LSA 46.3
Low Voltage Alternators - 4 pole
This manual concerns the alternator which you have just purchased.
We wish to draw your attention to the contents of this maintenance manual.
Warning symbol for general danger to © - We reserve the right to modify the
personnel. characteristics of its products at any time in
order to incorporate the latest technological
developments. The information contained in
this document may therefore be changed
without notice.
Warning symbol for electrical danger to This document may not be reproduced in
personnel. any form without prior authorization.
All brands and models have been registered
and patents applied for.
SAFETY INSTRUCTIONS
We wish to draw your attention to the
following 2 safety measures which must be
complied with:
2
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
CONTENTS
1 - RECEIPT.............................................................................................................................4
1.1 - Standards and safety measures................................................................................ 4
1.2 - Inspection.................................................................................................................. 4
1.3 - Identification.............................................................................................................. 4
1.4 - Storage...................................................................................................................... 4
1.5 - Applications............................................................................................................... 4
1.6 - Usage restrictions...................................................................................................... 4
2 - TECHNICAL CHARACTERISTICS....................................................................................5
2.1 - Electrical characteristics............................................................................................ 5
2.2 - Mechanical characteristics........................................................................................ 5
3 - INSTALLATION..................................................................................................................6
3.1 - Assembly................................................................................................................... 6
3.2 - Checks prior to first use............................................................................................. 6
3.3 - Terminal connection diagrams................................................................................... 7
3.4 - Commissioning........................................................................................................ 10
3.5 - Setting up................................................................................................................ 10
4 - SERVICING - MAINTENANCE......................................................................................... 11
4.1 - Safety measures.......................................................................................................11
4.2 - Routine maintenance................................................................................................11
4.3 - Bearings.................................................................................................................. 12
4.4 - Mechanical defects.................................................................................................. 12
4.5 - Electrical faults........................................................................................................ 13
4.6 - Dismantling, reassembly......................................................................................... 15
4.7 - Installation & maintenance of the PMG................................................................... 17
4.8 - Table of characteristics....................................................................................... 17-18
5 - SPARE PARTS.................................................................................................................19
5.1 - First maintenance parts........................................................................................... 19
5.2 - Technical support service........................................................................................ 19
5.3 - Accessories ............................................................................................................ 19
5.4 - Exploded views, parts list and tightening torque..................................................... 20
3
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
1 - RECEIPT 1.4 - Storage
1.1 - Standards and safety Prior to commissioning, machines should
measures be stored :
- away from humidity (< 90%); after a long
Our alternators comply with most period of storage, check the machine
international standards. insulation. To prevent the bearings from
See the EC Declaration of Incorporation on becoming marked, do not store in an
the last page. environment with significant vibration.
1.2 - Inspection 1.5 - Application
On receipt of your alternator, check that it These alternators are mainly designed to
has not suffered any damage in transit. If produce electricity in the context of
there are obvious signs of knocks, contact applications involving the use of
the transporter (you may be able to claim generators.
on their insurance) and after a visual
check, turn the machine by hand to detect 1.6 - Usage restrictions
any malfunction. Use of the machine is restricted to operating
conditions (environment, speed, voltage,
1.3 - Identification power, etc) compatible with the characteri-
The alternator is identified by means of a stics indicated on the nameplate.
nameplate fixed on the machine (see
drawing).
Make sure that the nameplate on the
machine conforms to your order.
So that you can identify your alternator
quickly and accurately, we suggest you fill in
its specifications on the nameplate below.
LSA IP RATINGS
N°: Date : Voltage V
r.p.m. Hz Weight : kg Phase
LSA 000-1-006 e
27°C. A
C US
166631 Made in ............................
IEC 60034 - 1 & 5. / ISO 8528 - 3. / NEMA MG1 - 32 & 33. Moteurs Leroy-Somer - Boulevard Marcellin Leroy,
CS 10015 - 16915 Angoulême Cedex 9 - France
4
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
2 - TECHNICAL CHARACTERISTICS 2.2 - Mechanical characteristics
2.1 - Electrical characteristics - Steel frame
- Cast iron end shields
This alternator is a machine without
- Protected ball bearings, greased for life
sliprings or revolving armature brushes,
- Mounting arrangements: foot and flange
wound as “2/3 pitch”, 6 or 12-wire, with
mounted, single-bearing with SAE coupling
class H insulation and a field excitation
disc, double-bearing with SAE flange and
system available in either SHUNT, AREP
standard cylindrical shaft extension
or PMG version (see diagrams and AVR
- Drip-proof machine, self-cooled
manuals).
