Sie sind auf Seite 1von 6

International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

Analysis of an Adaptive Overcurrent Relay for Transmission


and Distribution Lines

Chen Yanxia, Yin Xianggen, Zhang Zhe, Chen Deshu

Department of Electrical Engineering, Huazhong University of Science & Technology, Wuhan, 430074,
China (e-mail: yanxiachen@263.net, xgyin@mail.hust.edu.cn, zz_mail2002@163.com,
dschen@21cn.com)

Abstract – This paper presents an adaptive overcurrent relay influenced by the type of short-circuit fault. So it’s unnec-
based on the principle of phase-to-phase differential currents, essary to calculate settings on the worst-case condition. It
denominated as I&AB , I&BC and I&CA , to detect phase fault of does not respond to normal load current so it can be set
transmission and distribution line. The characteristics of below load current levels. Moreover, when phase fault
phase-to-phase differential currents under phase fault condi- occurs in the secondary side of a delta-wye transformer,
tion are analyzed. The trip criterion and coordination princi- the PDC in the primary side are in direct ratio to those in
ple are described. This relay is adaptive to the type of phase the secondary side. Thus the coordination can be simpli-
fault, the operating conditions of power system and the dis- fied. The sensitivity can be improved, too.
connection of PT. It can also provide an adaptive backup
protection for the secondary-side overcurrent relay of a delta-
wye transformer. Comparing with conventional overcurrent II. CHARACTERISTICS OF THE PDC AND THE
relays, this relay has a larger zone of protection and higher OPERATION CRITERION OF OVERCURRENT RELAY
sensitivity. Transient simulation results are presented, too. BASED ON PDC
Keywords – overcurrent relay, adaptive protection, phase-to- The three phase currents flow through the protective de-
phase differential current, line protection
vice are I& A , I&B and I&C . Then the PDC can be defined as:

I. INTRODUCTION  I& AB = I& A − I& B


&
By far, the most commonly used protective relays are  I BC = I& B − I&C (1)
 I& = I& − I&
the overcurrent relays (OCR). They could be classified by  CA C A
operating quantities including individual phase, residual,
Their amplitudes can be defined as:
and negative-sequence current. They are used as both pri-
mary and backup protective devices and are applied in  I AB = I& AB
every protective zone in the system [1,2]. 
Phase overcurrent protection is widely applied as line  I BC = I& BC (2)
 &
protection for the purpose of saving fuse, minimizing  I CA = I CA
equipment damage, enhancing coordination, limiting out-
age time and voltage dip duration, et al [3]. To coordinate
with downstream protections, it must be set to a magnitude A. Characteristics of the PDC In Single-source Power
greater than the full-load current [4]. This may decrease System
the sensitivity of overcurrent relays.
Unlike phase overcurrent relays, negative sequence 1) Single-source Power System with Load
overcurrent elements do not respond to balanced load cur- To analyze the characteristics of the PDC, a typical sin-
rent. So, it can be set below load current levels [5]. There gle-source power system is shown in Fig. 1. It is an inef-
is a drawback that it can’t respond to balanced three-phase fectively grounded system so that only phase fault is con-
fault. sidered. The protection device is installed at bus M. The
Using the adaptive setting capabilities, many microproc- system parameters are labeled in Fig. 1. It’s assumed that
essor-based devices can optimize settings of overcurrent the positive-sequence impedance of electrical apparatus is
relays. With this feature, settings can be changed to com- equal to their negative-sequence impedances. That is to say
ply with actual system operating conditions rather than that the equivalent source impedance on the left side of bus
being set on the worst-case condition [6]. But the above M is represented as Z SM = Z SM 1 = Z SM 2 . The three phase
problems are still unresolved. potentials of bus M are represented by E& MA , E& MB and
In this paper, an adaptive overcurrent relay is designed
to detect phase faults by measuring the phase-to-phase E& MC . The sequence impedances of the line under protec-

differential currents (PDC), denominated as I& AB , I& BC and tion are represented by Z L = Z L 1 = Z L 2 . The sequence
impedances of line segment from bus M to the fault loca-
I& . Analysis shows that the maximal magnitude of the
CA
tion is Z l = Z l1 = Z l 2 . Z l' = Z L − Z l . The balanced load
three PDC can indicate fault condition and it will not be

