Beruflich Dokumente
Kultur Dokumente
Engineering Guide
Terminal Units
Terminal Units
Engineering Guide
F-3
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
Figure 16: Bypass cooling with auxiliary perimeter heating (Heating is not in the
airflow, nor from RTU)
Dead Band
Rooftop cfm
Max. Cooling
Air Volume
Min. Cooling
Tset-point zone cfm
Tset-point
Zone calls for less cool air Zone calls for more cool air
F-5
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
Air Volume
Min. Cooling
Tset-point zone cfm
Tset-point
Zone calls for less cool air Zone calls for more cool air
Tset-point
Zone calls for less cool air Zone calls for more cool air
Max. Heating
Air Volume
Min. Heating
Tset-point
Zone calls for less cool air Zone calls for more cool air
Figure 25: Dual duct terminal with a constant zone supply air volume and zero
CONTROL TIP minimum cooling and heating airflows
Dual duct systems have the potential Dead Band
to maintain high levels of occupant
comfort, but may not be as energy Heating Cooling
efficient as other design approaches. Constant cfm
The inefficiency in design is due to
the continuous mixing of warm and
Air Volume
Tset-point
Zone calls for heating Zone calls for cooling
F-7
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
Air Volume
cooling air volume. Alternative sequences
that allow the fan volume to vary based on Stage 2
zone thermostat call for cooling or heating Stage 1
are sometimes used in an attempt to Electric Reheat
minimize the potential for over-supplying
air to the occupied zone. Min. Primary Air
One of the main benefits of the series fan
powered terminal is the consistent delivery Tset-point
of the same air volume to the occupied zone. Zone calls for heating Zone calls for cooling
Many occupants prefer the consistent air
movement and consistent ambient sound
levels.
One weakness in a series fan powered Figure 30: Constant or series FPU with ECM motor and variable fan volume, minimum
terminal is that they can generate significant primary air, and 3 stage electric reheat
levels of sound power, in particular radiated
sound. Care should be taken to not select Dead Band
too large of a fan capacity and to locate
the unit over an unoccupied space in
the building such as a closet or hallway. Full Volume
To minimize potential noise complaints Re-circulated Air cfm to Zone
Max. Primary Air
most designers prefer to limit the overall Stage 3 Max. Cooling
Air Volume
F-9
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
No Primary Air
Re-circulated Air
do this because there is a slight potential for
the blower to spin backward due to the flow
of primary air through the blower when the
motor is not in operation. It is possible that
if the blower is spinning backward, when
power is applied to the motor, the blower Reheat
will continue to operate with the reversed
rotation. This reverse operation will result
in lower air volumes, potential noise issues Tset-point
and motor overheating. Zone calls for heating
Figure 33: Constant or Series FPU, Min. Primary Air, Electric Reheat, Night Set
Back/Unoccupied Mode/Operation
Dead Band
Reheat Air Flow to Zone,
Re-circulated Air
No Primary Air
Stage 3
Stage 2
Stage 1
Reheat
Tset-point
Zone calls for heating
Figure 34: Constant or series FPU with ECM motor and variable fan volume, minimum
primary air, and hot water reheat
Dead Band
Constant
cfm to Zone Re-circulated Air
Air Volume
Hot Water
Reheat
Tset-point
Zone calls for heating
motor.
Due to access requirements for high voltage
electrical enclosures where the connections
for the terminal controls and motor are Reheat
contained as well as fused (if present), it is
recommended that the designer consider Min. Primary Air
using a door interlock switch. Most local
codes require a main disconnect and the Tset-point
integral interlock switch is an economical Zone calls for heating Zone calls for cooling
choice. Also, most local codes require a
minimum of 3 ft clearance in front of a high
voltage enclosure. Care should be taken
when selecting an installation location for
the terminal unit.
