicated
ing has indicated that oxygen at can be depressed during the period that each unit had been subject to
high levels (> 20 ppb) does not gen- of peak strain at locations suscepti- considerable past problems with
erally occur at the same time as the ble to corrosion fatigue. A pH level phosphate hideout and concurrent
peak in applied strain level (Figure of 8 and below is not unusual in possibility of low pH excursions
3-17); peak strains occur well after these cases as shown in Figure 16- when operating with congruent
the time when oxygen levels have 7. As indicated in Figure 13-20, this phosphate treatment. As a result,
approached a low level. It is impor- can reduce the number of cycles to both units had changed to equilib-
tant to know the time dependency of initiate or re-initiate corrosion fatigue rium phosphate treatment before the
the elevated oxygen levels on cracks. field tests and had not been experi-
startup and especially important to encing hideout, hideout return, or
monitor the oxygen levels in the Note that care is required to judge the low pH excursions which result.
downcomer as compared to the field test results. Table 13-3 shows
boiler drum. chemistry, strains and temperatures
measured for a variety of operating

13-18 Corrosion Fatigue


Table 13-3
Field Test Results
Temperature
Temperature Rate of Hoop Axial
Range Change Strain Strain Dissolved Cation
(Tube OD) (Tube OD) DeH DeA Oxygen conductivity
Operation/Boiler DT (˚C) (˚C/hr) (µe) (µe) pH (ppb) (µS/cm)

Cold Start

Unit A 170 70 280 -700 8.6 - 9.5 > 1,000 to < 1 2 - 10

Unit B 145 120 500 50 10.0 - 9.5 > 1,000 to < 5 20 - 40

Unit C1 260 250 150 — 8.5 - 7.2 > 1,000 to < 1 1 - 11

Unit C2 (trip) 160 1,750 2,000 — 8.5 - 7.2 > 1,000 to < 1 1 - 11

Warm Start

Unit A1 60 50 200 -500 9.2 - 9.4 <2 3-7

Unit A2 45 700 170 -500 9.2 - 9.4 <2 3-7

Unit B 125 110 400 -100 9.2 - 9.4 <2 10 - 30

Hot Start

Unit A1 40 80 100 -175 9.1 - 9.3 <5 2-6

Unit A2 50 350 100 -250 9.1 - 9.3 <5 2-6

Unit B 50 70 220 -100 9.1 - 9.8 <5 5 - 40

Load Changing

Unit A 40 75 115 -125 9.1 - 9.3 <5 2-6

Unit B — — 50 50 9.2 - 9.6 <5 10 - 25

Unit C1 50 90 80 — 8-9 <1 3.2 - 2.8

Unit C3 30 1,500 -700 — 8-9 <1 3.2 - 2.8

Notes:
1Pressure/temperature ramp event
2Subcooling correction event.
3Unidentified temperature excursion

Source: D. Sidey, et al.1c

Volume 2: Water-Touched Tubes 13-19


These results imply that cracks may drum units on oxygenated feedwater For drum units, utilities should add
only initiate, reinitiate and/or grow is also being implemented as the oxygen only when the unit is steam-
when environmental conditions are benefits are expected to be similar ing, operating above a certain mini-
conducive. Inactive cracks are to those for once-through units. The mum load, when the feedwater
found in field studies, indicating that level of oxygen entering the econo- cation conductivity is less than 0.15
the process is not continuous but mizer inlet has to be carefully con- mS/cm, and when the boiler water
consists of a series of re-initia- trolled to ensure that elevated oxy- (downcomer) cation conductivity is
tions.1d Laboratory tests are seldom gen levels do not occur in the boiler less than 1.5 mS/cm. Some utilities
able to duplicate this feature of field tubes. As indicated in the last sec- add oxygen no more than once a
cracking because of the time con- tion, once the boiler starts to steam week. Whatever procedure is
straints inherent in any test program. then the oxygen level in the water- adopted for control, the oxygen level
This discontinuous nature of the cor- walls is controlled by the recircula- should be targeted to keep the oxy-
rosion fatigue process also makes tion ratio (the ratio of oxygen at the gen level in waterwall tubes at
life assessment a very difficult task. economizer inlet to that in the down- around 5-10 ppb. Oxygen at this
comer) which is typically between 6 concentration should have minimal
2.6.3 Oxygenated water chemistry at low load and 4 at full load. A sam- influence on the initiation of corro-
and effect on corrosion fatigue. The ple point for oxygen in the down- sion fatigue cracks (see Figure 13-
operation of supercritical and once- comer rather than in the drum is 19). Guidelines for oxygenated treat-
through units on oxygenated treat- thus needed to control the oxygen ment for fossil plants have been pro-
ment has been fairly widespread. levels. duced.29
Today however, the operation of

13-20 Corrosion Fatigue


3. Possible Root Causes and Actions to Confirm
3.1 Introduction experienced with identical boilers
Corrosion Fatigue: Root Causes Corrosion fatigue is caused by the where the weld profile was improved
1. Corrosion fatigue is caused by interaction of stresses and environ- by grinding.
a combination of cyclic ment. The effects are synergistic Actions to confirm the influence of
stresses/strains and environ- and, as of yet, no closed form model excessive stresses/strains include:
mental effects. Analysis of root or analytical tool can predict corro- (a). Compare locations of damage
causes will consist of identify- sion fatigue initiation and propaga- to those compiled in Figures 13-
ing excessive sources of these tion from first principles. A method 7a/b and in Table 13-2. Note partic-
contributors. that is based on an influence dia- ularly those locations with high
gram has been developed and stress ranks, i.e., where field survey
2. An “influence diagram” can
allows decisions to be made about experience indicates attachment
help judge the relative contri-
the relative contribution of various details are likely to have the highest
bution of the various root
root cause influences. It also pro- stress levels.
cause influences to an identi-
vides a tool to evaluate possible
fied problem with corrosion (b). Use Figures 13-7a/b and Table
approaches to prevent the recur-
fatigue and to judge the effi- 13-2 as an inspection guide to
rence of corrosion fatigue; the
cacy of proposed solutions. locate other highly susceptible loca-
method is discussed at the end of
3. The influence diagram should this section. tions before damage is detected via
be considered as a predictive tube failure.
The discussion of root causes is
tool to anticipate the potential (c). Selectively sample tubes to see
divided into excessive stresses
for corrosion fatigue, even in if cracking has initiated.
(3.2), environment (3.3), and opera-
new units.
tional history of the boiler (3.4), as (d). Field test with thermocouples
each can contribute to the problem and/or strain gauges to confirm the
of corrosion fatigue. Table 13-4 sum- levels of strain developed at sus-
marizes the potential root causes, pect attachments during operation,
actions to confirm, and immediate including hot, warm and cold starts.
and long-term actions to be taken.
(e). Perform finite element stress
analysis for the suspect detail to
3.2 Influence of excessive confirm field results and/or predict
stresses/strains future behavior. See the guidelines
for stress analysis and field testing
3.2.1 Restraint stresses at attach- in Section 6 on long-term actions.
ments. Primary failure locations are
Applicable in tubes near attachments; many 3.2.2 Subcooling in natural circula-
successful solutions to the problem tion boilers. High strains have
have been effected by lowering the occurred during subcooling (stratifi-
stresses associated with the restraint cation of cooling water along the
at these attachments. Stress analy- length of the waterwall) during shut-
sis and confirmation with field mea- down and restart in natural circula-
surements should be used in any tion boilers.
redesign situation, particularly as
some redesigns to combat corrosion Actions to confirm:
fatigue by “lowering” local stresses (f). Review operating records.
have actually accumulated damage
(g). Install thermocouples at the top
more quickly than the original
and bottom of the boiler and monitor
design. It should also be noted that
the ÆT as a function of shutdown
weld reinforcement at an existing
length.
attachment in an attempt to improve
the weld profile and eliminate fatigue (h). Strain gauge to confirm exis-
caused by thermal restraint has tence and seriousness of the prob-
resulted in tube failures due to cor- lem.
rosion fatigue within two years. No
corrosion fatigue cracking was

