Beruflich Dokumente
Kultur Dokumente
a r t i c l e i n f o a b s t r a c t
Article history: This paper discusses the development of a new methodology for measurements of earth resistance and
Received 29 April 2016 touch and step voltages in ground mesh of urban power substations. The main challenge of the work is
Received in revised form to find a feasible solution for performing earth resistance measurements from short distances, given that
26 December 2016
this is the condition actually found in the majority of urban substations. A test field with four ground
Accepted 17 January 2017
Available online 22 January 2017
mesh units of different geometric configurations was implemented and used for performing numerous
measurement tests. Based on all the data collected and analysis of the measurement results, a mathemat-
ical model was developed to estimate and predict the correct distance in order to obtain earth resistance
Keywords:
Grounding measurements from short distances, the PRED Method – Polynomial Regression from Database Method.
Earth resistance A discussion of the proposed method, as well as analysis of its accuracy and susceptibility to external
Touch and step voltage interference is performed, in addition to its validation in real substations, so as to prove the efficiency
Power system measurements and applicability of the proposed method.
Substation protection © 2017 Elsevier B.V. All rights reserved.
1. Introduction tests, the fall-of-potential method is widely applied for almost all
types of grounding systems [1–6]. However, the fall-of-potential
Obtaining grounding resistance values is a major factor in the method and its regulatory procedures require certain conditions
analysis of electrical safety in electrical substations. This informa- that are often difficult to obtain for substations in operation in the
tion is considered essential, not only to maintain a low impedance electric power system, especially in urban environments. As a rule,
path for the protection of the electrical system in any outbreak, it is necessary a distance of approximately 4–10 time the greater
but also to ensure that the potential increase on the ground does diagonal (D) of the mesh for the proper positioning of the current
not reach levels above the limits set for touch and step voltages in electrode (dA) and 2–6 time D for the placement of the potential
substations. electrode (dP) (sometimes referred as 62% rule). This measure-
In view of its fundamental importance, it is possible to histor- ment procedure is often infeasible, either for operational reasons
ically observe a major concern of the scientific community and or for practical reasons in urban substations, given the extent of
engineers in obtaining measurements that are able to set the cor- cables and physical obstacles at measuring points. In an attempt to
rect value of the grounding system resistance with a high degree of overcome the above-mentioned aspects, some alternative methods
accuracy [1–9]. These methods are often the subject of work for the have been adapted, using other electric power system structures as
establishment of technical safety standards, with well-established auxiliary electrode, for example, grounded transmission line tow-
protocols and measurement methods [11–13]. The ANSI/IEEE Std ers and other substations grounding meshes. In these cases, the
81 [11] is the main Guide for Measuring Earth Resistivity, Ground distances can be very long and measurements may suffer from the
Impedance, and Earth Surface Potentials of a Ground System. influence of external factors (e.g. electromagnetic interference due
There are several methods for measuring resistance of the to coupling with transmission lines). So either the assessments are
ground electrode system. Among them, as verified in many field made providing incorrect values, which contradicts safety, or the
measurements end up not being performed.
In this paper, we propose an effective method for the evalua-
∗ Corresponding author.
tion of earth resistance, and touch and step voltages within urban
E-mail addresses: raizer@eel.ufsc.br (A. Raizer), wilson.valente@ifsc.edu.br
substations in order to contribute with this area of research and
(W. Valente Jr.), vilson.coelho@vlc.eng.br (V.L. Coelho). development (R&D). It employs a mathematical model based on
http://dx.doi.org/10.1016/j.epsr.2017.01.025
0378-7796/© 2017 Elsevier B.V. All rights reserved.