1
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

'
impedance is Z load = Z load
'
1 = Z load 2 .
' When phase fault occurs in single-source power systems,
the fault currents flowing through the protective relay have
When a phase-B-to-phase-C fault occurs on F, the se-
following characteristics:
quence network is shown in Fig. 2. It can be derived that:
1) The magnitude of the PDC between two faulted
& E& MA 3 3 3 Z load
 I AB = [( + j) − ] phases is as 3 times as the magnitude of the phase
 Z SM + Z l 2 2 2 Z Σ' current under three-phase short-circuit fault condition.
 3 E& MA (3) 2) Among the three PDC, the magnitude of PDC be-
 I&BC = − j
 Z SM + Z l tween faulted phases has the maximum value.
 E & 3 3 3 Z load 3) Above relations will not be influenced by the type of
 I&CA = [( − + j) +
MA
]
 Z SM + Z l 2 2 2 Z Σ' phase fault.
In a word, (5) always exists. So, an overcurrent relay
Where Z Σ' = Z SM + Z l + Z load , Z load = Z l' + Z load
'
. can be designed to detect phase fault by measuring the
maximum of PDC. When the maximum exceeds the set-
Suppose that Z SM = jX SM , Z l = Rl + jX l , and
ting, the relay will operate. The zone of protection will not
Zload = jXload . Equation (4) can be deduced as below: be affected by different type of phase fault. It is easy for
setting and coordination, too. The operation criterion of
 I AB < 3 I K(3) this relay is descried in (7) and (8).

 I BC = 3 I K (4)
( 3)

 I < 3 I (3) max( I& AB , I& BC , I&CA ) ≥ I op (7)


 CA K

3 E&φ E& l (8)


When three-phase fault occurs on F, there is I op = K rel = K rel
ZS + ZL ZS + ZL
I AB = I CA = I BC = 3 I K( 3 ) .
That is to say that (5) exists when phase fault occurs in
single-source system with load. E& M
M F Load
max( I& AB , I& BC , I&CA ) ≤ 3 I K(3) (5)
Z SM 1 Z l1 Z l'1 Z ' load 1
2) Single-source no Load Power System
Z SM 2 Zl2 Z l' 2 Z ' load 2
Z SM 0 Zl0 Z l' 0 Z ' load 0
Assumes that the single-source power system (Fig. 1)
operates in no load condition (Fig. 3) and fault occurs on F. Fig. 1 Single source line with load
Then =∞.
'
Z load Z l1 I& A1 I&1 ∑ I&2 ∑
When a phase-B-to-phase-C fault occurs on F, the se- M I& A 2
quence network is shown in Fig. 4. It can be derived from
Z SM 1 Z load 1 Z l2
(3) that: U& f 1 U& f 2 Z load 2
M
E& MA 3 3 3 3 E& MA ,
I& AB = [( + j) − ] = j E& MA
Z SM 2
Z SM + Z l 2 2 2 2 Z SM + Z l
3 E& MA Fig 2. Sequence network under fault status of system in Fig. 1
I&BC = I&B − I&C = − j
Z SM + Zl
E& M M
E& MA 3 3 3 3 E& MA . F
I&CA = [( − + j) + ] = j
Z SM + Z l 2 2 2 2 Z SM + Z l
Z SM 1 Z l1
So, there is Z SM 2 Zl2
 I AB = I& AB = ( 3 / 2) I K( 3) Z SM 0 Zl0

 I BC = I& BC = 3 I K
( 3) (6) Fig. 3 Single source no load system

 I CA = I&CA = ( 3 / 2) I K
( 3)
E& MA Z SM 1 Z l1 I&A1
When a three-phase fault occurs on F, it can be derived
U& M 1A U& f 1
that I AB = I CA = I BC = 3 I K( 3) .
Also, (5) exists when phase fault occurs in single-source Z SM 2 Zl2 I&A2
no load system.
U& M 2 A U& f 2
B. Operation Criterion of Overcurrent Relay Based on
PDC Fig. 4 Fault-condition sequence network of system in Fig.3