- Degree of protection: IP 23
• Electrical options
- Stator temperature detection sensors • Mechanical options
- Bearing sensors (PTC, PT100, etc) - Air inlet filter
- Space heater - Regreasable ball bearings
In order to conform to standard EN 61000- - IP 44 protection
6-3, EN 61000-6-2, EN 55011, the R 791
interference suppression kit is needed.
Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field
Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field
PMG
Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field
5
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
6
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
There are 2 possible methods for restoring 3.3 - Terminal connection diagrams
the above minimum values. To modify the connection, change the
a) Dry out the machine for 24 hours in a position of the stator cables on the terminals.
drying oven at a temperature of 110 °C The winding code is specified on the
(without the regulator). nameplate.
b) Blow hot air into the air intake, having
made sure that the machine is rotating with
the exciter field disconnected.
Note : Prolonged standstill
In order to avoid these problems, we
recommend the use of space heaters, as Any intervention on the alternator
well as turning over the machine from time terminals during reconnection or checks
should be performed with the machine
to time. Space heaters are only really
stopped.
effective if they are working continuously In no case should the internal
while the machine is stopped. connections in the terminal box be
subjected to stresses due to cables
WARNING connected by the user.
Ensure that the alternator has the degree
of protection matching the defined
environmental conditions.
• Mechanical checks
Before starting the machine for the first time,
check that:
- all fixing bolts are tight,
- the length of bolt and the tightening torque
are correct,
- the cooling air is drawn in freely,
- the protective grills and housing are cor-
rectly in place,
- the standard direction of rotation is clock-
wise as seen from the drive end (phase
rotation in order 1 - 2 - 3).
For anti-clockwise rotation, swap 2 and 3.
- the winding connection corresponds to the
site operating voltage (see section 3.3).
7
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
• Terminal connection : 12-wire
Connection codes Voltage / Detection Factory connection 12 wires
Parallel Star
T1 T7
6 190 - 208 190 - 240 T10
N
7 208 - 230 - T11 T12
T6 T3 W (3) - L3
T4 T10
T12 T5
8 - 190 - 208 T9
N T5 T2 V (2) - L2
T9 T2 R 250 : 0 => T8 / 110V => T11 T8
T11
R 450 : 0 => T3 / 220V => T2
T6 T4 T1 U (1) - L1
R 450M - R 450T - D 510 : T7
L3(W) T3 T8 L2(V) U => T1, V => T2, W => T3 NDE
F 1PH Winding 50 Hz 60 Hz DE
L1(U)
or
Series Delta T12 T1
3PH
6 220 - 240 220 - 240 T10 T12
T9 T4 7 250 - 260 - T3
W (3) - L3
T7 T6
T6 T9
8 200 220 - 240 T11
T3 T10 T5
V (2) - L2
R 250 : 0 => T8 / 110V => T11 T8 T2
L3(W) L2(V)
T11 T8 T5 T2 R 450 : 0 => T3 / 220V => T2
L L U (1) - L1
M R 450M - R 450T - D 510 : T7
T4
T1
Voltage LM = 1/2 voltage LL U => T1, V => T2, W => T3 NDE
FF 1PH
Winding 50 Hz 60 Hz DE
T9 T10 L
6 220 - 240 220 - 240
T2 T6 T8 T12 T8 T12
7 250 - 260 - M
T6
T3 T3 T11
T5 T11 T9 8 200 220 - 240
T1 T4 T7 T7
L
T10 R 250 : 0 => T4 / 110V => T1 T4 T2
L
M R 450 : 0 => T10 / 220V => T1
L
R 450M - D 510 : T5 T1
Voltage LM = 1/2 voltage LL V => T1, W => T10 NDE
G 1PH Winding 50 Hz 60 Hz DE
T10 M
6 220 - 240 220 - 240
T12
T6 T1 T7 T11
T12
T7 7 250 - 260 - T3 L
T9
T3 T4 8 200 220 - 240 T6
T5 T2
T2 L
T9 T10
R 250 : 0 => T8 / 110V => T11 T8
8
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
• Terminal connection : 6-wire
Connection codes Voltage / Detection Factory connection 6 wires
Star
T1 6S 380 - 415 380 - 480
N
7S 440 - T4 T5 T6
T3 W (3) - L3
T4 8S - 380 - 416
T6 T5
T2 V (2) - L2
R 450 : 0 => T3 / 380V => T2
R 450M : V => T2 / W => T3
T3 T2 T1 U (1) - L1
R 450T - D 510 :
L2(V)
U => T1, V => T2, W => T3 NDE
L3(W)
F or C 1PH Winding 50 Hz 60 Hz
DE
Delta L1(U)
or 6S 220 - 240 220 - 240 T4 T6
