Sie sind auf Seite 1von 2

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model FL-1 Fusible Links


50 lbs. (22,7 kg) Continuous Load
For Use With Automatic Closing Devices
General Technical
Description Data
The Model FL-1 Fusible Links (Ref. Fig- Approvals
ure 1) are fixed temperature releas- UL and C-UL Listed. FM Approved.
ing devices that are thermally actu- Minimum Continuous Load
ated fusible links. They are frequently 5 lbs. (2,3 kg).
installed over cooking appliances and
in the ducts of kitchen cooking equip- Maximum Continuous Load
ment to initiate the operation of extin- 50 lbs. (22,7 kg).
guishing systems. They are also com- Temperature Ratings
monly used to automatically operate See Table A.
smoke and heat vents as well as fire Physical Characteristics
doors.
The Model FL-1 Fusible Links is a re-
Fusible Link Halves. . . . Stainless Steel
Fusible Assembly ��������������������������������
Installation
designation of the Gem Issue C.
. . . . . . Solder, Copper, Stainless Steel The Model FL-1 Fusible Links are to be
installed with a continuous duty load of
WARNINGS NOTE 5 lb. (2,3 kg) to 50 Ibs. (22,7 kg). They
The Model FL-1 Fusible Links de- The Model FL-1 Fusible Links are not are to be secured so that, upon op-
scribed herein must be installed and rated for use in corrosive atmospheres. eration, the two halves of the Fusible
maintained in compliance with this Link will disengage and swing freely.
document, as well as with the applica-
ble standards of the National Fire Pro- Operation The Fusible Links are to be connect-
ed to either chain or cable via S-Hooks
tection Association, in addition to the When the fusible alloy melts due to having a minimum recommended 0.07
standards of any other authorities hav- exposure to heat, the Fusible Assem- inch (1,8 mm) wire diameter and a
ing jurisdiction. Failure to do so may bly compresses, allowing it to release minimum 0.25 inch (6,4 mm) diameter
impair the performance of these from between the two halves of the hook.
devices. Fusible Link. The two halves of the
The owner is responsible for maintain- Fusible Link are then separated by the
ing their fire protection system and de- tension force exerted by the continu-
vices in proper operating condition. ous duty load.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Issue C Maximum Allowable
Color of Link
Temperature Rating Temperature Exposure
135°F (57°C) 100°F (36°C) Black
165°F (74°C) 100°F (38°C) None
212°F (100°C) 150°F (66°C) White
286°F (141°C) 225°F (107°C) Blue
360°F (162°C) 300°F (149°C) Red
500°F (260°C) 475°F (246°C) Orange

table A
Temperature Ratings, Maximum Allowable
Temperature Exposure, And Color Code

Page  of 2 MAY, 2006 TFP1610


Page  of 2 TFP1610

Care and For installation other than per NFPA


96, frequent visual inspections are
In no event shall TFBP be liable, in
contract, tort, strict liability or under
Maintenance recommended to be initially per-
formed for Fusible Links installed in
any other legal theory, for incidental,
indirect, special or consequential dam­
The following inspection procedure potentially corrosive atmospheres to ages, including but not limited to labor
must be performed as indicated, in verify the integrity of the materials of charges, regardless of whether TFBP
addition to any specific requirements construction as they may be affected was informed about the possibility of
of the NFPA. Any impairments must be by the corrosive conditions present for such damages, and in no event shall
immediately corrected. a given installation. Thereafter, annual TFBP’s liability exceed an amount
inspections for signs of corrosion are equal to the sales price.
The owner is responsible for the in- recommended.
spection, testing, and maintenance of The foregoing warranty is made in lieu
of any and all other warranties, ex-
their fire protection system and devic-
es in compliance with this document, Limited press or implied, including warranties
of merchantability and fitness for a
as well as with the applicable stan-
dards of the National Fire Protection Warranty particular purpose.
Association (e.g., NFPA 25), in addition This limited warranty sets forth the ex­
to the standards of any authority hav- Products manufactured by Tyco Fire clusive remedy for claims based on
ing jurisdiction. The installing contrac- & Building Products (TFBP) are war­ failure of or defect in products, materi­
tor or product manufacturer should be ranted solely to the original Buyer for als or components, whether the claim
contacted relative to any questions. ten (10) years against defects in mate­ is made in contract, tort, strict liability
rial and workmanship when paid for or any other legal theory.
It is recommended that automatic sprin- and properly installed and maintained
kler systems be inspected, tested, and under normal use and service. This This warranty will apply to the full ex­
maintained by a qualified Inspection warranty will expire ten (10) years from tent permitted by law. The invalidity,
Service in accordance with local re- date of shipment by TFBP. No warran- in whole or part, of any portion of this
quirements and/or national codes. ty is given for products or com­ponents warranty will not affect the remainder.
Fusible Links must never be shipped manufactured by companies not af-
or stored where their temperatures will
exceed 100°F (38°C) and they must
filiated by ownership with TFBP or for
products and components which have Ordering
never be painted, plated, coated, or
otherwise altered after leaving the fac-
been subject to misuse, improper in-
stallation, corrosion, or which have not Procedure
tory. Modified Links must be replaced. been installed, maintained, modi­fied or Orders must include the description
repaired in accordance with ap­plicable and Part Number (P/N). Contact your
Care must be exercised to avoid dam- Standards of the National Fire Protec-
age to the Fusible Links both before local distributor for availability.
tion Association, and/or the standards
and after installation. Fusible Links of any other Authorities Having Juris- Model FL-1 Fusible Links
damaged by dropping, striking, or the diction. Materials found by TFBP to be Specify: Model FL-1 Fusible Link with
like, must be replaced. defective shall be either repaired or re- (specify) temperature rating, P/N
Fusible Links that are found to be ex- placed, at TFBP’s sole option. TFBP (specify).
hibiting signs of corrosion must be neither assumes, nor authorizes any 135°F (57°C). . . . . . . . . . . . . . . P/N 56-125-9-135
replaced. person to assume for it, any other ob- 165°F (74°C) . . . . . . . . . . . . . . . P/N 56-125-9-165
ligation in connection with the sale of 212°F (100°C). . . . . . . . . . . . . . P/N 56-125-9-212
NOTEs products or parts of prod­ucts. TFBP 286°F (141°C) . . . . . . . . . . . . . . P/N 56-125-9-286
shall not be responsible for sprinkler 360°F (162°C). . . . . . . . . . . . . . P/N 56-125-9-360
No attempt is to be made to disassem- 500°F (260°C). . . . . . . . . . . . . . P/N 56-125-9-500
ble, repair or clean a Model FL-1 Fus- system design errors or inac­curate or
ible Link. The complete assembly must incomplete information sup­plied by
be replaced if there is any indication of Buyer or Buyer’s repre­sentatives.
potential malfunction
Before closing a fire protection system 1”
control valve for inspection or mainte- (25,4 mm)
nance work on the fire protection sys- 17/64” DIA.
tem that it controls, permission to shut (6,75 mm)
down the affected system must first be
(15,88 mm)

obtained from the proper authorities


5/8”

and all personnel who may be affected


by this action must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for mon- 1-1/2”
itoring proprietary and/or central sta- (38,1 mm)
tion alarms.
INSPECTION PROCEDURE
Fusible Links installed per NFPA 96
“Standard for Ventilation Control Fire FUSIBLE ASSEMBLY
Protection of Commercial Cooking
Operations” are to be inspected per
the requirements of NFPA 96. figure 1, model fl-1 fusible link

TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale Pennsylvania 19446