Townhouse: CLUBHOUSE
Design Inputs
Based on NSCP 2010 adopted from ASCE7-05
Table 207 - 3
Occupancy Category No. 4
Iw = 1
Table 207 -1
Zone 1 62500
V= 250 kph
Building Height
z= 7.4 m
Table 207 -4
Category B, Case 1
Kz = 0.7
Section 207.5.7.2
Kzt = 1
Section 207.5.4.4
Kd = 0.85
Table 207 -5
Enclosed Building
Roof Angle = 0
0.18
GCpi=
-0.18
B= 7.5
L= 13
Computations
qh = 1.7590
Transverse Forces(Z)
LOCATION A B C D E
Storey 2 5 9 10 9 5
Storey 1 13 23 24 23 11
Longitudinal Forces(X)
LOCATION 1 2 3
Storey 2 6 10 6
Storey 1 13 26 15
3E 4E
-1.2489 -1.0730
-0.6156 -0.4397
1.2489 1.0730
Roof Building Surface
Angle 1 2 3 4 5 6 1E 2E 3E
0-5 0.4 -0.69 -0.37 -0.29 -0.45 -0.45 0.61 -1.07 -0.53
20 0.53 -0.69 -0.48 -0.43 -0.45 -0.45 0.8 -1.07 -0.69
30-45 0.56 0.21 -0.43 -0.37 -0.45 -0.45 0.69 0.27 0.53
90 0.56 0.56 -0.37 -0.37 -0.45 -0.45 0.69 0.69 -0.48
4E
-0.43
-0.64
-0.48
-0.48