112 A. Raizer et al. / Electric Power Systems Research 153 (2017) 111–118
2. Literature review
Tagg’s Method, also recommended by IEEE Std. 81-2012 [11], PPT /CP = −0.1242u3 + 0.2339u2 − 0.3049u + 0.738 (1)
is based on the work developed by Tagg [1] since 1970, and also
known as the “slope” method. In this method, uniform resistivity From this mathematical approximation, it is possible to perform
assumptions of the soil and representation of the ground elec- the extrapolation of Tagg’s method for applications in near distance
trode system as an equivalent hemispheric electrode are used. situations, and frequently encountered in practical evaluations. In
Additionally, this method allows performing the measurement at Fig. 1, original Tagg’s method [1] is shown by the solid line, while
near distances, by introducing the correction factor to the fall-of- the Extended-Tagg Method is shown by the dashed red line. This
potential procedure. allows the use of Tagg’s method for analysis of more near distance
In general, Dr. Tagg’s slope method [1] can be applied from the measurements, which is the main goal of this paper.
following protocol measures [11]:
3. Formulation of the proposed method (PRED)
a Choosing of a convenient starting point for linear measurements
and the selection of a suitable distance for the positioning of the The proposed method, denominated PRED method (Polynomial
current electrode (dA ). Regression from Database), was developed from a series of exper-
b Measurement of three resistance values R1, R2, R3 inserting the imental results considering the parametric assessment of dA and
potential electrodes (dP ) on the distance of 0.2 dA , 0.4 dA , and 0.6 dP and subsequent analysis of the measurement database. This
dA , respectively. method presented a different approach from the other works found
c Calculation of the inclination variation coefficient () using the in the technical literature, but can also be employed in order to pre-
equation: = (R3 − R2)/(R2 − R1). dict the correct probe placement for resistance measurement at
A. Raizer et al. / Electric Power Systems Research 153 (2017) 111–118 113
10 dA/D:
9 Mesh 1 6
Fig. 2. CT UFSC test site – Lat. 27◦ 40 52 , Long. 48◦ 32 11 . 5
8 4
7 3
6 2
1
5
R (p.u.)
0.9
4 0.8
3 0.7
0.6
2 0.5
1 0.4
0.3
0 0.2
0.2 0.4 dP/dA 0.6 0.1
3.5 dA/D:
Fig. 3. Grounding mesh 1: 10 m × 10 m. Mesh 2 6
3 5
4
near distances. The basic formulation is presented in this section, 2.5 3
and all validation tests will be presented latter. 2
2 1
R (p.u.)
0.9
3.1. Survey of experimental data 1.5 0.8
0.7
1 0.6
A test site was built for data collection (CT UFSC) with 4 ground- 0.5
ing meshes of different geometries (10 × 10 m, 5 × 10 m, 2.5 × 10 m, 0.5 0.4
5 × 5 m,) in a lot within the Agricultural Sciences Center of Fed- 0.3
0 0.2
eral University of Santa Catarina – UFSC, far enough away and free 0.2 0.4 dP/dA 0.6 0.1
from external interference, as shown in Fig. 2. The resistivity and
soil stratification parameters in this test site were systematically Fig. 6. Typical resistance versus potential probe spacing – mesh 2.
monitored so as to control their properties conditions during the
tests.
In this piece of land, the 4 grounding meshes were built with tances is the definition of equations or analytical models in order
bare copper wire, of medium hardness, 95 mm2 , and compression to correct the error due to the use of electrodes in nearby regions.
type connectors. Fig. 3 shows the geometric configuration of the With the PRED method, this is performed analytically, through lin-
10 × 10 mesh, buried at 0.5 m from the surface. The other meshes ear regression of all parametric measurement results, as shown
follow a similar configuration and were built spaced apart on the below.
available lot. The graphs in Figs. 5–8 show the behavior of the measured val-
After the implementation of the test site, a series of resistance ues, in p.u. of the normative theoretical value (Tagg Method [11])
measurement tests were performed, so as to form a database with for dP values equal to 20, 40 and 60% of dA . The dA values were
characteristic information of the ground meshes. Such tests follow used between 6D and 0.1D, where D is the greatest diagonal value
the configuration of the fall-of-potential method (IEEE Std 81) [11] of the analyzed mesh. By observing the graphs, one can see that
presented in Fig. 4. The systematic variation of the dP and dA dis- for the dP interval between 0.2dA and 0.6dA , the typical resistance
tances, using parametric assessment, allows the evaluation of the curve is approximately a straight line. By using the linear regres-
grounding resistance influence of reference electrodes, which is the sion techniques, it is possible to determine the linear and angular
main focus of this work. coefficients of the lines for the different values of the dA /D ratio.