3PH
T6 T1 7S 250 - 260 - T3
W (3) - L3
8S 200 220 - 240 T5
T3 T4 V (2) - L2
T2
L3(W) L2(V) R 450 : 0 => T3 / 220V => T2
U (1) - L1
L T5 T2 L R 450M : V => T2 / W => T3 T1
R 450T - D 510 : NDE
Note: // alternator: CT -> L1 (In) U => T1, V => T2, W => T3
Black T1 T1 T1 T1 T2
Black T2 T2 T2 T9 T3
ST
Black T3 T3 T3 NC NC Voltage adjustment
Blue N N via remote potentiometer
Green/Yellow
9
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
• Connection checks 3.4 - Commissioning
- The alternator earth terminal inside the The various adjustments during tests
terminal box is connected to the electrical must be made by a qualified engineer.
earth circuit Ensure that the drive speed specified on
- The earth terminal is connected to the the nameplate is reached before
frame. commencing adjustment.
The connections inside the terminal box
must never be subjected to stress due to After operational testing, replace all
cables connected by the user. access panels or covers.
The AVR is used to make any adjustments
to the machine.
10
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
4 - SERVICING - MAINTENANCE WARNING
4.1 - Safety measures Do not use: trichlorethylene, perchlo-
Servicing or troubleshooting must be
rethylene, trichloroethane or any alkaline
carried out strictly in accordance with
products.
instructions so as to avoid the risk of
accidents and to maintain the machine in
its original state.
These operations must be performed at a
cleaning station, equipped with a
vacuum system that collects and flushes
All such operations performed on the out the products used.
alternator should be undertaken by
The insulating components and the
personnel trained in the commissioning,
impregnation system are not at risk of
servicing and maintenance of electrical
damage from solvents. Avoid letting the
and mechanical components, who must
wear personal protective equipment cleaning product run into the slots.
appropriate for mechanical and electrical Apply the product with a brush, sponging
hazards. frequently to avoid accumulation in the
housing. Dry the winding with a dry cloth. Let
Before any intervention on the machine,
ensure that it cannot be started by a manual any traces evaporate before reassembling
or automatic system and that you have the machine.
understood the operating principles of the • Mechanical servicing
system.
WARNING
Cleaning the machine using water or a
highpressure washer is strictly prohi-
Warning : During and after running, the
bited. Any problems arising from such
alternator will reach temperatures hot
treatment are not covered by our
enough to cause injury, such as burns.
warranty.
Degreasing: Use a brush and detergent
4.2 - Routine maintenance (suitable for paintwork).
Dusting: Use an air gun.
• Checks after start-up
If the machine is fitted with air inlet and outlet
After approximately 20 hours of operation,
filters, the maintenance personnel should
check that all fixing bolts on the machine are
clean them routinely at regular intervals. In
still tight, plus the general state of the
machine and the various electrical the case of dry dust, the filter can be cleaned
connections in the installation. using compressed air and/or replaced if it is
clogged.
• Electrical servicing After cleaning the alternator, it is essential to
Commercially-available volatile degreasing check the winding insulation (see sections
agents can be used. 3.2 and 4.5).
11
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
4.3 - Bearings
The bearings are permanently greased Approximate life of the grease (depending on use) =
20,000 hours or 3 years.
As an option, the bearings are regreasable Regreasing interval: 4000 hrs of operation
DE bearing: Amount of grease: 33 gr
NDE bearing: Amount of grease: 30 gr
Standard grease LITHIUM - standard - NLGI 3
Grease used in the factory ESSO - Unirex N3
It is imperative to lubricate the alternator during operation and on first use. Before using another
grease, check for compatibility with the original one.