Volume 2: Water-Touched Tubes 13-21


Table 13-4
Major Root Cause Influences, Confirmation and Corrective Actions
Major Root Cause Immediate Actions Long-Term Actions and
Influences Actions to Confirm and Solutions Prevention of Repeat Failures

3.2 Influence of Excessive


Stresses/Strains

3.2.1 Restraint stresses (a). Compare damaged locations to those • Apply Influence Diagram • See guidance in Section 6.2.
at attachments typical of corrosion fatigue. See Figures (Section 3.5) as a tool to • Most effective measures have been
13-7a/b and Table 13-2. identify proper short- modification of attachments to lower
(b). Inspection of susceptible locations and long-term solutions. stresses.
before tube failures occur. • Replace damaged tubes.
(c). Selectively sample to identify damage • Do not pad weld.
accumulation. • Determine the extent of
(d). Thermocouple and/or strain gauge test- damage.
ing to confirm high strain • Confirm damage
locations. mechanism is corrosion
(e). Finite element stress analysis to fatigue.
predict high strain locations.

3.2.2 Subcooling (cooling (f). Review operating records. • Same as above. • Install off-line boiler circulation pumps
water stratification) (g). Thermocouple top and bottom of to reduce level of subcooling.
in natural circulation boiler to monitor DT as function of
boilers shutdown time.
(h). Strain gauge to confirm.

3.3 Influence of
Environmental Factors

3.3.1 Poor water chemistry (i). Review water chemistry logs and prac- • Same as above, particu- • Clean up overall cycle and confront
tices, with particular emphasis on pH larly initiating the appli- specific chemistry problems such as
reductions during shutdown and early cation of the Influence condenser leaks, impurity ingress,
startup; if review indicates a problem Diagram to characterize lack of appropriate procedures, lack
then implement a monitoring program. the contribution of the of appropriate monitoring devices, etc.
See discussion of minimum levels of environment. • Apply appropriate guideline procedures
instrumentation in Chapter 3, Volume 1. for specific chemistry, monitoring,
(j). Calculate Environmental Parameter for and instrumentation. See overview of
use in Influence Diagram from informa- recommended practices in Chapter 3,
tion gathered above Section 3.5.2 and Volume 1.
Table 13-5; this will help determine the
contribution of environment to the
corrosion fatigue problem.
(k). Selectively sample tubes from at-risk
areas for evidence of pitting or corro-
sion fatigue damage

13-22 Corrosion Fatigue


Table 13-4
Major Root Cause Influences, Confirmation and Corrective Actions (continued)
Possible Root Cause Immediate Actions Long-Term Actions and
Influences Actions to Confirm and Solutions Prevention of Repeat Failures

3.3.2 Overly aggressive (l). Review chemical cleaning procedures, • Same as above, plus • Optimize chemical cleaning procedures
or improper chemical and correlate chemical cleaning with • Revise chemical clean- and frequency. See overview in
cleaning corrosion fatigue failures. ing procedures, as Chapter 4, Volume 1.
(m). Selective sampling of at-risk tubes. required.

3.3.3 Improper boiler (n). See actions in items (i),(j) above. • Same as above, plus • Optimize shutdown, lay-up procedures.
shutdown and/or • Optimize shutdown, lay- • See overview in Chapter 4, Volume 1.
lay-up procedures up procedures.

3.4 Influence of Historical


Unit Operation

3.4.1 Operating procedures (o). Review operating records to determine • Apply Influence Diagram • See guidance in Section 6.2.
that have produced operating hours and boiler starts. as a tool to identify • Reduction of stresses or improvement
high stresses (p). Plot failure history against unit operat- proper short- and in environmental parameter are possible
ing conditions. See Figures 13-13 long-term solutions. actions.
and 13-14. • Replace damaged tubes.
• Do not pad weld.
• Determine the extent of
damage.
• Confirm damage
mechanism is corrosion
fatigue.

3.3 Influence of environmental given to reductions in pH during the If the review indicates a problem,
factors shutdown and early startup periods. then a monitoring effort should be
For phosphate-treated units, the key undertaken. The primary aim of such
3.3.1 Poor water chemistry. A vari- question will be whether phosphate a program would be to confirm any
ety of excursions, including low pH, hideout occurs, which will result in pH reduction. It should also address
high levels of dissolved oxygen, and phosphate return with concurrent pH the possibility that dissolved oxygen
cycle chemistry contaminants, can reductions during shutdown or load in the boiler tube, as monitored at
influence both propagation and initi- reductions. For AVT units, depres- the downcomer, is high during shut-
ation of corrosion fatigue. Poor water sions in pH during shutdown and down, and more importantly,
chemistry will accelerate the corro- early start up can result from conta- remains high (³ 20 ppb) well into the
sion attack in existing cracks or minant ingress, slippage from the startup period (past pressure rais-
breaks in the protective oxide; pit- condensate polisher, or carbon diox- ing).
ting caused by poor shutdown ide ingress. For both chemical treat-
chemistry can provide a preferential (k). Selectively sample tubes from
ments, the pH depressions can
initiation site for starting corrosion high stress areas, or other at-risk
remain during the early startup
fatigue cracks. locations, to determine whether pit-
period. ting has begun, or whether there is
Actions to confirm: (j). Using information gathered evidence of more advanced dam-
(i). A two-pronged approach is above, evaluate the severity of the age such as developing corrosion
required. The first part will be a environmental contribution to the fatigue cracks.
review of the chemistry records and corrosion fatigue problem by calcu-
logs. Particular emphasis should be lating the “environmental parameter”
for the influence diagram. This
process is discussed in more detail
in Section 3.5.2.

