DOMINO 1300 Z C SL R M1
DOMINO
The patented series of modular packaged chiller and heat pump with scroll compressors and R-410A refrigerant oriented
towards higher energy efficiency and low noise emissions.
MODULAR
Due to the multiple configuration available, Domino is suitable for air conditioning any environment. More than 200
compositions are possible and the power range can be increased over time in a simple and economical way, thus
following the development of the projects. The basic unit can be installed in every position as Domino card game where
its name come from, in this way no more problem for space and load of the unit.
ECOLOGICAL
The ecological refrigerant gas R-410A is not dangerous for the ozone; it allows high efficiency systems (ODP = 0) and
convenient electrical consumption, and therefore, lower emissions of CO2 in the atmosphere. The scroll compressor,
optimized for R410A are more efficienty, compact and silent.
EFFICIENT
The unit assure coefficients ESEER and IPLV extremely high and a perfect continuous response to the installation load
variation. DOMINO single circuit units operating with R410A are characterized by an ESEER clearly superior to the
traditional dual-circuit units operating with R407C.
SILENT
Due to the special axial fans with owlet or Hy Blade profile of the shovels, Domino is more silent: it reaches a noise
reduction of 6 dB(A) compared to standard axial fans version.
PATENTED
Web App
ver1.0 1
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
Domino is covered by international patents:External Air Recover® In heat pump mode it allows free heating of external
air, avoiding the use of an external heat recovery with an increase of 40% for the COP.Energy Multiplier Water
Storager® Regenerative recovery system to increase the power and efficiency by using chilled water storage at medium
heat.Hybrid Smart Cooling® With the hybrid smart cooling system the unit can match the load request at any outdoor
temperature. Domino is the only chiller able to increase capacity with the increase of the outdoor temperature.
BASIC VERSIONS
C ChillerCM Cooling only condensing unitMC Modular chiller (to be associated to the MULTI-MANAGER mandatory
option)
ENERGETIC VERSIONS
(To be combined with basic versions)
D Partial recovery stainless steel brazed plate type desuperheater, externally insulated.R Total recovery stainless steel
brazed type exchanger, externally insulated.
ACOUSTIC VERSIONS
(To be combined with basic versions)
LN Low Noise includes condensing control with variable fan speed regulation up to size 1130 and 2 speed condensing
control from size 1140 to 1300 and sound compressors jackets. Compared to basic versions, LN versions allows a
reduction of about 2 dB(A) in sound levels.SL Super Low Noise includes condensing control with variable fan speed
modulation, muffler on the compressor delivery lines and soundproof box. Compared to basic versions, SL versions
allows a reduction of about 5 Db(A) in sound levels.
HYDRAULIC VERSIONS
(To be combined with basic versions)
B/M/A Hydraulic kit including: N.1 or N.2 pumps, available head pressure (B) Low (150 kPa), (M) Medium (250 kPa), (A)
High (450 kPa), expansion vessel.SB/SM/SA Hydraulic kit including N.1 pump, available head pressure (B) Low (150
kPa), (M) Medium (250 kPa), (A) High (450 kPa), expansion vessel, buffer tank.XB/XM/XA Hydraulic kit including N.2
pumps, available head pressure (B) Low (150 kPa), (M) Medium (250 kPa), (A) High (450 kPa), expansion vessel, buffer
tank.
MAIN FEATURES
PARTIAL LOAD HIGH EFFICIENCY THANKS TO THE HUGE NUMBER OF CHOKING STEPS
Web App
ver1.0 2
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
Thanks to the combination of multiple machines it is possible to increase efficiencies at partial loads. For the sizes
equipped with two compressors of different power, it is possibile to obtain 3 capacity steps. This increases partial load
efficiency and the seasonal average efficiencies of the individual machine and the system of n machines.
Web App
ver1.0 3
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
The programmable controller is based on a powerful platform with 256bit microprocessor, 4MB mass storage with a
hardware and software configuration made with the most innovative technology in terms of processing speed and
connectivity.The diagnostics includes a complete alarm management, alarm history and data logger which stores an
archive of about 4 days (further expandable by USB memory) where the main variables and the operating status of the
unit are recorded. ModBus master and slave communication protocol.The operating parameters of the machine are
protected by 3 levels of password (user-maintainer-builder). The user panel provides information on LED display (sizes
from 120 up to 135) with exhaustive descriptions in Italian, English, Spanish and French (selectable) and on LCD display
(sizes from 150 up to 2145).- Ability to interface with the main BMS systems via RS485, BacNet, Lontalk;- Ability to
interface with I/O expansion modules via CanBus;- Ability to control the unit by voltage free contacts;- Input
USB/Ethernet adaptor for routing on the web of all the parameters of the unit, providing a total remote control of unit;-
USB input to upload parameter files, system files, firmware and to download files of historical alarms, residing
parameters files and default parameters files.t;- User interface on the door of the panel, low-reflection LCD, equipped
with 8 function keys, easy iconic display, easy sliding between the dynamic screens;- Control of condensation air directly
managed by the electronic controller based on proportional logic;- Management of electronic expansion valves through
controller based on PID logic, with LOP control (low operating pressure), maintenance of the minimum working pressure
and of the MOP (maximum operating pressure) for the management of the maximum working pressure;The
microprocessor manages:- Starting of the compressors with the start-up and stop time control;- Compressor rotation with
FIFO logic;- Fans start up and modulation according with condensation pressure;- Electric anti-freeze heater for user
exchangers;- Water pumps management through voltage free contacts for standard versions; for hydraulic versions the
pump management is automatically controlled;- Alarm signal of the unit through voltage free contacts.The
microprocessor will control and display by suitable measuring transducers the following variables:- Inlet and outlet water
temperature to the user exchanger;- Outdoor temperature;- Condensing pressure of each refrigerant circuit;- Evaporating
pressure of each refrigerant circuit;- Total operating time of each compressor;- Total operating time of the unit.The
microprocessor will protect the unit in the following cases, the resetting of any alarm will always be manual.- Low
evaporating pressure by analogical and digital input with possibility to edit the marking details;- High condensing
pressure by analogical and digital input;- High temperature of the compressors windings;- Reverse rotation of each
compressor;- High temperature of fans motor windings;- High temperature of pumps motor windings;- Lack of water flow
on evaporator and condenser;- Low outlet water temperature from the source heat exchanger.It is also possible to
display and edit through the microprocessor the following value:- Operating set point of the unit;- Operating differential
of the unit;- Set point and anti-freeze block differential;- Set point and differential of activation of the evaporator heater;-
Minimum operating time of each compressor;- Minimum stop time of each compressor;- Maximum number of starts per
hour of each compressor;- Set point and optimal condensation pressure differential (condensation control).Other
functionalities ensured from the microprocessor are:- Activating of preventive functions at extreme conditions of high
pressure;- Activating of preventive functions at extreme conditions of low p
UNIT DESCRIPTION
SCROLL COMPRESSORS
Hermetic scroll compressors, complete with a heating protection of the electric engine with automatic reinsertion and a
crankcase resistance in order to prevent the refrigerant thinning in the oil during device downtimes.The junction-box is
contained into a covering with an IP 54 protection degree.