- System short-circuit
- Misparalleling
Alternator damaged by a Possible consequences
Abnormal - Broken or damaged coupling
significant impact, followed by
noise - Broken or bent shaft end
humming and vibration
- Shifting and short-circuit of main field
- Fan fractured or coming loose on shaft
- Irreparable damage to rotating diodes/AVR, surge suppressor
12
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
4.5 - Electrical faults
Fault Action Effect Check/Cause
The alternator builds up and
its voltage is still correct - Lack of residual magnetism
when the battery is removed
Connect a new
battery of 4 to 12
No voltage volts to terminals The alternator builds up but - Check the connection of the voltage reference
at no load on E- and E+, its voltage does not reach the to the AVR
start-up respecting the rated value when the battery - Faulty diodes
polarity, for 2 to 3 is removed - Armature short-circuit
seconds - Faulty AVR
The alternator builds up but - Field windings open circuit (check winding)
its voltage disappears when - Revolving field coil open circuit (check the
the battery is removed resistance)
Check the AVR connections (AVR may be
faulty)
- Field windings short-circuited
Correct speed - Rotating diodes burnt out
Voltage too Check the drive - Revolving field coil short-circuited
low speed - Check the resistance
Increase the drive speed (do not touch the AVR
Speed too low voltage pot. (P2) before running at the correct
speed)
Voltage too Adjust AVR voltage Adjustment ineffective Faulty AVR
high potentiometer
- Check the speed: possibility of cyclic
irregularity
Adjust the
Voltage If no effect: try normal or fast - Loose connections
AVR stability
oscillations stability modes (ST2) - Faulty AVR
potentiometer - Speed too low when on load (or AVR LAM set
too high)
Voltage between E+ and E-
Voltage (DC) - Check the speed (or AVR LAM set too high)
correct at no Run at no load and SHUNT / AREP / PMG < 10V
check the voltage
load and too between E+ and - Faulty rotating diodes
low when on E- on the AVR Voltage between E+ and E- - Short-circuit in the revolving field coil. Check
load SHUNT / AREP / PMG > 15V the resistance.
- Faulty exciter armature. Check the resistance.
Check the AVR, the - Exciter winding open circuit
Voltage surge suppressor, - Faulty exciter armature
disappears the rotating diodes, The voltage does not return - Faulty AVR
during and replace any to the rated value - Revolving field coil open circuit or short-
operation defective circuited
components
13
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
• Checking the winding Assembly A: Connect a 12 V battery in
You can check the winding insulation by series with a rheostat of approximately
performing a high voltage test. In this case, 50 ohms - 300 W and a diode on both exciter
you must disconnect all AVR wires. field wires (5+) and (6-).
ASSEMBLY A
WARNING 6 - Field 5+
Damage caused to the AVR in such Rh. 50 -300W
1A diode
conditions is not covered by our
warranty.
+
• Checking the diode bridge -
70
80
10
0 100
AVR wires. - DC
Variac AC 12V
2) There are two ways of creating an 220V
assembly with separate excitation.
14
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
4.6 - Dismantling, reassembly • Access to connections and the
regulation system
WARNING Access directly by removing the top of the
cover (48) or the AVR access door (59).
During the warranty period, this
operation should only be carried out in • Replacing the NDE bearing
an approved workshop or in our factory,
- Remove the box lid (48), the NDE panel
otherwise the warranty
(47) and the side panels (367).
may be invalidated.
- Disconnect the stator outputs (T1 to T12).
Whilst being handled, the machine
- Disconnect the auxiliary winding wires
should remain horizontal (rotor not
AREP (X1,X2,Z1,Z2).
locked in position). Check how much the
- Disconnect the exciter wires (5+,6-).
machine weighs before choosing the
- Remove the air inlet louvre (51).
lifting method.
If using a single-bearing or double-bearing
machine without the regreasable bearing
option:
- Remove the 8 nuts from the tie rods (37).
- Remove the shield (36).
- Take out the antifriction bearing (70) using
a puller with a central screw (see drawing
below).
If the machine has the regreasable bearing
option, start by removing the screws from
the bearing stop (78).
• Tools required
To fully dismantle the machine, we
recommend using the tools listed below:
- 1 ratchet spanner + extension
- 1 torque wrench
- 1 set of flat spanners: 8 mm, 10 mm, 18 mm
- 1 socket set: 8, 10, 13, 16, 18, 21, 24, 30 mm
- 1 socket with male ferrule: 5 mm
- 1 puller - Fit the new antifriction bearing onto the
shaft after heating it by induction to
• Screw tightening torque approximately 80 °C.