Volume 2: Water-Touched Tubes 13-23


3.3.2 Overly aggressive or improper and total boiler starts (Ns) into one set among various locations; the
chemical cleaning. Aggressive parameter termed the equivalent stress rank chosen is the ordinate on
chemical cleaning can promote initi- operating hours (EOH): the influence diagram, Figure 13-21.
ation and propagation of corrosion
fatigue damage. EOH = (H/1000) + 3.5.2 Environmental parameter.
(NS/(H/1000)) (13-1) The effect of environment on corro-
Actions to confirm: sion fatigue propensity is also evalu-
(l). Review chemical cleaning pro- Actions to confirm: ated by a four level ranking scheme:
cedures and plot out corrosion (o). Review operating logs to deter- E1, E2, E3, and E4, where E1 is
fatigue failure history against past mine operating hours and boiler good cycle chemistry and E4 is
chemical cleaning events as shown starts. poorest. The ranking is chosen by
in Figure 13-15. answering the questions presented
(p) Plot failure history by corrosion in Table 13-5. A weighting process
(m). Selectively sample for evi- fatigue, if any, against unit operating provides a means to indicate the
dence of initiating or propagating conditions to observe patterns like larger influences on corrosion
corrosion fatigue cracks. in Figures 13-13 and 13-14. fatigue.
3.3.3 Improper boiler shutdown Environmental influences of interest
and/or lay-up procedures. 3.5 The influence diagram and include: (i) pH and dissolved oxygen
Oxygenated stagnant water is a key its use to confirm root cause levels as obtained either by direct
ingredient for pitting and the forma- influences. measurements or indirectly, such as
tion of corrosion fatigue initiation Figure 13-21 illustrates the influence indicated by hideout problems, (ii)
centers. Proper shutdown and/or diagram approach to analysis of chemical cleans, and (iii) boiler shut-
layup procedures are vital. These corrosion fatigue susceptibility or down and layup procedures.
involve the adequate use of N2H4 or failures. The approach integrates Completing the questionnaire will
alternatives, or ensuring nitrogen the three basic influences on failure allow an environmental factor to be
blanketing. of boiler tubes by corrosion fatigue: entered into the influence diagram.
Actions to confirm: stresses, environment and unit oper- A detailed example of how this form
ating history. is completed from unit information is
(n). Ensure that excessive oxygen provided in the case study that fol-
levels are not present into the 3.5.1 Stress rank. The influence of lows later in this section.
startup period, see items (i, j) above stresses enters the diagram through
for specific actions required. the choice of a stress rank for a 3.5.3 Unit operation. The effect of
given location and condition. Four unit starts and operating hours is
stress ranks have been proposed, entered into the influence diagram
3.4 Influence of unit operation through the calculation outlined in
labeled A through D in order of
3.4.1 Operating procedures that decreasing stress. Each of the 24 equation 13-1.
have produced high stress levels, susceptible locations was assigned
particularly during load changes. 3.5.4 Using the influence diagram.
a generic stress rank to be used as
Field experience indicates that the When the appropriate stress rank
the default stress rank, Table 13-2.
highest cyclic strains are developed and equivalent operating hours
The location-specific stress ranks
in tubes during load changes, par- have been calculated, a location on
were determined from time-to-failure
ticularly cold starts. Increased the influence diagram can be deter-
history for each of the 24 sites, infor-
cycling of the unit, choice of ramp- mined. A point to the left of the
mation on detailed site design, and
ing rates, and other operating appropriate environment line indi-
a qualitative estimate of the major
choices can adversely affect a mar- cates a low risk of failure by corro-
loads present.
ginal location. Peaking boilers with a sion fatigue; to the right indicates a
large number of starts and few Where additional information, such high risk of failure. It can be seen
operating hours display a distinctly as field measurements or stress how an increasingly higher stress,
different failure trend than base load analysis, about a particular location given a particular environmental
or load-following boilers. The influ- is available, it is used to fine-tune state, will lead to a greater risk of
ence diagram incorporates this con- the judgment about stress rank. For failure. Similarly, for two units of iden-
sideration through a combination of sites not listed, a first cut is to iden- tical design and operating history,
the number of operating hours (H) tify a listed site that is of similar the unit with a better environment
design and then fine-tune the including cycle chemistry practices
assessment through additional will have a significantly lower risk of
analysis or measurement. corrosion fatigue failures.
A primary aim of the stress ranking
process was to allow priorities to be

13-24 Corrosion Fatigue


Table 13-5
Form to Evaluate Environmental Parameter (E)
Response Total
Value Item Score Score

Phosphate boiler water alkalinity control

3 Does the boiler experience phosphate hideout No Irregularly Regularly


or phosphate carryover to the reheater? 3 6 9

Excursions

3 How many hydrogen damage or caustic gouging events None One More than one
resulting in tube failures have occurred over the life 3 6 9
of the boiler?

Typical on-line chemical operations

1 (1a) Boiler water pH at blowdown 9.0 - 9.6 8.0 - 10.0 < 8, > 10
1 2 3

1 (1b) Cation conductivity (µS/cm) <6 6 - 30 > 30


(minus phosphate correction 4.1 x ppm PO4) 1 2 3

1 (2) Feedwater at the economizer inlet, <5 < 20 > 20


dissolved oxygen (ppb) 1 2 3

Typical start-up chemical operating ranges


(measured at the point of reaching target (or full) pressure)

2 (1a) Boiler water pH at blowdown 9.0 - 9.6 8.0 - 10.0 < 8, > 10
2 4 6

2 (1b) Cation conductivity (µS/cm) <6 6 - 30 > 30


(minus phosphate correction 4.1 x ppm PO4) 2 4 6

2 (2) Feedwater at the economizer inlet, < 50 < 200 > 200
dissolved oxygen (ppb) 2 4 6

Chemical cleans

1 How many chemical cleans using a hydrochloric None One More than one
acid solution has the boiler been exposed to? 1 2 3

Boiler shutdown/lay-up procedures

2 What actions are taken for shutdown corrosion protection: Actions Actions No action
(a) N2 cap on drum and treat water if boiler not drained. (a) to (d) (a) and (b)
(b) Refill drained boiler with chemically treated water to 2 4 6
control pH and oxygen
(c) Ensure dry storage if drained.
(d) Monitor and adjust pH and oxygen in boiler water
during wet lay-up.

Total Value: __________ (total for questions answered) Total Score: _______
Environment Parameter: = E1, for Total Score/Total Value = 1.0 to 1.5; = E2, for Total Score/Total Value = 1.5 to 2.0; = E3, for Total Score/Total Value = 2.0 to 2.5
= E4, for Total Score/Total Value = 2.5 to 3.0
Source: D. Sidey, et al.1d

Volume 2: Water-Touched Tubes 13-25


The influence diagram has been
found to be particularly useful as a Stress Rank (S)
means to rank locations for further High (A)
analysis and to provide a quick Stress
screening method before consider-
ing approaches to prevent recur-
rence of the problem.
(B)
The version of the influence diagram
that is presented in Figure 13-21,
and in the case study is one based
on a 15% probability of failure (85% Low High
risk risk
survivability). This probabilistic mea- (C)
sure was determined by analysis of Environment
field data. A plot of field failure data parameter (E)
versus a boiler tube corrosion
E4 E3 E2 E1
fatigue index (a combination of the Low
environmental parameter, stress rank Stress (D)
and equivalent operating hours) was 0 30 60 90 120 150
fitted to a Weibull cumulative distrib- Equivalent Operating Hours (EOH)
ution function to calculate an influ-
ence diagram that incorporated a
probability of failure.1d Influence Figure 13-21. Influence map for corrosion fatigue in waterwall tubes (based on a 15%
maps can be derived for 5%, 25% probability of failure). Source: D. Sidey, et al.1d
and 50%, etc. probabilities of failure.

4. Determining the Extent of Damage


Selective tube sampling and various detected. In a limited number of It is vital that once corrosion fatigue
NDE methods (including UT and RT) cases where inside access was pos- has been confirmed, primarily by
have been tried for determining the sible, the inner surfaces of tubes metallurgical analysis, that the
extent of corrosion fatigue damage. have been examined by videoprobe. extent of damage and correspond-
The NDE methods suffer from draw- ing locations be carefully deter-
Most often tube removal and sam-
backs associated with access to the mined. The will help focus long-term
pling from suspect locations is the
susceptible locations and interfer- steps such as the redesign and
primary means to assess the extent
ence from attachments, membranes, modification of attachments for key
of damage.
etc. Another drawback is that gener- locations.
ally only advanced damage can be

13-26 Corrosion Fatigue


5. Background to Repairs, Immediate Solutions and Actions
In the past, in an effort to get units
Corrosion Fatigue: Immediate on-line quickly, minor corrosion
Solutions and Actions fatigue damage, such as pinhole
1. Implement the influence dia- and axial cracks, was repaired by
gram approach to identify the pad welds either with or without
most important root cause influ- grinding. Because corrosion fatigue
ence (stress level, environment cracks manifest multiple, branched
or operation). initiation sites, it is difficult to ensure
2. Remove and replace the that all damage has been removed
affected tube section. and as a consequence, this repair
strategy has often resulted in repeat
3. Determine the extent of dam- failures at the same location. Figure
age, including a confirmation of 13-22 shows an example of this
the failure mechanism. problem. Therefore, it is strongly rec-
4. Begin a long-term strategy to ommended that repairs be effected
deal with root causes of corro- by replacement of the damaged
sion fatigue in each affected tube sections.
location.
However, if tube replacement is per-
formed without understanding and
dealing with the underlying causes,
repeat failures will occur eventually.
The use of the influence diagram
early in the process will be of great
value in defining the appropriate Figure 13-22. Pad weld repair showing
directions to take over the short and renewed corrosion fatigue crack growth.
long term. For example, a direct Source: D. Sidey, et al.1d
cycle chemistry cause may be indi-
cated after application of the influ-
ence diagram, if so, then the appro-
priate steps should be undertaken
to optimize cycle chemistry.