CONTROL TIP
A standard height parallel fan powered
terminal has the blower/motor assembly When using a parallel FPU for reheat when the central air handler is not in operation,
installed with the blower inlets and the it is advised to ensure that the control sequence closes the primary valve prior to
motor oriented in the horizontal position. turning on the fan, particularly when using electric reheat. The issue is that the
The standard height parallel fan powered fan discharge air will take the path of least resistance and if the primary air valve
terminal is typically no taller than 20 in. is open, without the air handler in operation, there is a chance that some of the
fan discharge air will not go through the electric reheat coils and then to the zone,
A low profile construction style is available
but instead will discharge through the primary air valve. If there is not sufficient
with a typical height no taller than 12.5 in.
airflow across the electric reheat coils, nuisance tripping of the electric reheat
Due to the height restrictions, the typical
thermal limits is a distinct possibility.
low profile parallel fan powered terminal
will have the blower motor installed such
that the motor and blower intake opening
are oriented to the bottom of the terminal select too large of a capacity and to locate demonstrated that many of the energy
housing. the unit over an unoccupied space in savings due to the intermittent fan cycling
The overhead parallel fan powered terminal the building such as a closet, or hallway. are offset and in fact may be significantly
unit typically has bottom access panels to Most designers prefer to limit the overall less than the energy loss associated with
allow maintenance. airflow capacity of the parallel fan powered the conditioned primary air leaking into the
One weakness in a parallel fan powered terminal to no more than 3,000 cfm, with return plenum space through the back draft
terminal is that when the fan is in operation, many preferring no greater than 2,500 cfm damper and the mixing chamber housing.
they can generate significant levels of sound depending upon the type of occupancy and It is recommended that if leakage through
power, in particular radiated sound. Also, building construction. the back draft damper is of concern that
when the fan cycles on and off, there is a Another weakness in parallel FPUs is the the designer either use a different terminal
change in the ambient background noise leakage of primary air through the back draft type, or require that the leakage from the
that occupants can become aware of and damper on the fan and the mixing chamber terminal housing as an assembly be limited
in some cases, may lead to complaints housing. Recent research by ASHRAE and and certified to some specified amount.
about noise. Care should be taken to not Texas A and M University (Furr, 2007) have
F-11
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
commonly used in exterior zones where Max. Primary Air cfm to Zone
Re-circulated Air
the heating and cooling loads vary. They Max. Cooling
Air Volume
Stage 3
are also used in buildings to provide heat
during periods of un-occupancy where it is Stage 2
desirable to leave the central air handling
system off. Electric Reheat Stage 1
Air
from minimum airflow volume which is
typically determined by the minimum zone
fresh air volumes required for the zone Reheat
occupancy type. The maximum cooling
airflow rate is typically determined by the Min. Primary Air
maximum anticipated cooling load for that
zone. As the demand for cooling varies, the Tset-point
volume of primary air will vary. When reheat
is activated, the fan will energize and, the Zone calls for heating Zone calls for cooling
hot water coil or electric reheat coil will be
activated when the zone temperature falls
below the lower dead band limit.
It is possible to operate the parallel FPU with PRODUCT TIP
a variable fan volume during reheat as is Certified leakage in parallel FPUs is
shown in Figure 39. This is not a common not standard construction and would
sequence, but there has been some interest require special manufacturing. This
in this as a way of saving fan energy. is not a standard unit offered by any
manufacturer.
related controls.
Optional accessories include water reheat Induced Plenum/Return Air
and electric reheat and various liner types.
The sequence of operation is shown in Reheat
Figure 42. The primary air volume is Min. Primary Air
regulated by closing or opening the primary
induction aperture, with the volume of Tset-point
primary air based on the zone cooling
requirements. The supply air to the zone is Zone calls for heating Zone calls for cooling
a mixture of the primary air and the induced
return air. The amount of induced return
air is regulated by the return air damper
and will vary between full open at the set-
point to full close at the peak cooling call.
Optional reheat will activate when the zone
temperature drops below the set-point.