- Mount the new preloading (wavy) washer
See section 5.4. (79) + the new “O” ring seal (349) in the
shield (36) and coat the bearing seat with
• Access to diodes adhesive paste (see After Sales Service).
If using a single-bearing or double-bearing
- Open the air intake grille (51). machine with the regreasable bearing
- Disconnect the diodes. option:
- Check the 6 diodes, change the diode - Screw a threaded rod into the thrust
bridges if necessary. bearing (78).
- Refit the end shield on the machine using
a dowel and nut in the shaft extension (see
drawing).
15
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
- Slide the threaded rod into the shield hole - Refit the shield (32) on the machine.
to make it easier to assemble (see basic - Slide the threaded rod into the shield hole
diagram). to make it easier to assemble (see basic
diagram).
4 78 36
Threaded rod
- Tighten the bottom thrust bearing screws
(78), remove the threaded rod and fit the
other screws.
- Block the 6 screws (31) of the bearing
before locking the tie rods (37).
Dowel - Refit the air grille (33) and (51).
Nut
• Dismantling the rotor assembly
Rotor Follow the procedure for dismantling the
bearings.
- In a single bearing machine:
• remove the SAE washer as per the front
bearing (32) removal procedure,
• remove the coupling disc (322).
NDE shield - Rest the rotor on one of its poles.
- Support the DE rotor (4) with a strap or with
a support constructed in accordance with
- Fit the thrust bearing screws (78), remove the following drawing.
the threaded rod, fit the other screw and - After extraction of the rotor, be careful not
tighten up the assembly. to damage the fan (15) or the booster (19) or
- Block the 8 tie rods (37) of the bearing.
dismantle it.
- Reconnect wires.
- Fit the air inlet louvre (51). - Remove the rotor on special V-shaped
- Replace the cover. supports.
WARNING
When dismantling the shields, you will
need to change the antifriction bearings,
the “O” ring seal, the preloading (wavy)
washer and adhesive paste.
16
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
• Reassembling the machine 4.7 - Installation and maintenance of
- Follow the dismantling procedure in reverse the PMG
order. The PMG reference is PMG 2.
Take care not to knock the windings when See the PMG manual ref : 4211.
refitting the rotor in the stator.
- In a single or dual bearing machine with
regreasable bearing option: apply the 4.8 - Table of characteristics
regreasable bearing changing procedure.
Table of average values
- Block the 6 screws (31) of the front bearing /
Alternator - 4 poles - 50 Hz - Standard
SAE washer before tightening the tie rods
winding No. 6.
(37).
(400V for the excitation values)
- Refit the air grille (33) and (51). The voltage and current values are given for
no-load operation and operation at rated
• Dismantling and reassembly of the load with separate field excitation.
filters All values are given to within ± 10% and may
- Remove the grille (51) then take out the be changed without prior notification (for
filter (52). Change the filter if necessary; exact values, consult the test report).
please refer to section 4.2 for cleaning the
filter. • Average values
To replace, follow the instructions in reverse Resistances at 20 °C (Ω)
order.
Exciter
Type Stator L/N Rotor armature
S2 0.028 0.26 0.03
53
S3 0.021 0.27 0.03
52 S4/S5 0.016 0.29 0.03
M7/M8 0.0115 0.31 0.035
51
L10/L11 0.0085 0.36 0.035
17
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
Field excitation current i exc (A)
Symbols : “i exc”: excitation current of the
exciter field
• Table of weights
(values given for information only)
18
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
5 - SPARE PARTS In the event of failure to comply with this
5.1 - First maintenance parts advice, the manufacturer cannot be held
responsible for any damage.
Emergency repair kits are available as an
option.
They contain the following items:
Emergency kit SHUNT 4254514
AVR R 250 - After operational testing, it is essential to
Diode bridge assembly - replace all access panels or covers.
Surge suppressor -
Emergency kit AREP/PMG 4061607 5.3 - Accessories
AVR R 450 - • Space heater for use when stopped
Diode bridge assembly - The space heater must run as soon as the
Surge suppressor - alternator stops. It is installed at the rear of
the machine. Its standard power is 250W
Single-bearing kit 4061227
with 220V or 250W with 110V on request.