Volume 2: Water-Touched Tubes 13-27


6. Background to Long-Term Actions and Prevention of Repeat
Failures
6.1 Options for long-term • Optimize boiler shutdown and lay-
Corrosion Fatigue: Long-Term solutions up procedures to avoid out-of-
Actions service corrosion.
1. An understanding of what is
The key to corrosion fatigue preven-
causing corrosion fatigue must tion is a coherent long term strategy • Chemically clean to remove
be obtained before the proper that begins with understanding what deposits; be cognizant that the
long-term actions can be is driving the corrosion fatigue. In use of hydrochloric acid cleans,
developed; the influence dia- the past, costly mistakes have been where there is advanced corro-
gram should be used as a tool made when solutions were applied sion fatigue damage, may lead to
to gain this understanding. without such understanding. Simply a spike in the number of failures
designing a “more flexible” attach- observed.
2. The influence diagram can also ment and assuming that it will,
be used to anticipate future • Install off-line boiler circulation
through “lower” stresses, solve the
potential problems with corro- pumps to reduce level of sub-
sion fatigue, even in new units.
problem has been shown to be a
costly wrong assumption. Any solu- cooling in the waterwalls, which
The consequences of decisions will reduce the stress level
about operations, environment, tion that is applied must have a
means of testing its benefits. Thus, if caused by thermal transients on
or to a lesser extent stresses startup. Such modifications have
can thus be evaluated. the solution is to lower strains
through attachment modification, been successful in reducing the
3. Any solution must have a measurement of actual strains amount of subcooling but it is still
means to determine its effec- before and after is recommended. unknown whether they have also
tiveness; an example might be Note that the approach chosen will reduced the amount of corrosion
before and after strain mea- fatigue.
be site-specific; there is no global
sures if attachment redesign is
used.
approach to corrosion fatigue pre- • Place restrictions on amount of
vention. cycling operation. This is not nor-
4. Solutions will consist of (i) mally a feasible option although
improving cycle chemistry, (ii) Possible long-term actions are
drawn from a range of hardware the effect of increased cycling in
lowering strains, primarily by future operations can be seen
redesign and modification of modifications, operating changes,
cycle chemistry controls, chemical from its effects on the influence
attachments, or (iii) both. Each diagram.
may have effects throughout cleaning procedures, and lay-
the boiler. up/shutdown procedures as follows:
Because of the number of potential
5. The most effective long-term • Redesign tube attachments to locations that might be considered
approaches have been eliminate or reduce restraint. Most for modification of attachments, i.e.,
achieved by modifying attach- successful modifications increase sites with similar attachment
ment designs. However, the amount of flexibility at the designs, it is important that the
improper modifications have connection and thus reduce the extent of corrosion fatigue damage
intensified the problem. total applied stress. be clearly determined before
• Correct causes of low pH water embarking on an extensive program
chemistry, such as condenser of attachment redesign and modifi-
leaks, or other impurity ingress, cation.
by adopting the latest phos-
phate30 and AVT31 guidelines;
control cycle chemistry levels.

13-28 Corrosion Fatigue


FEA guide lines

6.2 Guidelines for the use of 4. Any analysis of stresses via finite Iteration may be required to refine
stress analysis and field mea- element methods should be sup- boundary conditions and symme-
surements ported by a field test program. try assumptions until agreement
A combination of stress analysis, Field testing alone may be is obtained.
using finite element methods, and enough. 2. A 3-D model should be formu-
field confirmation using strain lated to accommodate the triaxial
6.2.2 Evaluation of the subject
gauges, is useful for determining the stress state. Mesh size and num-
boiler. Analysis of the boiler should
contribution of strain to a location ber of elements should be such
precede any analytical program and
experiencing corrosion fatigue. It will as to allow convergence in a 2D
include identifying critical locations,
also be helpful to (i) determine thermal analysis: apply a thermal
identifying the major anticipated
whether proposed modifications will load to one side of the model and
loads, and reviewing tube failure
lower the applied strains, and (ii) add elements until there is no
history. This evaluation should result
confirm that, after modification, the change in the thermal distribution.
in a prioritized list of sites for evalua-
local condition did improve. Utilities A maximum aspect ratio of 7:1 for
tion. Tables 13-2 and Figures 13-
seeking to apply these methods elements has been recom-
7a/b provide a starting point for
should do so with a full understand- mended.
identifying those locations which
ing of the benefits to be gained and
have generally been a concern. 3. Detail of attachment is important.
the costs to execute such detailed
It was found, for example, that
evaluations. 6.2.3 Field testing. Field testing the assumption of a point attach-
is required to confirm major loads, ment for tack welds was not
6.2.1 Overall guidance
help define applicable boundary appropriate.
1. An analytical and experimental conditions for the stress analysis,
determination of applicable 4. When it is necessary to consider
and relate operating changes to
stresses is only one part of the structural loads, an orthogonal
load and cycle chemistry changes.
overall approach to corrosion plate extension to a local model
Instrumentation for a test program
fatigue. It is important to under- was recommended; however, a
might include temperature and
stand how it fits into that ap- global model was not considered
strain instrumentation, heat flux
proach and what the limitations of cost-effective.
meters, cycle chemistry analyzers,
the stress analysis methods are. and data acquisition equipment. 5. The cost of the analysis is related
2. A consistent and fully predictive to the complexity of the model,
6.2.4 Finite element analysis. which will cause tradeoffs to be
finite element stress analysis
Evaluation of model choice, degree made.
method is desirable as it would
of detail, boundary and symmetry
provide a way to assess potential 6. A sensitivity analysis is necessary
conditions are critical; simplifying
design changes prior to their to identify major applied loads at
assumptions must be made with
introduction and to predict their a given location.
care and confirmed. The following
efficacy.
key aspects are important1c: 7. Results should be presented in a
3. Modeling of a waterwall tube with form (polar coordinates, a nodal
1. Boundary and symmetry condi-
attachment requires careful con- map, etc.) that allow for the iden-
tions must be formulated from a
sideration of actual field loading, tification of high stress locations.
detailed evaluation of field test
geometry, and local constraint; A deformation map was also
results to include all critical field
simplification of model, boundary deemed to be useful.
conditions and loads.
conditions and/or symmetry
Subsequently, boundary and
choices can compromise the
symmetry conditions must be ver-
results.
ified. Measured and calculated
strains should be compared.

