Sie sind auf Seite 1von 6

Aiman shafiq bin Shuhaimi (FA15090), Mohammad Maarif bin Mohd Mahfoz (FB15036),

Muhammad Azri Hariz bin Md Yazid (FB15048), Azirulsyazwan bin Jaffar (FB15038),
Muhammad Huzaifi bin Yusniman (FB15029), Muhammad Akmal bin Azhar (FB15046)

The Analysis of Mechanical Vibrations and Acoustic Pressure Level of a Transformer Model

Faculty of Manufacturing Engineering, Universiti Malaysia Pahang

Abstract environment. Transformer operation is more


and more often connected with the problem
The paper presents the results of of an excessive emission of noise into
vibroacoustic investigations and the environment. This phenomenon becomes
measurements of the acoustic pressure level even more valid if a transformer station is
(noise) of a transformer model. The located in the vicinity of living quarters. The
measurements were taken at a full problems with exceeding allowable values
transformer load in two operation con- of acoustic power around a transformer
ditions: at a producer packeted core and at usually refer to the units of older
unpacketed core. Unpacketing consisted in constructions. The sources of sound are not
loosing the screws pressing the particular only magnetostriction phenomena taking
core plates. Mechanical vibrations were place in the core or cooler spinning fans but
registered and the acoustic pressure level also windings which vibrate due to
was measured. The vibroacoustic analysis electrodynamic forces and operation of the
results are presented in the form of pumps forcing oil flow. The paper presents
frequency spectra and the results of the the results of vibroacoustic investigations
acoustic analysis of the transformer and measurements of the acoustic pressure
understudy are shown by determining level around a dry transformer model, in
corrected values of the acoustic pressure which coredamage, consisting in its partial
level and by a frequency analysis. unpacketing, was modelled. The
measurements were taken on the transformer
Introduction and Background model, the view of which is shown in Fig. 1.
The transformer under study was
Modern approach of electric power characteristic of the following nominal data:
enterprises to the management of the
network assets accumulated, especially - type: ET3S-20,
power transformers, is based on a multi- - power: 20 kVA,
parameter analysis of the units under study. - rated voltage GN: 3 £ 400 V,
An overall assessment of a transformer may - rated voltage DN: 3 £ 20 V,
be carried out based on several parameters, - rated current GN: 17.1 A,
including its current significance in an - rated current DN: 333 A,
electric power system and its impact on - type of work: S1.
Mechanical vibrations of the transformer
model were measured with an ac-
celerometer type 752-10 by Endevko
company, which was attached to the core
with a magnet and the view of which is Fig.2 Transducer(a) and measuring
shown in Fig. 2a. Sensitivity of the amplifier(b)
measuring transducer was 1.021 mV/(m s2)
(for 100 Hz). The signal received by the Methodology
transducer was passed onto the input of a
low-noise measuring amplifier from During the measurements, the transformer
Nexus2693 family by the firm BrÄuel & under study was loaded with rated current
Kj½r, shown in Fig. 2b. In order to get using a water resistance making adjustment
separated from disturbances transferred by of the current values in the range from 0 to
the low-voltage net 230 V, the amplifying 340 A possible. The investigation was
system was supplied from the internal carried out in the stages: the first stage
battery source during the measurements. A contained analyses of the transformer
computer equipped with a measuring card vibrations and the acoustic pressure level at
type CH 3160 by the firm Acquitek and a packeted core, and the second stage
specialized AcquiFlex software were used referred to measurements at an unpacketed
for observation and registration of the core. Mechanical vibrations were registered
vibration signals. The measurements of the with a transducer placed on the core, and the
acoustic pressure level were taken with a acoustic pressure level was measured in the
meter type 945A by the firm SVAN. This distance of 1 m away from the transformer
appliance is used for taking measurements under study.
of the sound level with accuracy
corresponding to class 1 and the frequency Analysis of Result Obtained
analysis of the acoustic signals in the band 1
Hz{20 kHz. The measuring tool makes it In the result of the measurements taken, the
also possible to perform: the tone analysis, values of the corrected acoustic pressure
volume measurement, octave and tierce levels for two operation conditions of the
analysis, fast Fourier transform (FFT) transformer under study were determined.
analysis and detecting discrete tones of the Operation of a transformer with a properly
acoustic signal measured. Figure 3 shows pressed core is characteristic of the value of
the appearance of the meter used. the acoustic pressure level lower by 12.2 dB
than in the case when the core has become
loose. This difference in the values obtained
indicates a significant influence of the
construction and proper packeting of the
transformer core on the noise emitted into amplitude values of the particular frequency
surrounding. components. Bigger amplitudes correspond
to the results determined for the transformer
with the loose core. In order to determine
frequency ranges, based on which it is
possible to discover core damage in a
transformer, it is necessary to carry out
vibroacoustic investigations. The
measurement results of the mechanic
vibrations of the transformer under study are
Graph 1 The results of the FFT analysis of shown:
the acoustic pressure level around the trans-
former: (a) with the packeted core, (b) with
the unpacketed core.

