1 CT FAN
Operate the fan and reduce
level from Level switch Once the testing is
Lube oil level low mm .Ensure that level swich is Fan trips staisfied, normalize the half yearly
isolated from gear box oil level switch
sump
Hammer near the switch
Vibration high mm/s 11 mm/s Fan trips
with a wooden piece as above
Page 1 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOP
Sequnce of Belt
Try to operte in reverse Belt does not operation- from farthest
Sequence check as above
sequence take start one to nearest of grzzly
hopper.
3 COMPRESSOR
Page 2 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOP
Page 3 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOP
Put AC driven pump on
auto by ensuring that
AC driven pump hydrant pressure is above 7
AC pump
starts at low Kg/cm2 6.5 kg/cm2.Take JP on manual quarterly
starts
pressure mode.Reduce the pressure
of hydrant below 6.5
kg/cm2
4 DM TRANSFER
Checked by Witnessed by
Page 4 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOP
Date date
Page 5 of 33
Interlock in
Tested date Due date service
Page 6 of 33
Page 7 of 33
Page 8 of 33
Page 9 of 33
Page 10 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
REMARKS/
Set actual RESULT frequency
SNO DESCRIPTION UOM METHOD OF TESTING ANY RE-
value value EXPECTED of checking
SETTING
Put STG on turning gear ,by
HAND TRIP TEST BY Turbine trip & Every
1 Trip pass vacuum protection, reset
MANUALTRIP ESV close opportunity
STG
REMOTE TRIP TEST BY PB
2 Trip as above as above as above
ON GOVERNER PANEL
Page 11 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
Put STG on turning gear
,normalize pass vacuum
protection, try to reset STG.
STG will not get
Otherwise, pull some vacuum
EXHAUST STEAM PRESS reset. In the
6 kg/cm2 -0.6 above trip value and reset the yearly
HIGH second case
STG. Now reduce vacuum by
turbine must trip
controlling ejector steam
pressuure to trip value. Note
the trip value
8 INLET STEAM TEMP LOW deg C 465 as above TURBINE TRIP yearly
TURBINE EXHAUST STEAM
9 deg C 120 as above TURBINE TRIP yearly
TEMP HIGH
TURBINE THRUST BRG IN-
10 deg C 105 as above TURBINE TRIP yearly
ACTIVE TEMP HIGH
TURBINE THRUST BRG
11 deg C 105 as above TURBINE TRIP yearly
ACTIVE TEMP HIGH
TURBINE FRONT BRG.TEMP
12 deg C 105 as above TURBINE TRIP yearly
HIGH
TURBINE REAR BRG.TEMP
13 deg C 105 as above TURBINE TRIP yearly
HIGH
REDUCTION GEAR PINION
14 deg C 105 as above TURBINE TRIP yearly
FRONT BRG TEMP HIGH
REDUCTION GEAR PINION
15 deg C 105 as above TURBINE TRIP yearly
REAR BRG TEMP HIGH
REDUCTION GEAR WHEEL
16 deg C 105 as above TURBINE TRIP yearly
FRONT BRG TEMP HIGH
REDUCTION GEAR WHEEL
17 deg C 105 as above TURBINE TRIP yearly
REAR BRG TEMP HIGH
Page 12 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
TURBINE REAR BRG OIL
18 deg C 75 as above TURBINE TRIP yearly
RETURN TEMP HIGH
TURBINE FRONT BRG OIL
19 deg C 75 as above TURBINE TRIP yearly
RETURN TEMP HIGH
REDUCTION GEAR BRG OIL
20 deg C 75 as above TURBINE TRIP yearly
RETURN TEMP HIGH
TURBINE AXIAL
21 mm ± 0.8 as above TURBINE TRIP yearly
DISPLACEMENT HIGH
TURBINE CASING / ROTOR +1.25,
22 mm as above TURBINE TRIP yearly
DIFF.EXPANSION HIGH -1.0
TURBINE FRONT SHAFT
23 micron 85 as above TURBINE TRIP yearly
VIBRATION HIGH
TURBINE REAR SHAFT
24 micron 85 as above TURBINE TRIP yearly
VIBRATION HIGH
REDUCTION GEAR PINION
25 micron 85 as above TURBINE TRIP yearly
SHAFT VIBRATION HIGH
REDUCTION GEAR WHEEL
26 micron 105 as above TURBINE TRIP yearly
SHAFT VIBRATION HIGH
GENERATOR FRONT SHAFT
27 micron 105 as above TURBINE TRIP yearly
VIBRATION HIGH
GENERATOR REAR SHAFT
28 micron 105 as above TURBINE TRIP yearly
VIBRATION HIGH
29 HOTWELL LEVEL HIGH-HIGH mm as above TURBINE TRIP yearly
30 GOVERNER HEAVY FALT TURBINE TRIP yearly
Reduce control oil pressure every 3
CONTROL OIL PRESSURE by switching off the pump or month
31 kg/cm2 TURBINE TRIP
LOW LOW by draining the transmitter/ /available
switch opportunity.