Volume 2: Water-Touched Tubes 13-29


7. Case study

Corrosion Fatigue
Case Study I: Application of Influence Diagram

This case study illustrates how the Typical On-Line Chemical Operating The boiler is fired and pressurized to
influence diagram approach might Ranges: Typical on-line ranges for approximately 3 MPa to purge any
be used to determine locations with critical chemistry parameters (post- air in the steam and water circuits.
a potential for corrosion fatigue prob- 1984) are: Score “4”, for actions “a” and “b” on
lems and how the evaluation of the form.
stress rank and environmental para- • Boiler water pH: 9.1-9.8. Score “1”
on the form. The assessed environmental para-
meter might influence that analysis. meter is the total score “23”, divided
Unit Background: The unit is rated at • Boiler water cation conductivity: by the value of the questions
163 MW. The boiler is a subcritical, < 12 mS/cm minus a phosphate answered “18” or E = 1.3 in this
drum-type unit with natural circulation correction gives about 8mS/cm. case. As shown in the form, the
and reheat. It is fired on lignite. The Score “2” on the form. result falls in the range of E1 (good).
boiler has 68,000 firing hours and 728 • Feedwater dissolved oxygen: Equivalent Operating Hours: For
starts. Although the boiler has experi- < 5 ppb. Score “1” on the form. 68,000 firing hours, (H) and 728 total
enced serious sootblower erosion boiler starts (Ns) the equivalent
problems, there have been no report The cation conductivity required for
the form is corrected to typical phos- operating hours are derived from the
of BTF by corrosion fatigue to date. equation:
phate concentrations. Unit records
Stress Rank Evaluation: The first indicated a normal phosphate level of EOH = (H/1000) + (Ns/(H/1000))
step in the evaluation process is to 1 ppm, for a correction of 4.1 mS/cm. = 78.7
identify sites where the magnitude of Note also that the unit has an all fer-
the stress might be sufficient to Results: The corrosion fatigue
rous feedwater system; that is, there
cause a corrosion fatigue concern. A regime for this situation can now be
are no copper alloy materials in the
detailed inspection of unit was con- determined by plotting the results on
condensate or feedwater systems.
ducted; as a result a boiler ash hop- the influence map. This is shown in
per seal plate attachment was Typical Start-Up Chemical Operating Figure 13-24. Under the assigned
selected for further evaluation. Figure Ranges: Selection of proper ranges conditions, the location is at high
13-23 shows detail of the location. A for start is complicated by variations risk for damage due to corrosion
stress rank of “B” was assigned by in chemistry and stress over the start- fatigue because the point falls to the
noting that this location was similar up period. For the evaluation, typical right of the E1 line. There have been
to that of location #3 in Figure 13-7 ranges at the point of attaining full or no failures yet. It is possible that the
and Table 13-2. target steam drum pressures are actual stress at the location is
used. Defining these ranges will slightly less than the typical “B”
Environmental Parameter: A review require data from several starts of location. However, there should be
of the unit chemistry history allowed each type (cold, warm and hot). The sufficient concern to conduct selec-
a calculation of the environmental subject boiler had these ranges: tive tube sampling for corrosion
parameter as detailed in Table 13-6. fatigue at this location, despite the
The following information served as • Boiler water pH: 9.1-9.8. Score “2” fact that no failures have been
the basis: on the form. observed yet.
Phosphate Boiler Water Alkalinity • Boiler water cation conductivity, 20 It is also easy to see how, given a
Control: Until about mid-1984 the mS/cm - correction of 4 mS/cm = 16 currently marginal situation, a slight
unit used congruent phosphate treat- mS/cm. Score “4” on the form. deterioration in the operating prac-
ment. A review of the level of phos- tices for cycle chemistry control
phate consumption indicates that the • Feedwater dissolved oxygen < 50
ppb. Score “2” on the form. could push the situation into consid-
boiler had a severe hideout problem, erably more severe problems. It is
which would be a factor of “9” on the Chemical Cleans: There had been no interesting to note that the earlier
form. However, the unit switched to chemical cleans since commission- operation with congruent phosphate
equilibrium phosphate treatment in ing. Score “1” on the form. treatment and a severe hideout
late 1984 and has not had a hideout problem would have been charac-
problem since that time. Therefore Boiler Shutdown/Lay-Up Procedures:
On shutdown a nitrogen blanket is terized by a calculated environmen-
the form shows “3” for this entry. tal parameter of E2; almost certainly
introduced once the boiler reaches
Excursions: The boiler had experi- atmospheric levels. If the boiler is a severe corrosion fatigue problem
enced no excursions causing hydro- drained and refilled, the water is would have resulted.
gen damage (low pH events). Score treated during the refilling process.
“3” on the form.

13-30 Corrosion Fatigue


Scalloped Seal
Plate Attachment
Membrane
Tube

Scallop
bar

Windbox Fillet
casing weld

CL furnace

O.D.front or rear
wall tubes
Mud drum

Top of ash hopper

Seal
Slag screen: stainless plates
steel type 430 woven
wire space cloth Water Water
level trough

Figure 13-23. Schematic of the boiler ash hopper seal plate attachment.
Source: D. Sidey, et al.1d

Stress Rank (S)


High (A)
Stress

(B)

Low High
risk risk
(C)

Environment
parameter (E)
E4 E3 E2 E1
Low
Stress (D)
0 30 60 79 90 120 150
Equivalent Operating Hours (EOH)

Figure 13-24. The case study results are plotted onto the influence map to determine
the appropriate corrosion fatigue susceptibility. Source: D. Sidey, et al.1d

Volume 2: Water-Touched Tubes 13-31


Table 13-6
Completed Form for Case Study to Evaluate Environmental Parameter (E)
Response Total
Value Item Score Score

Phosphate boiler water alkalinity control

3 Does the boiler experience phosphate hideout or phosphate No Irregularly Regularly


carryover to the reheater? 3 6 9 3

Excursions

3 How many hydrogen damage or caustic gouging events resulting None One More than one
in tube failures have occurred over the life of the boiler? 3 6 9 3

Typical on-line chemical operations

1 (1a) Boiler water pH at blowdown 9.0 - 9.6 8.0 - 10.0 < 8, > 10
1 2 3 1

1 (1b) Cation conductivity (µS/cm) ²6 6 - 30 > 30


(minus phosphate correction 4.1 x ppm PO4) 1 2 3 2

1 (2) Feedwater at the economizer inlet, dissolved ²5 ² 20 > 20


oxygen (ppb) 1 2 3 1

Typical start-up chemical operating ranges


(measured at the point of reaching target (or full) pressure)

2 (1a) Boiler water pH at blowdown 9.0 - 9.6 8.0 - 10.0 < 8, > 10
2 4 6 2

2 (1b) Cation conductivity (µS/cm) ²6 6 - 30 > 30


(minus phosphate correction 4.1 x ppm PO4) 2 4 6 4

2 (2) Feedwater at the economizer inlet, dissolved oxygen (ppb) ² 50 ² 200 > 200
2 4 6 2

Chemical cleans

1 How many chemical cleans using a hydrochloric acid solution None One More than one
has the boiler been exposed to? 1 2 3 1

Boiler shutdown/lay-up procedures

2 What actions are taken for shutdown corrosion protection: Actions Actions No action
(a) N2 cap on drum and treat water if boiler not drained. (a) to (d) (a) and (b)
(b) Refill drained boiler with chemically treated water to 2 4 6 4
control pH and oxygen
(c) Ensure dry storage if drained.
(d) Monitor and adjust pH and oxygen in boiler water
during wet lay-up.