For each set of measurements performed for the same dA value,
3.2. Analytical data treatment the dP for R equal to 1 p.u. was determined. The graph in Fig. 9
shows the behavior of the dP , values for R = 1 p.u., due to the differ-
It is understood that, as performed by Tagg in his work [1,2,11], ent spacing of the current electrode. A strong correlation is noticed
the main challenge in obtaining grounding values for short dis- between the values toward a line with a logarithmic tendency.
114 A. Raizer et al. / Electric Power Systems Research 153 (2017) 111–118
3.5 dA/D:
Mesh 3 6
3 5
4
2.5 3
2
2 1
R (p.u.)
0.9
1.5 0.8
0.7
1 0.6
0.5
0.5 0.4
0.3
0 0.2
0.2 0.4 dP/dA 0.6 0.1
3 dA/D:
Mesh 4 6 4. Measurement of earth surface potentials
2.5 5
4 Traditionally, the analysis of touch and step voltages is
2 3
2 performed from measurement procedures and equipment in accor-
1 dance with well-established standards [11,13].
1.5
R (p.u.)
50 current of the mesh and VR the real voltage (step and touch).
40 Therefore, the main result of this test is the relation between the
30 touch or step voltage values and the test current, which represent
such voltages referred to a unitary current, or to a touch and step
20
“resistance”.
10
0 4.1. Measuring earth surface potentials by PRED method
0 2 4 6 dA/D 8
In the mesh potential measurement test, the ground terminal of
Fig. 9. Behavior of voltage probe spacing (dP ) as a function of the ratio of the current
probe spacing and the major diagonal of the ground grid (D). the voltmeter is connected to the potential electrode (PP ) located
at a dP distance from the mesh, and the current electrode (CP ), posi-
tioned at a dA reference distance, it is connected to the generator
and center point of the grounding mesh, in a procedure similar to
3.3. Analytical expression of PRED method the configuration of the fall-of-potential method (Fig. 4).
In this specific test, measurements were performed for various
In view of the analysis performed in the previous section (Fig. 9), dA distances, and the dP distances were determined according to
it is seen that the logarithmic Eq. (2) can determine with a certain the PRED method.
degree of accuracy the relative distance between the potential elec- By means of this method, the maximum touch and step voltages
trode and the current electrode for a determined distance between can be estimated indirectly, using the mesh potential curve and the
the current electrode and the mesh. application of Kirchoff’s Law in the measurement circuit. Just like
the traditional method, the results refer to the test current. Further
d
A on Eq. (2) is also applied.
dP (R) = 0.14 ln + 0.41 (2)
D
5. Validation tests of the proposed method
This equation can be useful for measurements with small val-
ues of dA , where it is not possible to obtain a typical behavior in This section presents the validation results of the Extended Tagg
determining the resistance curve. Method [2] and PRED Method, when compared to the standard
A. Raizer et al. / Electric Power Systems Research 153 (2017) 111–118 115
other trials, and considering all different mesh sizes in this survey.
Therefore, it is observed that at distant placements of dA the per-
centage of error between the presented methods is usually less than
1%, and quite similar to the reference standard at hemispherical
condition [11].
Table 1 Table 2
Measurement of resistance values and error estimate (STANDARD Method, Extended Measurement of resistance at urban substations (PRED Method).
Tagg Method, and PRED Method).