2
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

Where, K rel is the coefficient to assure reliability, E& φ U& AB ( t ) − U& AB ( 0 ) (13)
ZS = −
I& AB ( t ) − I& AB ( 0 )
is the phase potential of the equivalent source, E& l is the
phase-to-phase potential of the equivalent source. The 3) When phase-B-to-phase-C short-circuit fault occurs,
symbol Z s represents the equivalent source impedance U& BC (t ) − U& BC ( 0)
ZS = − (14)
and Z L the positive sequence impedance of the line to be I& (t ) − I& ( 0)
BC BC
protected. I op is the setting of relay. 4) When phase-C-to-phase-A short-circuit fault occurs,
In some cases there is only two CTs for phase A and C,
U& CA (t ) − U& CA ( 0 )
what is a common practice in ineffectively grounded sys- ZS = − (15)
tem. In this system, there is I& B = − ( I& A + I&C ) . So The I& (t ) − I& ( 0 )
CA CA

PDC can be described as below: Among the three PDC, the differential current between
faulted phases has the highest magnitude. So the faulted
 I& AB = I& A − I& B = 2 I& A + I&C
& phases can be selected. Then the real-time setting can be
 I BC = I& B − I&C = − I& A − 2 I&C (9) calculated and the operation criterion can be simplified
 I& = I& − I&
 CA C A from (7) and (8).
For example, when phase-A-to-phase-B short-circuit
The operation criterion is expressed as below:
fault occurs, max( I&AB , I&BC , I&CA ) = I AB . So phase-A
max( 2 I& A + I&C , I& A + 2 I&C , I&C − I& A ) ≥ I op (10)
and phase-B are selected as faulted phases.

3 E& A E& l E& l = E& AB (t ) = U& AB (t ) + I& AB (t ) Z S (16)


I op = K rel = K rel (11)
ZS + ZL ZS + ZL
Z S = − (U& AB (t ) − U& AB ( 0 )) /( I& AB (t ) − I& AB ( 0 )) (17)
The symbols represent the same meaning as those de-
fined in (7-8). Then, I op can be expressed as (18):

I op = K rel E& l /(Z S + Z L )


III. ADAPTIVE METHODS TO IMPROVE THE
PERFORMANCE OF THE OVERCURRENT RELAY BASED U& (t)(I& AB (t ) − I&AB (0)) − I& AB (t)(U& AB (t ) −U& AB (0)) (18)
= K rel AB
ON THE PRINCIPLE OF PDC − (U& AB (t ) −U& AB (0)) + Z L (I& AB (t ) − I& AB (0))

Using adaptive impedance recognition can change relay


settings to match them with power system conditions. With B. Adaptive Schemes for the Disconnection of PT
methods described below, the zone of protection can be When voltage is applied in the calculation of equivalent
extended, the sensitivity of protection can be increased, source impedance, the disconnection of PT may leads to
and the trip criterion and coordination principle can be malfunction of relays. To avoid this situation, a two-level
simplified. adaptation is considered in this paper. The first level is to
use only fault currents to realize the adaptive functions.
A. Recognition of Equivalent Source Impedance The second one is to use both fault currents and fault volt-
Suppose that before fault occurs, the PDC are I& AB (0) , ages. In normal situation, the second scheme is applied.
When PT is disconnected, the protection scheme will
I&BC (0) and I&CA (0) . And the phase-to-phase voltages are switch to the first one automatically. Thus the performance
U& AB (0) , U& BC (0) and U& CA (0) . After fault occurs, the of overcurrent relay can be improved. This switching of
operation criterion is very applicable to be installed in the
PDC are I& (t ) , I& (t ) and I& (t ) . And the phase-to-
AB BC CA unmanned substations or the field where no PT exists.
phase voltages are U& AB (t ) , U& BC (t ) and U& CA (t ) . The Equation (7) and (8) are the operation criterion and set-
equivalent source impedance can be calculated as follow- ting value for the second level. When only the first level is
ing: considered, the operation criterion and setting can be illus-
1) When three-phase fault occurs, trated as following:

U& BC (t ) − U& BC ( 0 ) U& (t ) − U& AB ( 0 ) max( I& AB , I& BC , I&CA ) ≥ I op (19)


ZS = − = − AB
&I (t ) − I& ( 0 ) I& AB (t ) − I& AB ( 0 )
BC BC
E& l
I op = K rel = K rel 3 I K( 3) (20)
U& (t ) − U& CA ( 0 ) (12) Z S . min + Z L
= − CA
I& (t ) − I& ( 0 )
CA CA

2) When phase-A-to-phase-B short-circuit fault occurs, IV. COORDINATION CONSIDERATIONS WHEN


SERVED AS BACKUP OVERCURRENT PROTECTION
As it is described above, the operation criterions can

3
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

switch automatically to achieve a two-level adaptation. backup protection spanning a transformer, the sensitivity
Without communication, a protection can’t know which of the relay based on PDC will not be decreased. So, the
criterion is really used in the upstream and downstream operation criterion can be described as below:
protections [7,8]. Therefore, when served as backup over-
current relay, it is better to coordinate only on the first max( I& AB , I& BC , I&CA ) ≥ K rel.T I op
III

level, that is, coordinate without calculating the equivalent 3 III (27)
source impedance (see 19-20). = K rel
III
.l K T I op
2
Applied on the primary side of a transformer, the over-
current relay described above can provide backup protec- Where, K rel .T - the reliable coefficient of the backup
tion for secondary-side faults of the transformer. To ana- protection of a transformer;
lyze the characteristics and sensitivity of the relay, a K T - the reciprocal of the transformer ratio;
Y / ∆ − 11 connected transformer will be considered [9]. III
K rel .l - the reliable coefficient of the backup protection of
When a phase-to-phase fault occurs, the magnitudes of
the currents of two faulted phases are equal to half of the the downstream line;
III
third one. This will decrease the sensibility of traditional I op - the setting value of the backup protection of the
overcurrent relays. But when relays based on the principle
downstream line.
of PDC are used, it will be different.
When phase-B-to-phase-C short-circuit fault occurs on
V. ANALYSIS OF THE ZONE OF PROTECTION AND
the wye-side of the transformer, the current distribution on
both sides of the transformer is illustrated in Fig. 5. Sup- SENSITIVITY COMPARING WITH THE TRADITIONAL
pose that the transformation ratio n = 1 : 1 . OVERCURRENT RELAYS
It’s obvious that
A. Zone of Protection of Traditional Overcurrent Relays
 I&b = − I&c
 I& = 0 The traditional instantaneous overcurrent relay is set as
 a (28):
 I& β = − (1 / 3 ) I&b
& &
(21) Eφ
I γ = − I β I op = K rel ⋅ (28)
 I& = 0 Z s . min + Z L
 &α & &
I A + I B + I C = 0 Where, I op is the set value of fault current; K rel is the
And it’s easy to derive that reliable coefficient.
I&A = I&α − I&β = (1 / 3 ) I&b When fault occurs on the position of ∂Z L , the fault cur-
 rent is:
I&B = − I&γ + I&β = −(2 / 3 ) I&b (22)
I& = I& − I& = (1 / 3 ) I& IF =
K d Eφ
(29)
 C γ α b
Z s + ∂Z L

 I& AB = 3 I&b = ( 3 / 2 ) I&bc Where, I F is the fault current; K d is coefficient of the


 fault type.
So,  I& BC = − 3 I&b = − ( 3 / 2 ) I&bc (23)
 I& = 0 Suppose that I op = I F , the zone of protection of tradi-
 CA
tional overcurrent relays can be calculated from (30):
Thus,
K d ( Z s . min + Z L ) − K rel Z S
∂= (30)
max( I& AB , I& BC , I&CA ) = ( 3 / 2) I&bc K rel Z L
(24)
= ( 3 / 2) max( I& , I& , I& )
ab bc ca
B. Zone of Protection of Adaptive Overcurrent Relay
It’s the same when other type of phase-to-phase fault
occurs on wye-side. So, when phase-to-phase fault occurs
on wye-side, there will always be: I& A . I&α
.
I&a
3
max( I& AB , I& BC , I&CA )= max( I&ab , I&bc , I&ca ) (25) I&B I&b
2 . I&β .