Graph 2 Frequency spectra of transformer


vibrations: (a) packeted core, (b)
unpacketed
Chart 1 The results of the octave analysis of core.
the acoustic pressure level around
thetransformer: (a) with the packeted core, Amplitude values, determined based on the
(b) with the unpacketed core. measurement of the vibration acceleration,
differ both in the range of dominant
In order to examine the influence of the frequencies and in amplitude. In the case of
modelled core damage on the participation the loose core, a significant participation of
of the particular frequency components, the components for frequencies from the range
measurement of the acoustic level pressure from 0 to about 5 kHz can be observed.
was supplemented by an analysis in the
frequency domain, which was carried out by Summing-up
using a FFT and an octave analysis. The
results of the frequency analysis are shown An excessive value of the acoustic pressure
in Figs. 4 and 5. Analyzing the runs of the level occurring around transformers is a
frequency spectra as well as the column significant problem for both professional
diagrams showing the results of the octave power engineering and services involved in
analysis, it can be observed that environment protection [7, 8]. Over the
participations of the particular frequencies years the level of the acoustic pressure
are relatively constant and do not depend on emitted by power transformers into
the modelled core damage. Significant environment is not constant but is subject to
differences can be observed analyzing changes. This can be caused either by a
significant wear of cooling appliances or [3] T. Boczar, M. Lorenc, D. ZmarzÃly, in:
changes taking place in a transformer core. Proc. 14th Int. Congress on Sound
The works on noise reduction presently Vibration, Cairns (Australia) 2007, 1{8,
concentrate on seeking new technical Abstract 316, p. 1.
solutions, the aim of which is limiting the
value of the acoustic pressure level emitted [4] T. Boczar, S. Borucki, A. Cichon, Arch.
by such appliances as pumps or coolers. Acoust. 32 (Supplement), 291 (2007).
Increasing the noise level above the values
provided at the stage of a transformer [5] T. Boczar, S. Borucki, A. Cichon, Mol.
construction can be the cause of non- Quant. Acoust. 28, 13 (2007).
compliance with environmental standards.
Therefore it is vital that the acoustic [6] IEEE Standards, Test Core for Liquid-
pressure level be monitored during Immersed Distribution, Power and Regu-
periodical check-ups, especially around lating Transformers, IEEE Std. C57.12.90
high-power transformers. The research (1999).
results presented in this paper indicate a
significant influence of the core construction [7] Order of Environment Ministry since
on the value of the acoustic pressure level 29.07.2004 (Dz. U. since 13.08.2004)
occurring around a transformer. These (inPolish).
results prove that the assessment of the
transformer core condition should be an [8] T. Boczar, S. Borucki, A. Cichon, M.
indispensable element of a transformer Lorenc, Mol. Quant. Acoust. 28, 45 (2007).
diagnostics as potential failures can
influence not only technical parameters but
also increase the noise level emitted into
surrounding.

References

[1] A. Carlson, J. Fuhr, G. Schemel,


F.Wegscheider, ABB | Testing of Power
Transformers, Pro Print, DÄusseldorf 2003.

[2] T. Boczar, S. Borucki, A. Cichon, M.


Lorenc: in Proc. 37th Int. Conf.
andExhibition, Defektoskopie 2007, Praha
2007, Eds. M. Ko·renska, P. Mazal,
BrnoUniversity of Technology, Brno 2008,
p. 45.
Appendix
FACULTY OF MANUFACTURING ENGINEERING

BFF 3103: VIBRATIONS


SEMESTER 2, 2017/2018

TERM PAPER

MATRIC NO. NAME

FB15038 AZIRULSYAZWAN BIN JAAFFAR

FB15028 MUHAMMAD HUZAIFI BIN YUSNIMAN

FB15036 MOHAMMAD MAARIF BIN MOHD MAHFOZ

FA15090 AIMAN SHAFIQ BIN SHUHAIMI

FB15048 MUHAMMAD AZRI HARIZ BIN MD YAZID

FB15046 MUHAMMAD AKMAL BIN AZHAR

Das könnte Ihnen auch gefallen