Page 13 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
every 3
Reduce LO pressure by by
LUB OIL HEADER PRESSURE month
32 kg/cm2 draining the transmitter/ TURBINE TRIP
LOW LOW /available
switch
opportunity.
Checked by Witnessed by
Date date
Page 14 of 33
Interloc
k in
Tested date Due date service
Page 15 of 33
Page 16 of 33
Page 17 of 33
Page 18 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
frequency
sl no Equipment interlock/ Permissive UOM set value Method of checking Actual value Remarks of
checking
Page 19 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
Now put other pump on auto
mode keeping the first pump
on condition. Ensure breaker
interlock
of stand by is racked out.
Check the following interlock
one by one.
Page 20 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
Close suction valve partly so
Suction valve open As above
that lt. sw . Gets disengaged
Suction DP Ok kg/cm2 Drain DP switch As above
Now put other pump on auto
mode keeping the first pump
on condition. Ensure power
interlock
fuse of stand by is taken out.
Check the following interlock
one by one.
Page 21 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
Stop indication should
Discharge valve come, once the checking is
lt. SW Open the discharge valve
close satisfied, normalize the
switch
Cold well level low mm Drain level transmitter As above
Now put other pump on auto
mode keeping the first pump
on condition. Ensure power
interlock Annually
fuse/ breaker of stand by is
out. Check the following
interlock one by one.
Page 22 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
SITE:
Stop indication should
Discharge valve come, once the checking is
lt. SW Open the discharge valve
close satisfied, normalize the
switch
Cold well level low mm Drain level transmitter As above
Now put other pump on auto
mode keeping the first pump
on condition. Ensure power
interlock Annually
fuse/ breaker of stand by is
out. Check the following
interlock one by one.
Page 23 of 33
Interlock in
Tested date Due date service
Page 24 of 33
Page 25 of 33
Page 26 of 33
Page 27 of 33
Page 28 of 33
PROTECTION AGAINST GENERATOR FAULT
Current Related Fault Relay name setting
Instantanous phase Over current 50
Residual Directional over current 67N
Stator earth fault
Rotor earth fault
Generator Phase Differential current 87
Zero seq ( ground Zero) Generator Phase
Differential current 87 GD
Negative seq over Current 46
Instantanous neutral Over current 50N
Inverse time Neutral Over current 51N
Three phase inverse time over current with voltage
restrained 51V
Voltage related Fault
Phase Over voltage 59
Neutral Over voltage 59N
Phase under voltage 27
Third harmonic under voltage 27TN
Third harmonic voltage differential 59D
BOILER TRIP.
Once the checking
Reduce drum level through level Trip Indication
STEAM DRUM LEVEL is satisfactory,
1 transmitter(s) . Ensure that of ID, FD, PA &
LOW LOW normalize the level
transmitter(s) are isolated from drum CF should be in
transmitter (s)
DCS
Page 30 of 33
THERMAX LTD.
PLANT TRIP INTERLOCK CHECKING REPORT
BOILER-1
PA FAN , Coal
feeder TRIP
5 FD FAN TRIP Stop command for FD fan from DCS
indication in
DCS
Checked
Witnessed by
by
Date date
Page 31 of 33
Frequency of Interlock in
checking Tested date Due date service
half yearly/ on
opportunity
as above
as above
as above
Page 32 of 33
as above
as above
as above
as above
Page 33 of 33