It can also be derived that when phase-to-phase fault oc-


curs on delta-side, (26) will exist: I&C . I&γ . I&c F

3
max( I& ab , I&bc , I& ca ) = max( I& AB , I& BC , I&CA ) (26)
2
Fig. 5 Distribution of primary and secondary currents of trans-
From above it can be concluded that: when served as former

4
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

Based on PDC (2) When phase-to-phase short-circuit fault occurs,


a) Consider the Real-time Calculation of Equivalent 3.
Kd =
Source Impedance 2
Then, ∂ > 2 .
"
If real-time equivalent source impedance is calculated,
the set value of fault current is: ∂ 3

3 Eφ So, to all type of phase fault, there is ∂ " ≥ ∂ too.


'
I op = K rel ⋅ (31) Moreover, there is ∂ " / ∂ ' < 1 . So the zone of protection
Zs + ZL
of the adaptive overcurrent relay based on PDC is larger
When fault occurs on the position of ∂Z L , the fault cur- than the traditional one. And when the equivalent source
rent is : impedance is calculated, the zone of protection of the
adaptive relay can be extended.
I F' = 3 Eφ /( Z s + ∂Z L ) (32)

'
Suppose that I op = I F' , the zone of protection can be VI. TRANSIENT SIMULATION OF THE PDC-BASED
calculated from: OVERCURRENT RELAY USING ATP AND MODELS

∂ ' = [ Z L + (1 − K rel ) Z S ] /( K rel Z L ) (33) To test the dynamic operational characteristics of relay-
ing algorithm based on PDC, the Alternative Transients
From (30) and (33), it can be derived that: Program (ATP) is used for simulation.
ATP is a widely used program for digital simulation and
∂' (1 − K rel ) Z S + Z L
= (34) analysis of power system transients. MODELS in ATP is a
∂ ( K d Z S . min − K rel Z S ) + K d Z L general-purpose description language supported by an ex-
For traditional overcurrent relays, K d have two possi- tensive set of simulation tools for the representation and
study of time-variant systems. MODELS allows the de-
ble values:
scription of arbitrary user-defined control and circuit com-
(1) When three-phase short-circuit fault occurs, K d = 1 . ponents, providing a simple interface for connecting other
program/models to ATP [10,11]. With MODELS facilities,
∂' (1 − K rel ) Z S + Z L
= >1 it is possible to simulate the process of real-time coordina-
∂ ( Z S . min − K rel Z S ) + Z L tion and tripping (see Fig. 6).
(2) When phase-phase short-circuit fault occurs, The simulation system is shown in Fig.7. The parame-
ters are listed in table I. By programming the line parame-
Kd = 3 / 2 . ters, fault location can be changed along the line.
∂' (1 − K rel ) Z S + Z L 2 Some of simulation results of primary currents are
= > shown in Fig.8. Here, fault occurs when t=0.1s. Respond-
∂ 3 3 3
( Z S . min − K rel Z S ) + ZL ing to different fault type, the real-time settings are differ-
2 2
ent (Table II). It’s shows that this overcurrent relay can
So, to all type of phase fault, there is ∂ ' ≥ ∂ . operate properly within about one cycle after fault occurs.
b) Without Real-time Calculation of the Equivalent Source
Impedance VII. CONCLUSIONS
When the equivalent source impedance is set as a con-
In this paper, a novel adaptive overcurrent relay based
3 Eφ on phase-to-phase differential current is proposed. The
stant, there are "
I op = K rel ⋅ and
Z s. min + Z L sensitivity of this relay will not be influenced by fault type.
Through the real-time calculation of the equivalent source
3Eφ
I F" =
"
. Suppose that I op = I F" , the zone of impedance, its sensitivity can be improved. The two levels
Zs + ∂ ZL ''
of adaptation can be switched automatically or manually.
protection can be calculated from (35): The operation principle is simple. And it is easy to coordi-
nate. Moreover, when applied as the backup protection of
Z S . min + Z L − K rel Z S transformers, the sensitivity of protection can be improved
∂ '' = (35)
K rel Z L remarkably. It is a promising protection scheme for the
middle-low voltage transmission and distribution lines.
Then ∂ =
"
Z S . min + Z L − K rel Z S (36)
∂ K d ( Z S . min + Z L ) − K rel Z S REFERENCES
Also there are two possible values of K d : [1] Schweitzer, E.O., III; Zocholl, S.E. “The Universal Overcurrent
Relay”. IEEE Industry Application Magazine, Volume: 2, Issue:
(1) When three-phase short-circuit fault occurs, K d = 1 . 3, pp. 28-34, May-June 1996
[2] “IEEE Recommended Practice for Protection and Coordination of
∂"
Then, = 1; Industrial and Commercial Power Systems”. Approved 14 June
∂ 2001, New York, USA: The Institute of Electrical and Electron-