F-13
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
Re 0.0002 Microbar
60
units, the sound pressure level of octave
bands two through seven (125 to 4000 Hz) 50
should be considered.These pressure levels
are plotted on a standard NC curve form 40
(Figure 43). The highest pressure level
when measured against the NC curves, 30
regardless of frequency, determines the
NC of the unit. 20
Table 1 illustrates the ASHRAE 10
recommended space NC values for many 63 125 250 500 1000 2000 4000 8000
commercial air conditioning applications Approximate Threshold of Band Center Frequencies, Hz
(ASHRAE, 2007). Terminal units should be Hearing for Continuous Noise
selected so that the tabulated NC levels
are within these design goals. Most
manufacturers’ catalog data for terminal
units lists the sound power levels at various
operating conditions. To determine the
actual sound pressure level in the space,
we must evaluate which attenuation factors
are present in the system and subtract these
values from the manufacturers’ sound power
levels. The Air-Conditioning, Heating and
Refrigeration Institute (AHRI) has published
“A Procedure for Estimating Occupied
Space Sound Levels in the Application of Air
Terminals and Air Outlets," known as AHRI
Standard 885‑2008.This standard forms the
basis for the sound estimation guidelines
presented on the following pages. These
guidelines are offered for typical conditions.
For a more detailed analysis, refer to AHRI
Standard 885-2008 and the ASHRAE HVAC
Applications Handbook (ASHRAE, 2007)
RC(N)
Room Types
(QAI[5 dBa,b)
Private residences 25-35
Hotels/Motels
F-15
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
F-17
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
Table 8: Insertion Loss of Unlined and Lined Elbows with Turning Vanes, dB
Octave Band Mid Frequency
Model Type Duct Diameter
2 3 4 5 6 7
5-10 [100-125] 0 0 1 4 6 4
11-20 [260-700] 1 4 6 4 4 3
Unlined Duct
21-40 [710-1000] 4 4 6 4 4 3
41-80 [1010-2000] 4 6 6 4 4 3
5-10 [100-125] 0 0 1 4 7 7
11-20 [260-700] 1 4 7 7 7 7
Lined Duct
21-40 [710-1000] 4 7 7 7 7 7
41-80 [1010-2000] 4 7 7 7 7 7
Reference • AHRI Standard 885-2008, Appendix D, Table D12, page 51
• 2007 ASHRAE Handbook, HVAC Applications, Chapter 47, Table 19
Space Effect
Figure 47: Tee Fitting Loss Mean Duct Width = D/2
A sound source terminating in the occupied
space is assumed to be a point source. The
calculation of the sound pressure level Lp
in rooms for the entering sound power level
Lw can be accomplished using the Schultz
equation:
Lp = 10 log (10Lp1/10 + 10Lp2/10 + ... 10Lpn/10 ) Table 10: NC versus Sound Pressure Level (dB]
F-19
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
Multiple Sound Sources Table 12: Room Sound Attenuation For an Outlet Array, 4 Outlets
All outlet sound data is for a single source. Octave Band Mid Frequency
Allowances must be made for multiple Ceiling Height Ceiling Height
outlets when this occurs in a space since the 2 3 4 5 6 7
overall noise level may be the resultant of 200 ft2 [20 m2] 2 3 4 5 6 7
more than one outlet or sound source. One
300 ft2 [30 m2] 8 ft [2.4 m] 3 4 5 6 7 8
way to calculate the sound pressure level
ENGINEERING GUIDE - TERMINAL UNITS
F-21
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
If a liner other than 1 in. fiberglass is Table 16: Adjusted attenuation factors for solid metal liner
selected, the designer is urged to consider Large box, >700 cfm [330 L/s]
the impact that this will make on the 2 3 4 5 6 7
estimated sound values in the space. It is Octave Band Mid Freq, Hz
125 250 500 1000 2000 4000
suggested that for liner types other than Lining Reduction
1 in. dual density fiberglass (which is the 0 0 0 0 0 0
(solid metal liner, 15 x 15 in. duct)
‘standard construction’), attenuation factors Power Splits (3 diffusers) 5 5 5 5 5 5
ENGINEERING GUIDE - TERMINAL UNITS
should be adjusted to reflect this change. For End Reflection (8 in. duct) 9 5 2 0 0 0
instance, if the design intent is a terminal
Flex Duct Reduction (8 in. duct) 6 10 18 20 21 12
unit with solid metal liner (no exposed
insulating material) then the standard AHRI Environmental Adj. Factor 2 1 0 0 0 0
Standard 885-2008, appendix E attenuation Room Attenuation 2400 ft3 5 6 7 8 9 10