Total Value: ____18


_____ (total for questions answered) Total Score: ____23
_____

Environment Parameter: = E1, for Total Score/Total Value = 1.0 to 1.5


= E2, for Total Score/Total Value = 1.5 to 2.0
= E3, for Total Score/Total Value = 2.0 to 2.5
= E4, for Total Score/Total Value = 2.5 to 3.0

13-32 Corrosion Fatigue


8. References
1Patterson, 10Paterson, S.R., T.A. Kuntz, R.S. Moser, and H.
R.W., et al., Corrosion Fatigue Boiler Tube
Failures in Waterwalls and Economizers, Research Vaillancourt, Boiler Tube Failure Metallurgical Guide,
Project 1890-5, Final Report TR-100455, Electric Power Volume 1: Technical Report, Volume 2: Appendices,
Research Institute, Palo Alto, CA. Research Project 1890-09, Final Report TR-102433,
Electric Power Research Institute, Palo Alto, CA, October,
a. McNabb, D., D. Sidey, R.W. Patterson, J. Fishburn, 1993.
and A. Banweg, Volume 1: Field Survey Results, April, 11Hay,
1992. K.A. and D.B. Meadowcroft, “Kinetics of Oxide
Growth Through Cracks in Coatings on 9% Cr Steels”,
b. Ogundele, G.I., E.T.C. Ho, D. Sidey, R.W. Patterson, Corrosion Science, Volume 16, 1976, pp. 349-354.
L.D. Paul, M.T. Miglin, and A. Banweg, Volume 2: 12Scott,
Laboratory Corrosion Studies, July, 1992. P.M. and W.H. Bamford, “The Development and
Use of Electrochemical Potential Monitoring in
c. Sidey, D., D. McNabb, J. Stodola, R.W. Patterson, R. Environment Assisted Cracking Tests in High
Ganta, B. Barishpolski, J. Fishburn, D. Peterson, D.K. Temperature, High Pressure , Aqueous Environments” in
Johnson, and A. Banweg, Volume 3: Field Testing and W.H. Cullen, ed., Proceedings of the Second
Stress Analysis, January, 1993. International Atomic Energy Agency Specialists’ Meeting
d. Sidey, D., D.D. McNabb, R.W. Patterson, J. Fishburn, on Subcritical Crack Growth, NUREG/CP-0067, Vol. 1,
A. Banweg, and R.B. Dooley, Volume 4: Summary 1986, pp. 51-67.
Report and Guidelines for Corrosion Fatigue 13Chen. C.M., K. Aral, and G.J. Theus, Computer-
Evaluation, December, 1993. Calculated Potential-pH Diagrams to 300°C, Volume 2:
2Moles, M.D.C. and H.J. Westwood, “Corrosion Fatigue Handbook of Diagrams, Research Project 1167-2, Final
Tube Failures in Fossil-Fueled Boilers”, Proceedings Report NP-3137, Electric Power Research Institute, Palo
International Conference on Materials to Supply the Alto, CA, June, 1983.
Energy Demand, Harrison, B.C. Canada, American 14Parkins,R.N., “Stress Corrosion Spectrum”, British
Society for Metals, 1980, pp. 515-537. Corrosion Journal, vol. 7, January, 1972.
3Westwood, H.J. and W.K. Lee, “Corrosion Fatigue 15Ford,F.P., “Relationship Between Mechanics of
Cracking in Fossil-fueled Boilers”, Journal of Materials Environmental Cracking and Design Criteria”, ICM3, Vol.
Engineering, Vol. 9, 1987, pp. 163-173. 2, Cambridge, England, August, 1979.
4Crouch, A.G. and R.B. Dooley, “The Mechanical 16Ford,F.P. and P.W. Emigh, “The Prediction of the
Integrity and Protective Performance of Silica Coatings”, Maximum Corrosion Fatigue Crack Propagation Rate in
Corrosion Science, Volume 16, 1976, pp. 341-347. the Low Alloy Steel De-Oxygenated Water System at
5Magnin, T., “An Approach to the Mechanisms of 288°C”, Corrosion Science, Vol. 25, No. 8/9, 1985, pp.
Corrosion Fatigue Damage”, Memoires et Etudes 673-692.
Scientifiques Revue de Metallurgie, LS7857/7Feb90/js, 17Ford, F.P. and P. Combrade, “Electrochemical Reaction
November, 1983. Rates on Bare Surfaces and Their Use in a Crack
6Hickling, J. and D. Blind, “Strain-Induced Corrosion Prediction Model for the Low Alloy Steel/Water System”,
Cracking of Low-Alloy Steels in LWR Systems - Case Proceedings of the 2nd IAEA Specialists’ Meeting on
Histories and Identification of Conditions Leading to Subcritical Crack Growth, Sendai, Japan, May 15-17,
Susceptibility”, Nuclear Engineering and Design, Vol. 91, 1985.
1986, pp. 305-330. 18Parkins,R.N., “Environment Sensitive Fracture and Its
7Ward, G., B.S. Hockenhull, and P. Hancock, “The Effect Prevention”, British Corrosion Journal, Vol. 14, 1979, pp.
of Cyclic Stressing on the Oxidation of a Low Carbon 5-14.
Steel”, Metallurgical Transactions, Vol. 5., June, 1974. 19Galvele,J.R., “A Stress Corrosion Cracking Mechanism
8Hurst, R.C., M. Davies, and P. Hancock, “The Based on Surface Mobility”, Corrosion Science, Vol. 27,
Determination of Fracture Strains of Growing Surface No. 1, 1987, pp. 1-33.
Oxides on Mild Steel at High Temperatures”, Oxidation of 20Pugh, E.N., J.A.S. Green, and A.J. Sedricks, “Current
Metals, Vol. 9, No. 2, 1975, p 161. Understanding of Stress Corrosion Cracking
9Grosskreutz, J.C. and M.B. McNeil, Journal of Applied Phenomena”, RIAS Technical Report 69-3, Research
Physics, Vol. 40, 1969, pp. 355. Institute for Advanced Studies, Martin Marietta
Corporation, Baltimore Maryland, March, 1969.

Volume 2: Water-Touched Tubes 13-33


21Scully,
J.C., “The Theory of Stress Corrosion Cracking”, 28Layton, K.F., “Water Side Corrosion in the Waterwall
The Theory of Stress Corrosion Cracking in Alloys, NATO Tubes of Hunter Unit 3”, in Dooley, B and D. Broske,
Science Affairs Division, September, 1972. eds., Boiler Tube Failures in Fossil Power Plants:
22Hickling,J., “Strain Induced Corrosion Cracking: Conference Proceedings, Conference held in Atlanta,
Georgia, November 10-12, 1987, CS-5500-SR, Electric
Relationships to Stress Corrosion Cracking/Corrosion
Power Research Institute, Palo Alto, CA, 1988, pp. 2-271
Fatigue and Importance for Nuclear Plant Service Life”,
through 2-286.
Proceedings 3rd IAEA Specialists’ Meeting on Subcritical
Crack Growth, NUREG/CP-0112, ANL-90/22, Vol. II, 29Bursik,A., R. B. Dooley, and B. Larkin, Guidelines for
Moscow, May 14-17, 1990. Oxygenated Treatment for Fossil Plants, Research
23Newman, Project 1403-45, Final Report TR-102285, Electric Power
R.C. and R.P.M. Procter, “Stress Corrosion
Research Institute, Palo Alto, CA, December, 1994.
Cracking: 1965-1990”, British Corrosion Journal, Vol. 25,
No. 4, 1990, pp. 259-269. 30Dooley, R.B., A. Aschoff, and F. Pocock, Cycle