5
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

ics Engineers, Inc. First Printing, 17 December 2001


[3] The Effectiveness of Distribution Protective Working Group of Data ATP Trip
IEEE/PSRC. “Distribution Line Protection Practices-Industry Sampling Simulation Signal
Survey Results”. IEEE Transactions on Power Delivery, Vol.3,
No.2, pp. 514-524, April 1988
ATP MODELS of the overcurrent
[4] Herbert A. Fleck, Frank J. Mercede. “Using Short-circuit Cur-
rents to Perform a Protective Device Coordination Study”. IEEE relay based on PDC
Industry Application Magazine, pp. 43-52, March/April 2000
[5] Edmund O. Schweitzer, Mark W. Feltis, Ahmed F. Elneweihi, Digital Fault Relaying
“Improved sensitivity and security for distribution bus and feeder Filter Detection Algorithm
relays”. WESCANEX 93. 'Communications, Computers and
Power in the Modern Environment.' Conference Proceedings. Fig. 6 Block diagram of ATP simulation
IEEE, pp. 337-339, 1993
[6] “IEEE/PSRC Working Group Report on Considerations in Setting
Instantaneous Overcurrent Relays on Transimission Lines”,
IEEE Transactions on Power Delivery, Vol. 14, No. 1, pp. 116-
125, January 1999
[7] J C Tan, P A Crossley, I Hall, J Farrell, P Gale. “Intelligent Wide
Area Back-up Protection and Its role in Enhancine Transmission
Network Reliability”. Developments in Power system Protection,
Conference Publication No. 479, IEE, pp. 446-449, 2001
[8] Y. Serizawa, H. Imamura, N. Sugaya. “Experimental Examina-
tion of Wide-area Current Differential Backup Protection Em-
ploying Broadband Communications and Time Transfer Sys-
tems”. 0-7803-5569-5/99,IEEE, pp. 1070-1075, 1999
[9] Chen Deshu. The Principle and Practice of the Power System
Protection, Beijing, China: China Electrical Power Publication,
First Edition, 1981
[10] Chul-Hwan Kim, Myung-Hee Lee, Raj K. Aggarwal, et al.
“Educational use of EMTP MODELS for the study of a distance
relaying algorithm for protecting transmission lines,” IEEE Trans. Fig. 7 Distribution network for ATP simulation
on Power Systems, Vol. 15, No. 1, pp. 9-15, 2000.
[11] Robert E. Wilson, Jerry M, Nordstrom. “EMPT transient model- Table I Parameters of the simulation system
ing of a distance relay and a comparison with EMTP laboratory
testing.” IEEE Trans. on power delivery, Vol. 8, No. 3, pp. 984- Z1[ohm] Z2[ohm]
992, July 1993. Line 5.4+j55.66 5.4+j55.66
Source 0.2534+j20.046 0.2534+j20.046
Load 1470+j1102.5 1470+j1102.5

Table II Relay settings and the maximum of PDCs

Fault type f (BC ) f ( ABC )

Max. of PDCs [A] 526.48 526.69


Relay setting [A] 472.06 433.54

ia ib ic

Fig.8 Phase currents when B-C phase fault occurs

Das könnte Ihnen auch gefallen