factors for lined ductwork downstream of Total Attenuation 27 27 32 33 35 27
the terminal unit should not be used. If
the attenuation factors are not adjusted by
removing the estimated absorption of the Table 17: Adjusted attenuation factors for fiber free foam liner
fiberglass liner, the actual sound values in Large box, >700 cfm [330 L/s]
the occupied space will vary significantly 2 3 4 5 6 7
from the estimate provided by the Appendix Octave Band Mid Freq, Hz
125 250 500 1000 2000 4000
E attenuation factors and may lead to an Lining Reduction
0 1 0 2 3 2
overestimate of how much sound power will (fiber free foam liner, 15 x15 in. duct)
be absorbed by the ductwork. This can lead Power Splits (3 diffusers) 5 5 5 5 5 5
to loud spaces. End Reflection (8 in.duct) 9 5 2 0 0 0
Discharge Sound Attenuation Factors Flex Duct Reduction (8 in. duct) 6 10 18 20 21 12
For Alternative Liners 2 1 0 0 0 0
Environmental Adj. Factor
For liner types such as foil faced fiberglass Room Attenuation 2400 ft3 5 6 7 8 9 10
liner, fiber free liner, or solid metal liner on
Total Attenuation 27 28 32 35 38 29
single duct, the attenuation factors used for
estimating the sound values in the space are
modified by using the attenuation factors Table 18: Price SDV, 12 in. single duct with 2000 cfm air volume
shown in tables 16 and 17. The attenuation Pressure drop across terminal unit, in. w.c.
Discharge NC Values
factors values for the fiber free foam are 0.5 1.0 1.5 2.0 3.0
not generally available and are shown for Using AHRI 885-2008, Appendix E,
<20 23 27 31 35
illustration purposes only as they are from 1 in. fiberglass 15 x 15 in. duct
only one brand/type of foam insulation. Using adjusted factors for solid metal 30 36 40 43 46
Due to different materials used in the Using adjusted factors for fiber free foam 20 28 32 35 40
manufacturing of the foam insulation liner,
it is recommended that the designer use
the attenuation factors for solid metal for
all liner types other than 1 in. fiberglass.
As an example, three different liner types
are explored for a large terminal unit.
The discharge sound attenuation factors
are shown by type of factor. In tables 15,
16 and 17, it is easy to see that the solid
metal liner has the lowest attenuation of
discharge sound, and that the fiber free
foam falls between the standard fiberglass
liner and the solid metal in discharge sound
attenuation. This difference in attenuation
is magnified when the terminal unit is
operating with pressure drops over 1 in.
w.c. (see Table 18).
PRODUCT TIP
The attenuation for fiber free foam
liners is based on the data from one
manufacturer of this product type, and
may not be available from all vendors.
To be safe, it is suggested that the
designer use the attenuation factors
for solid metal liners.
Radiated Sound For Alternative Liners Table 19: Price SDV, 12 in. single duct with 2000 cfm air volume
For liner types such as foil faced fiberglass Pressure drop across terminal unit, in. w.c.
Radiated NC Values
liner, fiber free liner or solid metal liner on 0.5 1.0 1.5 2.0 3.0
terminals, the attenuation factors used for Using AHRI Standard 885-2008, Appendix E
<20 24 28 31 33
estimating the sound values in the space 1 in. fiberglass 15 x 15 in. duct
are the same for standard fiberglass. The Using Solid Metal liner <20 <20 20 23 27
only absorbing factors in the sound path Using Aluminum Foil Faced Insulation 20 26 29 31 35
1. Select a terminal which will operate in the mid to low area of its 5. Flex duct and fiberglass duct board allow significantly greater
operating range. Lower fan speeds produce lower sound levels. breakout noise than metal duct and should be avoided. Flex
2. Design duct systems to provide adequate but not excessive duct can also generate sound if bending, folding or sagging
static pressure at the primary air inlet. Excess static pressure take place.
generates noise. 6. Locate terminal units in the largest plenum volume available
3. Locate terminals above non‑critical areas like corridors, closets for increased reduction of radiated noise.
or file areas. This will isolate critical areas from potential 7. A ceiling with high transmission loss will help reduce radiated
sources of radiated noise. sound.