Test dA /D dA R Reference PRAD Method
Test dA/D dA Standard Method Extended PRAD Method dP /dA R Abs. Error Error
(FoP) Tagg Method (m) () (m) () () (%)
R Error R Error 1 5 400 0.75 256 0.56 0.19 25
(m) (Ω) (Ω) % (Ω) % 2 4 320 0.75 192 0.57 0.18 24
3 3 240 0.75 134.4 0.71 0.04 5
1 9.9 140 18.2 18.5 2 18.7 3 4 2 160 0.75 81.6 1 −0.25 33
2 8.5 120 18.2 18.5 2 18.7 3 5 1 80 0.75 32.8 0.78 −0.03 4
3 7.1 100 18.2 18.4 1 18.5 2 6 0.75 60 0.75 22.2 0.72 0.03 5
4 5.6 80 18.2 17.2 5 18.9 4 7 0.5 40 0.75 12.4 0.83 −0.08 10
5 4.2 60 18.2 18.2 0 18.2 0 8 5 387 2.36 247.7 2.28 0.08 3
6 2.8 40 18.2 17.8 2 18.7 3 9 4 310 2.36 185.8 2.28 0.08 3
7 1.4 20 18.2 18.7 3 18.7 3 10 3 232 2.36 130.7 2.26 0.1 4
8 0.99 14 13.6 13.9 2 13.9 2
11 2 155 2.36 78.9 2.2 0.16 7
9 0.91 13 13.6 14.3 5 14.3 5
12 1 77 2.36 31.7 2.28 0.08 3
10 0.85 12 13.6 10 26 14 3
11 0.77 11 13.6 11 19 14 3 13 0.75 58 2.36 21.5 2.34 0.02 1
12 0.70 10 13.6 16 18 15 10 14 0.5 39 2.36 12.0 2.49 −0.13 6
13 0.64 9 13.6 15 10 14 3 Total Average Error 10
14 0.56 8 13.6 13 4 13 4
15 0.49 7 13.6 14 3 14 3
16 0.42 6 13.6 12 12 16 18
Table 3
17 0.35 5 13.6 19 40 19 40
Touch and step voltages measured by the STANDARD Method.
18 0.28 4 13.6 16 18 18 32
19 0.21 3 13.6 35 157 25 84 dA /D Generator Voltage (V) Ve/Ie
20 0.14 2 13.6 51 275 41 201
21 0.07 1 13.6 110 709 68 400 V (V) I (A) Touch Step Touch Step
22 5 70.7 13.9 13.9 0 13.9 0
23 4 56.56 13.9 14 1 14.2 2 5 221.7 0.279 0.64 0.07 2.28 0.26
24 3 42.42 13.9 14 1 14.2 2 4 220.9 0.246 0.56 0.06 2.28 0.25
25 2 28.28 13.9 14.6 5 14.5 4 3 221.6 0.376 0.85 0.09 2.27 0.25
26 1 14.14 13.9 13.3 4 14 1 2 221.6 0.821 1.82 0.2 2.22 0.24
27 0.75 10.6 13.9 14.91 7 14.1 1 1 221.8 0.949 2.14 0.23 2.25 0.24
28 0.5 7.07 13.9 13.9 0 13.9 0 0.75 221.5 0.714 1.66 0.17 2.32 0.23
29 0.25 3.53 13.9 21 51 19 37 0.5 221.7 0.583 1.43 0.12 2.45 0.2
30 5 35.35 62.8 63.5 1 64 2 0.25 221.6 0.396 1.18 0.06 2.98 0.15
31 4 28.28 62.8 64.4 3 65.5 4
32 3 21.21 62.8 64.7 3 64.5 3
33 2 14.14 62.8 66 5 64 2
34 1 7.07 62.8 68.1 8 59 6
35 0.75 5.3 62.8 70 11 56 11 about 2.36 . Table 2 presents the results achieved by PRED method
36 0.5 3.53 62.8 77.8 24 46.8 25 during the evaluation of both urban substations. In this table, 14 sets
37 0.25 1.76 62.8 80 27 43 32 of measurement tests can be observed. Grounding resistance and
38 5 55.9 31.2 32.5 4 31.8 2
39 4 44.72 31.2 32.1 3 32 3 error estimate is also provided at this table. The total average error
40 3 33.54 31.2 33 6 32.1 3 was about 10%, and it was considered a reasonable accuracy for the
41 2 22.36 31.2 33.9 9 31.9 2 proposed method, especially because the resistance values in this
42 1 11.18 31.2 32 3 29 7
43 0.75 8.38 31.2 33.8 8 27 13 situation are very small. It is important to note that at Substation A,
