2 ADVR-440
SECTION 2 : APPEARANCE / DIMENSIONS / INSTALLATION DRAWING
135.0 [5.31"] 45.0 [1.77"]
114.0 [4.49"] 20.0 [0.79"]
100.0 [3.94"]
80.0 [3.15"]
5.4 [0.21"]
Z2:Power Input
ADVR-440 50, C, 60:
Frequency Select
40 – 300 Vac PIN 50 and C for 50 Hz
PIN 60 and C for 60 Hz
8:Sensing Input U/F:
90 260 Vac -
Under Frequency
+
Protection
7:Power and Sensing
Input terminals A, B, C, D :
Stability Setting
F1, F2: A-B > 550KW
Excitation Output B-C 100-550KW
Connect to generator A-C < 100KW Fast
excitation field B-D < 100KW Slow
S F
STAB:
Stability Setting
- +
VOLT:Voltage
- + EXC.:Over Excitation Protection
Adjustment
- + TRIM:Analogue Voltage Input
1, 2:External VR Input
Shorted when not in use A1、A2:Analogue Voltage Input
3:No use +/- Max. +/- 5 Vdc or + 10 Vdc
S1、S2:Quadrature Droop Input
L, L:Short for 110V Max. sensitivity 0.07A for 5% droop,
Open for 220V Max. 0.33A
- +
DROOP:Current Compensation
Droop Adjustment
___________________________________________________________________________________________
ADVR-440 3
SECTION 4 : CONNECTION DIAGRAMS
N
R
G
~
S
T
OPEN:220VAC
SHORT:110VAC
N
R
G
~
S
T
___________________________________________________________________________________________
4 ADVR-440
N
Aux.winding
R
G
~
S
T
OPEN:220VAC
SHORT:110VAC
ATTENTION
1. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test
equipment must not be used. Use of such equipment could damage the AVR.
2. Improper setting of under-frequency protection could cause the output voltage of the unit to drop or
become unstable under with changes in load. Avoid making any changes to the U/F setting unless
necessary.