4. Locate terminal to allow maximum length of lined discharge 8. Avoid locating terminals near return air openings. This allows a
duct work. Consider a larger number of smaller diffusers to direct path for radiated noise to enter the space.
minimize discharge sound. 9. The use of acoustically lined flex duct on the diffuser will reduce
discharge sound.
F-23
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
Catalog Highlight 1 – Updated Discharge Sound with Duct longer meet their room NC specification based on the new catalog
End Reflection Corrections values. Remember that the terminal is not actually any louder than
Discharge sound power levels for all Price terminals have been before and the same noise level will be heard or measured in the
updated to include duct end reflection corrections to comply with field. Relaxing the room NC specification may be the best option.
the 2011 version of ANSI/AHRI Standard 880 – Performance Rating Otherwise a quieter terminal will need to be selected which usually
of Air Terminals. carries a cost premium.The table below illustrates how the updated
Price single duct terminal (SDV) NC values compare with previous
How Does This Affect Data? cataloged values. Note that the small size units increase the most.
Discharge Sound Power Levels
Duct end reflection is a calculated value that is dependent on octave Noise Criteria (NC) Table
band center frequency and equivalent discharge duct diameter.The Size cfm Old NC New NC
correction is highest at low frequencies and small discharge duct 225 27 34
4
sizes. As a result, the new published discharge sound power levels
will be higher than previous levels, particularly for small terminals 6 400 23 30
in the low octave bands. For an example, see the following table of 8 700 24 30
duct end reflection corrections for Price single duct terminal model 10 1100 24 26
SDV. The updated catalog sound power levels will be higher than
12 1800 27 31
previous by the decibel amount tabulated below.
14 2500 29 31
Octave Band Center Frequency 16 3500 30 33
Unit Size
125 250 500 1000 2000 4000 24x16 6000 39 41
4 8 3 1 0 0 0
5 8 3 1 0 0 0 Comparing Data
6 8 3 1 0 0 0 According to the deadline imposed by AHRI, manufacturers have
7 7 3 1 0 0 0 until January 1, 2013 to catalog discharge sound power levels with
duct end reflection corrections. Until that time it will be important
8 7 3 1 0 0 0
to understand if cataloged discharge performance data includes
9 6 2 1 0 0 0 duct end reflection corrections or not. Discharge sound power level
10 6 2 1 0 0 0 or NC level comparisons cannot be made between manufacturers
5 2 0 0 0 0 unless both are based on the same calculation procedure.
12
14 4 1 0 0 0 0
16 3 1 0 0 0 0
24x16 2 1 0 0 0 0
As stated on the previous page, the new AIO catalog provides Catalog Highlight 2 – Application Data with Embedded
discharge sound data with duct end reflection corrections applied Certified Ratings
for all Price terminals. This fact is clearly stated in the performance To comply with AHRI Standard 880-2011, manufacturers must
notes on each page of the performance data, and can be seen in rate their equipment at ‘standard rating conditions’ as specified
the example below. by AHRI. Data based on these conditions are defined as Standard
Ratings.The Standard Ratings for Price certified products are listed
Performance Notes: with the performance data tables for each certified product and
Performance Notes:
1. Test data obtained in accordance with AHRI Standard 5. AHRI certified data is highlighted in blue. All other data
880-2011 and ASHRAE Standard 130-2008. are application ratings.