44 0.5 5.59 31.2 37 19 25.4 19 the largest error estimate was about 33% and it was presented dur-
45 0.25 2.79 31.2 57 83 23 26 ing test number 4. The average error for this substation was 15%, but
46 5 51.53 49.7 50 1 50.5 2
47 4 41.23 49.7 50.5 2 50.5 2 it is also considered a good result because the absolute error was
48 3 30.92 49.7 51.2 3 50.8 2 less than 1 . At Substation B, the maximum error was 7% obtained
49 2 20.61 49.7 52.5 6 50.7 2 during test 11, and the average error for this substation was about
50 1 10.3 49.7 55 11 50 1
51 0.75 7.73 49.7 54 9 48 3 4%. It can be also considered a reasonable grounding estimate by
52 0.5 5.15 49.7 61 23 44 11 PRED method.
53 0.25 2.57 49.7 74 49 43 13
54 5 70.7 16.74 16.8 0 16.8 0
55 4 56.56 16.74 17.03 2 17.04 2 6.2. Application of proposed methods for touch and step potential
56 3 42.42 16.74 16.8 0 17.2 3
57 2 28.28 16.74 17.3 3 17.2 3 estimate
58 1 14.14 16.74 18 8 17.2 3
59 0.75 10.6 16.74 15.9 5 17.2 3 An important goal of this work is to evaluate the application
60 0.5 7.07 16.74 15 10 16.41 2
61 0.25 3.53 16.74 24 43 22 31 of the proposed method in order to obtain the touch and step
62 5 35.35 81.3 81.5 0 81.6 0 potential, since this information is very important for safety rea-
63 4 28.28 81.3 82.4 1 83.1 2 sons. During the preview section, it was demonstrated that PRED
64 3 21.21 81.3 81 0 81 0
65 2 14.14 81.3 83 2 79.2 3
Method was capable to obtain earth resistance measurements with
66 1 7.07 81.3 85.9 6 75 8 reasonable accuracy, since average error remains about 5% when
67 0.75 5.3 81.3 78 4 75 8 compared to Standard references [11]. Therefore, in this section the
68 0.5 3.53 81.3 92.5 14 70 14
indirect measurements proposed by the PRED method are again
69 0.25 1.76 81.3 101.4 25 70 14
compared with the traditional method set by IEEE Std. 81-2012
Total Average Error (considering all results) 26 17
[11], but now considering touch and step potential results.
Total Average Error (neglecting dA < 5m) 6 4
Tables 3 and 4 present results of touch and step potential
measurements performed by the standard and PRED methods
respectively. Here, both tests were performed on experimental
mesh 1.
A. Raizer et al. / Electric Power Systems Research 153 (2017) 111–118 117
PRED Method can predict the measurement point in advance, [2] A. Raizer, V.L. Coelho, W. Valente Jr., C.I. Cardoso, Contribution to Tagg’s
based on mesh dimension D, and requires only one direct mea- methodology in the resistance measurement of earth-electrode systems at
reduced distances, in: International Symposium on Lightning Protection (XIII
surement). SIPDA 2015), Balneario Camboriu, 2015, pp. 109–115.
