WIND LOAD CALCULATION (ASCE-07-10)

Methode-2, Analytical Procedure ( Chapter 26 )


Job No : Prepared : -
Job Name Structural calculation for mullion

Basic wind velocity,Vb = 45 m/s


Ridge height,Hr = 12.0 m
Eave height, He = 12.0 m
Effective area, Ae = 4.712 m2
whether open or closed? Enclosed
Type of structure buildings
Directional factor, Kd 0.85 Table 26.6.1
Topography factor, Kzt = 1 Section 26.8 & Fig 26.8.1
exposure category C Section 26.7.3
Importance factor 1 Table 1.5.2
Mean roof height, h 12 m (Roof height,h =he if roof angle <10 0)
Wall External pressure coefficient
Gcpe (+) Zone 4 = + 0.90
Gcpe (-) Zone 4 = - 0.90
Gcpe (+) Zone 5 = + 0.90
Gcpe (-) Zone 5 = - 1.20 ASCE-7-10, As per fig.6-17
Internal pressure coefficient
Gcpi(+) = + 0.18
Gcpi(-) = - 0.18
If h<15 ft, kh= 2.01(15/Zg)(2/α)
If h>15 ft, kh= 2.01(Z/Zg)(2/α)
α = 9.5 (Table 26.9.1 ASCE 7-10)
Zg = 274.3 m (Table 26.9.1 ASCE 7-10)
kh = 1.04 (Table 26.9.1 ASCE 7-10)

Velocity pressure, q= 0.613*kd*kzt*kz*V2 Cl 27.3.2 ASCE 7-10


= 1.097 kpa
Wind load @ height 12 m
Height Net design pressure
Zone 4 (+) Zone 4 (-) Zone 5 (+) Zone 5 (-)
12.0 m 1.19 1.19 1.19 1.51
STRUCTURAL CALCULATION
Double glazed Glass Design
Rev 0 Prepared By sqk

Structural Check for Double glazing cable galzing unit 13.52mm FT+Airspace+6 mm FT
Code References:-
ASTM E 1300-07 Standard practice for determining load resistance in building

Glass description
a= 2945 mm Glass Long dimension
b= 1600 mm Glass short dimension
t1 = 13.52 mm Thickness of inner lite (Table 4)
t2 = 6 mm Thickness of outer lite (Table 4)
Modulus of elascity of Glass,Eg = 72000 Mpa
Unit weight of glass,γ = 24.525 kN/m3

Loading
Design wind load,P = 1.51 Kpa

LS1 = 1.081 Load sharing factor for inner lite (Table 5)


LS2 = 14.752 Load sharing factor for outer lite (Table 5)

q1 = P/LS1 = 1.40 Kpa Load carried by inner lite


q2 = P/LS2 = 0.10 Kpa Load carried by outer lite

Glass Load Resistance


Support condition : Edges simply supported (spring support in STAAD Pro)
STRUCTURAL CALCULATION
Double glazed Glass Design
Rev 0 Prepared By Sqk

2.4

NFL1 = 2.4 Kpa Non factored load for inner lite ( Fig-A1.6-Upper chart)
NFL2 = 2.4 Kpa Non factored load for inner lite ( Fig-A1.6-Upper chart)

GTF1 = 3.6 Glass type factor for inner lite (Table-2)


GTF2 = 3.6 Glass type factor for outer lite (Table-2)
STRUCTURAL CALCULATION
Double glazed Glass Design
Rev 0 Prepared By Sqk

LR1 = NFL1*GTF1*LS1 Internal lite Load resistance


= 9.33984 Kpa
Load capacity of inner lite is greater than actual load
SAFE
LR2 = NFL2*GTF2*LS2 Outer lite Load resistance
= 127.457 Kpa
Load capacity of inner lite is greater than actual load
SAFE

Glass Center Deflection

b = 1600 mm (Glass short dimension)


a = 2945 mm (Glass long dimesnion)
L= Min(2945,1600) = 1600 mm
δ = Min (L/60,30) = 26.67 mm
(Allowable Glass deflection)

Center deflection for inner lite (As per X2.1)


r0 = (0.553-3.83(a/b)+1.11(a/b)2-.0969(a/b)3
= -3.340
r1 = (-)2.29+5.83(a/b)-2.17(a/b)2+0.2067(a/b)3
= 2.378
r2 = 1.485-1.908(a/b)+0.815(a/b)2-0.0822(a/b)3
= 0.222

x = ln(ln(q1*(a.b)2/(Eg.t1^4)
0.939

Center of glass deflection = w= t.e(r0+r1.x+r2.x2)


= 5.427 mm

Adopt:13.52 mm thick FT/AIR SPACE/6mm thick FT glass