Sie sind auf Seite 1von 1

SIEMENS

F.1 12kV Busbar Discriminating Zones Protection

Relay Type: 7SR2302-1BA12-0CA0 Applicable for both Discriminating Zone-1 and Zone-2

Common CT Data:

CT Ratio: 2500/5A

Class of Accuracy: PX

Magnetizing current(@ Vk) Im = 0.05 A

CT Resistance: Rct = 1.4

Knee Point Voltage: VK = 150 V

CT primary current: 2500 A

For stability consideration , through fault current is set to be equal to Switchgear S.C.Rating

Maximum short circuit current = I F = 25 KA

7SR23 DISCRIMINATIONG ZONES PROTECTION

1 Maximum value of primary fault current IF = 25 KA

= 6250 A
2 Minimum value of primary fault current (25% of Maximum fault current)

3 Bus bar Rated Current = 3000 A

4 CT Primary current IP = 2500 A

5 CT Secondary current Is = 5 A

6 Turns ratio of CT core T IS / IP = 0.002

7 CT knee point voltage VK = 150 V

8 CT Secondary Winding Resistance RCT = 1.40 Ohms

9 Lead resistance between furthest current transformer and relay RL = 0.33 Ohms

terminals

10 Require Voltage stability Limit V I F x (RCT + 2*RL) * T = 103 V

11 Selected Relay setting voltage Vs Vs V = 105 V

12 Number of CT cores in circulating current differential circuit n = 16 nos

SIEMENS
Energy Sector Projects/Engineering EM-TS PROJECTS /A5174/Relay Settings

Unrestricted