[3] C. Korasli, Ground resistance measurement with alternative fall-of-potential
However, as in the case of any scientific development process, it method, in: Proceedings of the Transmission and a Distribution Conference
and Exhibition-IEEE-PES, 21–24 May, Dallas-TX, USA, 2006, pp. 942–946.
is important to note some possible limitations that may be related [4] C. Wang, T.T. Takasima, T. Sakuta, Y. Tsubota, Ground resistance measurement
to the following aspects: using fall-of-potential method with potential probe located in opposite
direction to the current probe, IEEE Trans. Power Deliv. 13 (October) (1998)
• The experimental developments of this project were based on 4 1128–1135.
[5] J. Ma, F.P. Dawalibi, Extended analysis of ground impedance measurement
meshes of different dimensions, located in the same region, in using the fall-of-potential method, IEEE Trans. Power Deliv. 17 (October)
which the soil has similar characteristics. (2002) 881–885.
• Since only two real urban substations meshes were evaluated [6] J. Ma, F.P. Dawalibi, Influence of inductive coupling between leads on ground
impedance measurements using the fall-of-potential method, IEEE Trans.
using PRED Method, it is important to provide the use of this Power Deliv. 16 (October) (2001) 739–743.
procedure in large scales analysis and compare the results with [7] R.J. Heppe, Computation of potential at surface above and energized grid or
standard methods to confirm the effectiveness of the methods other electrode, allowing for non-uniform current distribution, in: IEEE
PAS-98, November/December, 1979, No. 6.
under general conditions. [8] G. Parise, M. Lucheroni, Measurements of touch and step voltages adopting
current auxiliary electrodes at reduced distance, in: Proceedings of the
To summarize, after a series of technical analyses, which Industrial and Commercial Power Systems Technical Conference, 8–12 May,
Saratoga Springs-NY, USA, 2005, pp. 191–198.
involved, soil resistivity measurement processes, computer sim- [9] K. Murakawa, H. Yamane, M. Hattori, Earthing resistance measurement
ulation, parametric evaluation, mathematical analysis and data technique without using auxiliary electrodes, 16 May, Instabul, Turkey, in:
correlation, it was possible to gather relevant information for the Proceedings of the IEEE International Symposium on Electromagnetic
Compatibility, vol. 1, 2003, pp. 213–216.
assessment of earth resistance measurement methods at reduced [10] A.S. Meliopoulos, Shashi Patel, G.J. Cokkinides, A new method and instrument
distances. The PRED method underwent a results validation pro- for touch and step voltage measurements, IEEE Trans Power Deliv. 9 (4)
cess and it is currently regarded as a functional tool that can be (1994).
[11] IEEEStd. 81-2012, IEEE guide for measurement earth resistivity, ground
applied by design engineers of grounding systems, as well as for
impedance, and earth surface potentials of a grounding system, in: IEEE
monitoring the electrical performance at CEEE-D utility company. Power and Energy Society, New York-USA, 2012.
[12] C.-H. Lee, A.P. Sakis Meliopoulos, Comparison of touch and step voltages
between IEEE Std 80 and IEC 479-1, September, in: IEEE Procedings
Acknowledgement
Generation Transmission Distribution, vol. 146, 1999, pp. 593–601, No. 5.
[13] ANSI/IEEE Std 80-IEEE Guide for Safety in AC Substation Grounding, in: IEEE
This work was developed under the State Company of Electric Power and Energy Society, New York-USA, 2000.
[14] W. Valente Jr., V.L. Coelho, A. Raizer, C.I. Cardoso, Ground impedance
Power Distribution (CEEE-D) R&D program which is regulated by
assessment employing earth measurements, numerical simulations, and
the Brazilian Electricity Regulatory Agency (ANEEL). analytical techniques, in: International Symposium on Lightning Protection
(XIII SIPDA 2015), Balneario Camboriu, 2015.
References