24Kussmaul, K. and B. Iskluth, “Environmentally Assisted Chemistry Guidelines for Fossil Plants: Phosphate
Crack Growth in a Low Alloy Boiler Steel in High Treatment for Drum Units, Final Report TR-103655,
Electric Power Research Institute, Palo Alto, CA,
Temperature Water Containing Oxygen”, Nuclear
December, 1994.
Engineering and Design, Vol. 119, Elsevier Science
Publishers, B.V., North Holland, 1990, pp. 415-430. 31Dooley, R.B., A. Aschoff, and F. Pocock, Cycle

25Personal Communication from T. Healy, (ESB Ireland) to Chemistry Guidelines for Fossil Plants: All-Volatile
R.B. Dooley, February, 1995. Treatment for Drum Units, TR-105041, Electric Power
Research Institute, Palo Alto, CA, to be published 1996.
26Sidey,D., et al., “Lambton TGS Unit 4, Investigation 32Dooley, R.B. and L.D. Paul, “Phosphate Chemistry and
Into Lower Waterwall Header and Steam Drum
Corrosion Fatigue”, International Water Conference,
Cracking”, Ontario Hydro Internal Report CTS-31020-5,
Pittsburgh, PA, October, 1995, IWC-95-17.
August, 1983.
27Stodola, J., “Review of Boiler Water Alkalinity Control”,
International Water Conference, 47th Annual Meeting,
held in Pittsburgh, Pennsylvania, October 27-29, 1986.

13-34 Corrosion Fatigue


ACTIONS for Corrosion Fatigue
Action 1a: If a BTF has oc- • Evidence of corrosion fatigue
Two paths for the BTF team to curred and corrosion fatigue is damage found in similar units.
take in the investigation of corro- the likely mechanism.
sion fatigue begin here. The goal • Evidence that one or more of the
of these actions is to see if fur- ➠ Determine whether the failure has risk factors from the influence dia-
ther investigation of corrosion occurred in a location that is typi- gram: environment ranking, stress
fatigue is warranted or whether cal of corrosion fatigue ranking or equivalent operating
hours, may lead to a concern.
another BTF mechanism should ➠Review Figures 13-7a and b for
be investigated. See case study in main text.
typical boiler regions.
➠ Follow Action 1a: If a BTF has • Evaluation of unit cycle chemistry
➠Review Table 13-2 for suscepti-
occurred and corrosion fatigue indicates an environmental rank-
ble locations.
is the likely mechanism. ing of E3 or E4. See the case
➠Determine whether failure loca- study and Table 13-5. Such a
➠ Follow Action 1b: If a precursor tions are near tube attachments warning might be triggered by
has occurred in the unit that or other locations where con- one or more of the following:
could lead to future BTF by straint during transient opera-
corrosion fatigue. • A persistent problem with phos-
tions is likely.
phate hideout and return.
➠ Confirm that the macroscopic • One or more tube failures by
appearance of the failure
either hydrogen damage or
includes such features as:
caustic gouging.
• Cracking that has initiated on
• Cycle chemistry operating
the inside surface of the tube,
ranges for pH, cation conduc-
typically at multiple locations
tivity, or dissolved oxygen,
(Figure 13-3).
either during normal operation
• Association of the failure with or upon startup, that are consis-
an external attachment (Figure tently outside the recom-
13-1). mended ranges.
• A pin-hole leak (Figure 13-4), a • More than one chemical clean
thick-edged crack (Figure 13-5) by hydrochloric acid.
oriented either axially or circum-
• Boiler shutdown and layup pro-
ferentially, or a thick-edged
cedures which have not
blowout or rupture (Figure 13-1).
included such steps as nitrogen
➠ If the BTF seems to be consistent capping, chemical treatment for
with these features of failure, go pH and oxygen control during
to Action 2 for further steps to the lay-up and on re-start,
confirm the mechanism. and/or dry storage during
➠ If the BTF does not seem to have drained periods.
features like those listed, return to • Unit has been subjected to
the screening Table for water- numerous starts or has accumu-
touched tubing (Table 12-1) to lated a large number of “equiva-
pick a more likely candidate. lent operating hours”. This should
be considered in conjunction with
Action 1b: If a precursor has location stress rank and environ-
occurred in the unit that could mental factors - see main text.
lead to future BTF by corrosion
fatigue. ➠ These precursors can be root
cause influences of corrosion
➠ Determine whether one of more fatigue. If one or more has
of the following precursors has occurred, go to Action 3 which
been found or is likely to have outlines the steps to confirm the
occurred in the unit: influence of each.
• Evidence of cracking found dur-
ing routine inspections, particu-
larly at susceptible locations. See
Table 13-2, Figures 13-7 a and b.

Volume 2: Water-Touched Tubes 13-35


Action 2: Determine (confirm) that the mechanism is corrosion
fatigue.

A failure has occurred which the ➠ Confirm that damage location is May still be corrosion fatigue, con-
BTF team has tentatively identi- consistent with corrosion fatigue. tinue through flowchart; however,
fied as being caused by corro- Is damage associated with a review for indications of mechani-
sion fatigue (Action 1a). Action 2 susceptible location? See cal fatigue, see distinctions dis-
should clearly identify corrosion Figures 13-7a/b and Table 13-2. cussed in main text, Section 1.1.
fatigue as the primary mecha-
nism or point to another cause.
The actions listed will be exe-
cuted by removing representative ➠ Determine location of damage If OD-initiated, mechanism is more
tube sample(s), followed by initiation. Is damage initiated likely to be mechanically-induced
from the inside (waterside) of fatigue. Review main text Section
visual examination and detailed
the tube? 1.1 for distinctions.
metallographic analysis. One of
the primary aims is to establish
that damage is not OD-initiated
fatigue. ➠ Evaluate nature of cracking. Is If damage is of a more ‘gouging”
there evidence of multiple initia- nature check to see if an underde-
tion sites, with wide cracks, of a posit corrosion mechanism (hydro-
transgranular nature? gen damage, caustic gouging or
acid phosphate corrosion) is active.

Probably mechanism is corrosion


fatigue. Confirming characteristics
are:
• Cracks filled with oxide and
blunt tipped.
• Crack profiles usually irregular.
• Signs of discontinuous growth,
re-initiation.

➠ Go to Action 3: Root Cause


Determination

References to other sources of infor-


mation:
• Main text (this chapter) provides • Some care is required to distin-
the background to the mecha- guish between ID-initiated corro-
nism and development of corro- sion fatigue and OD-initiated
sion fatigue. fatigue. Key differences are dis-
• Summary of the steps and meth- cussed in the main text, Section
ods of metallurgical investigation 1.1, and in Chapter 7, Volume 1.
of boiler tube failures can be
found in Chapter 6, Volume 1.

13-36 Corrosion Fatigue


Action 3: Determine root cause of corrosion fatigue
➠ Review list of major root cause influences in first column, below.
A BTF failure has occurred and
the mechanism has been con- ➠ Take indicated actions to confirm the applicability of that influence in unit.
firmed as corrosion fatigue
(Action 2) or a precursor
occurred (Action 1b). The goal of Major Root Cause Influences ➠ Actions to Confirm
this Action 3 is for the BTF Team
3.2 Influence of Excessive Stresses/Strains
to review the potential root
causes of corrosion fatigue, iden-
tify probable ones, and take 3.2.1 Restraint stresses at attachments ➠ a). Compare damaged locations to those
typical of corrosion fatigue. See Figures
those actions that are needed to
13-7 a/b and Table 13-2.
confirm which are operative in
the unit. This step must be taken ➠ b). Inspect susceptible locations before
so that the proper actions can be tube failures occur.
taken to prevent future BTF from ➠ c). Selectively sample to identify damage
occurring by this mechanism. accumulation.
Execute, in parallel, Action 4 to
determine the extent of damage. ➠ d). Thermocouple and/or strain gauge
testing to confirm high strain locations.
➠ e). Finite element stress analysis to
predict high strain locations.