Non drive end bearing -
«O» ring -
Preloading (wavy) washer -
Double-bearing kit 4061463
Non drive end bearing - Warning: the power supply is present
when the machine has stopped.
Drive end bearing -
«O» ring -
• Temperature sensors with thermistors
Preloading (wavy) washer -
(PTC)
These are thermistor triplets with a positive
5.2 - Technical support service temperature coefficient installed in the
Our technical support service will be stator winding (1 per phase). There can be a
pleased to provide any additional maximum of 2 triplets in the winding (at 2
information you may require. levels: warning and trip) and 1 or 2
thermistors in the shields.
For all spare parts orders or technical These sensors must be linked to adapted
support requests, send your request to sensing relays (supplied optionally).
service.epg@leroy-somer.com or your Cold resistance of cold thermistor sensors:
closest contact, whom you will find at 100 to 250 Ω per sensor.
www.lrsm.co/support indicating the comp-
lete type of machine, its number and the • Connection accessories
information indicated on the nameplate. - 6-wire machines : coupling (F)
- 12-wire machines : coupling (A), (F .F), (F).
Part numbers should be identified from the
exploded views and their description from
the parts list.
19
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
5.4 - Exploded view, parts list and tightening torque
• Single-bearing
20
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
• Double-bearing
21
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
22
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
Disposal and recycling instructions The oil and grease from the lubrication
We are committed to limit the environmental system should be considered as a hazardous
impact of our activity. We continuously waste and has to be handled according to
survey our production processes, material local legislation.
sourcing and products design to improve
recyclability and diminish our footprint.
These instructions are for information
purposes only. It is the user responsibility to
comply with local legislation regarding
product disposal and recycling.
Recyclable materials
Our alternators are mainly built out of iron,
steel and copper materials, which can be
reclaimed for recycling purposes.
These materials can be reclaimed through a
combination of manual dismantling,
mechanical separation and melting
processes. Our technical support depar-
tment can provide detailed directions on
products dismounting upon request.
23
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
24
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
This Declaration applies to the generators designed to be incorporated into machines complying with the
Machinery Directive Nr 2006/42/EC dated 17 May 2006.
LSA40, LSA42.3, LSA44.2, LSA44.3, LSA46.2, LSA46.3, LSA47.2, LSA49.1, LSA49.3, LSA50.1, LSA50.2,
LSA51.2, LSA52.2, LSA52.3, LSA53.1, LSA53, LSA53.2, LSA54, LSA54.2, TAL040, TAL042, TAL044,
TAL046, TAL047, TAL049, as well as their derivatives, manufactured by Leroy-Somer or on Leroy-Somer's
behalf, comply with the following International Standards and Directive:
Furthermore, these generators, designed in compliance with the Machine Directive Nr 2006/42, are therefore
able to be incorporated into Electrical Gen-Sets complying with the following International Directives:
WARNING:
The here mentioned generators should not be commissioned until the corresponding Gen-Sets have been
declared in compliance with the Directives Nr 2006/42/EC and 2014/30/UE, as well as with the other relevant
Directives.
Leroy-Somer undertakes to transmit, in response to a reasoned request by the national authorities, relevant
information on the generator.
Technical Managers
J.P. CHARPENTIER Y. MESSIN
4152 en - 2017.05 / m
The contractual EC Declaration of Conformity and Incorporation can be obtained from your contact on
Moteurs Leroy-Somer
request.
Siege social : Boulevard Marcellin Leroy CS 10015 - 16915 Angoulême cedex 9 - France
SAS au capital de 65 800 512 € - RCS Angoulême 338 567 258
25
Electric Power Generation Installation and maintenance 5278 en - 2017.11 / f
LSA 46.3
Low Voltage Alternators - 4 pole
26
Service & Support
Life Extension
•Remanufacturing Start-up
•System upgrade
•Commissioning
•Training
Optimization
•Monitoring Operation
•System audit •Genuine spare parts
•Repair services
Contact us:
Americas: +1 (507) 625 4011
Europe & Rest of the world: +33 238 609 908
Asia Pacific: +65 6250 8488
China: +86 591 88373036
India: +91 806 726 4867
Middle East: +971 4 811 8483 Scan the code or go to:
service.epg@leroy-somer.com www.lrsm.co/support
www.emersonindustrial.com
www.leroy-somer.com/epg
Linkedin.com/company/Leroy-Somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
5278 en - 2017.11 / f