2. Sound power levels include duct end corrections per 6. Application ratings are outside the scope of the AHRI
AHRI Standard 880-2011. Please refer to page F25 for 880 Certification Program.
more details. 7. Asterisks (*) indicate minimum static pressure of the
3. Airflow given in L/s and cfm. unit exceeds the minimum operating pressure across
4. Pressure is given in Pa and in.w.g. the unit.
F-25
© Copyright Price Industries Limited 2014. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Terminal Units
Engineering Guide
References
AHRI (2001). Standard 410-2001—Forced circulation air-cooling and air heating coils. Arlington,VA: American
Heating and Refrigeration Institute.
AHRI (2008a). Standard 880-2008—Performance rating of air terminals. Arlington,VA: American Heating and
Refrigeration Institute.
AHRI (2008b). Standard 885-2008—Procedure for estimating occupied space sound levels in the application
ENGINEERING GUIDE - TERMINAL UNITS
of air terminals and air outlets. Arlington,VA: American Heating and Refrigeration Institute.
ASHRAE (2004). Standard 62.1-2004—Ventilation for acceptable indoor air quality. Atlanta, GA: American
Society for Heating, Refrigerating and Air Conditioning Engineers.
ASHRAE, (2007). ASHRAE handbook—HVAC applications. Atlanta, GA: American Society of Heating,
Refrigeration and Air-Conditioning Engineers.
ASHRAE, (2008a). ASHRAE handbook—HVAC systems and equipment. Atlanta, GA: American Society of
Heating, Refrigeration and Air-Conditioning Engineers.
ASHRAE (2008b). Standard 170-2008—Ventilation of health care facilities. Atlanta, GA: American Society for
Heating, Refrigerating and Air Conditioning Engineers.
ASHRAE (2008c). Standard 130-2008—Methods of testing air terminal units. Atlanta, GA: American Society
for Heating, Refrigerating and Air Conditioning Engineers.
ASHRAE, (2009). ASHRAE handbook— Fundamentals. Atlanta, GA: Atlanta, GA: American Society of Heating,
Refrigeration and Air-Conditioning Engineers.
Avallone, E. A., Baumeister III, T., eds. (1987). Marks standard handbook for mechanical engineers (9th ed.).
New York, NY: McGraw-Hill Book Company.
Clifford, G. (1984). Modern heating, ventilating and air conditioning. Englewood Cliffs, NJ: Prentice Hall.
E.H. Price (2007). Catalog 6, volume 3: Price terminals. Winnipeg, MB: E.H. Price Ltd.
Furr, J. C., O’Neal, D. L., Davis, M., Bryant, J. A., & Cramlet, A. (2007). Phase 1 Final report for ASHRAE RP-
1292: Comparison of the total energy consumption of series versus parallel fan powered VAV terminal
units. Atlanta, GA: American Society of Heating, Refrigeration and Air-Conditioning Engineers.
International Agency for Research on Cancer (IARC) (2001). Press release No. 137: IARC monographs on the
evaluation of carcinogenic risks to humans: Man-made vitreous fibres. Lyon, France: WHO/IARC.
Janis, R. R., & Tao, W. K. Y. (2009). Mechanical and electrical systems in buildings (4th ed.). Upper Saddle
River, NJ: Pearson Prentice Hall.
Oliver, P., Dyck, A. & Sipes, J. (2011). Close coupling duct silencers with terminal units [unpublished study].
Winnipeg, MB: E.H. Price Ltd.
Price Industries (2011). Price engineer's HVAC handbook—A comprehensive guide to HVAC fundamentals.
Winnipeg, MB: Price Industries Limited.
Sun, T (1994). Air handling system design. New York, NY: McGraw-Hill Book Company.
U.S. Department of Health and Human Services, Agency for Toxic Substance and Disease Registry (ATSDR)
(2004). Toxicological profile for synthetic vitreous fibers. Washington, D.C.: ATSDR.
U.S. National Academy of Sciences, Committee on Toxicology (2000). Review of the U.S. Navy’s exposure
standard for manufactured vitreous fibers. Washington, D.C.: National Academy Press.
Underwriters Laboratories (1995). UL 1995—Heating and cooling equipment. Camas, WA: Underwriters
Laboratories Inc.