3.2.2 Subcooling (cooling water stratification) in ➠ f). Review operating records.


natural circulation boilers ➠ g). Thermocouple top and bottom of
boiler to monitor ÆT as function of shut-
down time.
➠ h). Strain gauge to confirm.

3.3 Influence of Environmental Factors

3.3.1 Poor water chemistry ➠ i). Review water chemistry logs and prac-
tices, with particular emphasis on pH
reductions during shutdown and early
startup; if review indicates a problem then
implement a monitoring program. See dis-
cussion of minimum levels of instrumenta-
tion in Chapter 3, Volume 1.
➠ j). Calculate Environmental Parameter for
use in Influence Diagram from information
gathered above; this will help determine
the contribution of environment to the cor-
rosion fatigue problem.
➠ k). Selectively sample tubes from at-risk
areas for evidence of pitting or corrosion
fatigue damage.

3.3.2 Overly aggressive or improper chemical ➠ l). Review chemical cleaning procedures
cleaning and correlate chemical cleaning with cor-
rosion fatigue failures. See Chapter 4,
Volume 1 for additional information about
chemical cleaning.
➠ m). Selectively sample at-risk tubes.

Volume 2: Water-Touched Tubes 13-37


Action 3: Determine root cause of corrosion fatigue (continued)

Major Root Cause Influences ➠ Actions to Confirm

3.3.3 Improper boiler shutdown and/or ➠ (n). See actions in items (i, j) above.
lay-up procedures

3.4 Influence of Historical Unit Operation

3.4.1 Operating procedures that have pro- ➠ (o). Review operating records to deter-
duced high stresses mine operating hours and boiler starts.
➠ (p). Plot failure history against unit oper-
ating conditions. See Figures 13-13 and
13-14.

Action 4: Determine the extent of damage or affected areas

In parallel with Action 3 (root


cause analysis), the BTF Team ➠Identify all locations to be examined. Refer to Section
should determine the extent of 1.2 of main text, Figures 13-7 a/b, and Table 13-2 for
damage. Evaluation will be typical locations. Missed locations are sites for future
failures. Corrosion fatigue is very unlikely to have
based on detecting obvious
occurred in only one area.
signs of cracking.

➠Perform visual examination to detect obvious signs of


cracking.

➠Perform UT/RT/videoprobe survey, as possible, to


measure extent of cracking. A review of NDE methods
is provided in Chapter 9, Volume 1.

➠Perform tube sampling to confirm results of NDE


inspection and to determine the degree of damage.

➠Use results interactively with Action 3.

➠Go to Action 5: Implement Repairs, Immediate


Solutions and Actions.

13-38 Corrosion Fatigue


Action 5: Implement repairs, immediate solutions and actions
➠Implement repairs or replacement ➠Implement the appropriate
The most important immediate of affected tubes as identified guidelines, controls and monitor-
actions for the BTF team are from the NDE Survey (Action 4). ing if the root cause is poor cycle
to:(i) start the application of the chemistry. See main text this sec-
influence diagram method to ➠See Chapter 11, Volume 1 for tion and background material in
summary of applicable tube Chapter 3, Volume 1.
determine the probable effec-
repair techniques.
tiveness of longer-term solutions, ➠Institute modified procedures to
(ii) repair or replace damaged ➠Develop a plan to replace correct overly aggressive chemi-
tubes, (iii) implement available affected tubing on the basis of cal cleaning. See Chapter 4,
short-term changes to operation the root causes and probable Volume 1 for an overview of the
or chemical cleaning where they choice of long-term solution. recommended practices.
are at the root of the existing
➠ Apply the influence diagram. ➠If improper unit shutdown or
problem. The use of the influence diagram layup procedures underlie the
approach will help pinpoint which problem, modify procedures.
root cause must be addressed to See Chapter 4, Volume 1 for an
prevent repeat failures by corro- overview of the recommended
sion fatigue. This is primarily a practices.
long-term action, but an immedi-
ate action that can be imple- References to other sources of
mented during any repair or detailed information:
replacement activities is to
ensure that the necessary plant • Main text and Table 13-4 provide
information is gathered. See the additional detail on repairs, imme-
case study for an example of the diate solutions and actions and
process. their relation to the underlying root
causes.

Volume 2: Water-Touched Tubes 13-39


Action 6: Implement long-term actions to prevent repeat failures

The correction of the underlying Major Root Cause Influences ➠ Long-Term Actions
problem(s) and the prevention of
repeat failures are priorities for Influence of Excessive Stresses
the BTF team. The proper
choice of long-term actions will Restraint stresses at attachments ➠ See guidance in main text for this mecha-
be based on clear identification nism, Section 6.2.
of the underlying root cause(s), ➠ Most effective measures have been modifi-
guided by the influence dia- cation of attachments to lower stresses.
gram. The most effective long-
term solution has been lowering Subcooling (cooling water stratification) in ➠ Install off-line boiler circulation pumps to
the applied stresses by modify-
natural circulation boilers reduce level of subcooling.
ing attachment designs; how-
ever, improper modifications
have intensified the problem. Influence of Environmental Factors

Poor water chemistry ➠ Clean up overall cycle and confront specific


chemistry problems such as condenser
leaks, impurity ingress, lack of appropriate
procedures, lack of appropriate monitoring
devices, etc.
➠ Apply appropriate guideline procedures for
specific chemistry, monitoring, and instrumen-
tation. See the overview of recommended prac-
tices in Chapter 3, Volume 1.

Overly aggressive or improper chemical ➠ Optimize chemical cleaning procedures and


cleaning frequency. See Chapter 4, Volume 1.

Improper boiler shutdown and/or lay-up ➠ Optimize shutdown, lay-up procedures. See
procedures Chapter 4, Volume 1.

Influence of Historical Unit Operation

Operating procedures that have produced high ➠ See guidance in main text for this
stresses mechanism, Section 6.2, and references
provided there.
➠ Reduction of stresses or improvement in
environmental parameter are possible actions.

13-40 Corrosion Fatigue


Action 7: Determine possible ramifications/ancillary problems

The final step for the BTF team is Corrosion Fatigue Alert for Other Cycle ➠ Actions
to review the possible ramifica- Aspect Components
tions to other cycle components Problems with boiler • Potential for boiler tube ➠Implement stricter cycle chemistry
implied by the presence of corro- water or feedwater damage by other mech control program, instrumentation. See
sion fatigue or its precursors. chemistry control. anisms such as acid phos- Chapter 3, Volume 1 for an overview of
phate corrosion, if underly- the issues.
ing problem is phosphate ➠Alert to potential problems
hideout, or hydrogen dam- throughout cycle.
age such as via condenser
leakage.
• Potential for carryover
in steam to reheater.

Excessive or overly Potential for boiler tube ➠Apply guidelines for chemical
aggressive chemical damage by other mecha- cleaning as summarized in Chapter 4,
cleans. nisms Volume 1.

Inadequate or improper Potential for boiler tube ➠Modify shutdown procedures.


shutdown procedures. damage by other mecha-
nisms such as pitting.

Volume 2: Water-Touched Tubes 13-41


13-42 Corrosion Fatigue

Das könnte Ihnen auch gefallen