FRAME
Lattice framework piece of furniture with elements made of varnished zinc-coated steel able to withstand the mechanical
stress both during transport and functioning. The high corrosion strength, assured by an epoxy powder based treatment,
and the weather events strength allows the outdoor installation. The building shape assures a perfect air transition
through finned parcel exchangers and allows accessibility to internal components so as to simplify repairs and
maintenance.
Web App
ver1.0 4
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
Air-cooled microchannel condensing coils with aluminum fins. The coil is made up of three components: the multichannel
tubes, the fins which are placed between the microchannels and the two refrigerant headers.Main features:- Reduced
consumption and noise levelWith lower pressure drop in the air side and small size of microchannels condensing coils,
the turbulence on the condensing coil and pressure drops losses are reduced resulting in reduced noise, power and/or
number of fans needed.- CompactThe heat transfer surface in contact with the refrigerant is greatly increased, so these
heat exchangers are more compact and provide higher performance compared to the tube & fin.- Reduced refrigerant
chargeThanks to new Microchannel technology (heat exchanger) the refrigerant charge is reduced by up to 37%
compared to equivalent units with Al-Cu fin & tube condensers.- Reduced emissions of refrigerant into the
atmosphereLower emissions of refrigerant into the atmosphere with considerable benefits in terms of environmental
protection.- Significant reductions in weightSignificant reductions in weight, which is a double advantage, a significant
reduction of costs and maintenance time, and at the same time lower CO2 emissions in transport. Optional coatings are
available to protect the coils and to increase the corrosion resistance and for the use in chemical risk environnement.
EVAPORATORS
Directly expanded braze welded plated, externally isolated with closed cells anti-condensate mat, fitted with antifreeze
electrical resistance driven by thermostat and water differential gear pressure switch.
FANS
The technology of ECOPROFILE propeller fans, has blades statically and dynamically balanced, driven directly by the
electric motors, closed type, external rotor and thermal protection for outdoor installation. Class F windings, internal
protection according to VDE 0730. Ecoprofile are characterized by low speed and ""owlet"" profile to reduce the effect of
vortices, thereby reducing the energy consumed for operation and noise, reducing it by an average of 6dB (A) compared
with standard fans.ECOPROFILE ELECTRONIC fans are available as well in the brushless version, which uses
brushless electric motors, further improving both power consumption and noise emissions. In addition, these fans
provide a continuous adjustment of condensation.Condensing control by variable fans speed modulation is included on
all Domino version up to 1130 Z size.CONDENSING CONTROL IN THE ACOUSTIC VERSIONS:LN (Low Noise)•
variable fan speed modulation up to size 1130;• step condensing/evaporating control control from size 1140 up to size
1300;Fan speed is automatically increased if the units works in extreme outdoor conditions.SL (Super Low Noise)•
Condensing control with variable fan speed modulation for all the sizes.Fan speed is automatically increased if the units
works in extreme outdoor conditions.
MOUNTED ACCESSORIES
Hybrid smart cooling® (2 way modulating valve, brazed heat exchanger)Low outdoor water temperature kit from - 6 up to
- 10°CRemote adjustable set point (3)Electronic expansion valve (5)Power factor correction to cos. phi. = 0,91 (2)
(5)Automatic circuit breakers (5)Numbered wiresControl panel electric heater with thermostat Water pumps automatic
changeoverOver/under voltage + phase failure protection relay (5)Condensing control (14)Condensing control with
variable fan speed modulationElettronic ecoprofile fans - C VERSIONElettronic ecoprofile fans - SL VERSIONHigh static
pressure fans 100 PaSoft starter (5)Low outdoor temperature kit up to -10°C (in cooling mode only) (4))Compressors
sound jacketsPlastic wrapping + open wooden cratePlastic wrapping + close wooden cratePlastic wrapping + close
wooden crate for sea transportPlastic wrapping and close wooden crate extra price (for hydraulic kit version)Powder
coated condensing coils (5) (15) (16)Anti-corrosion coated condensing coils (5) (15) (17)Anti intrusion grilles - opposite
side electrical panelAnti intrusion grilles - electrical panel sideAnti intrusion grilles - lateral (1 side)Condensing coils Anti
intrusion grillesComplete anti intrusion grilles kitGas gauges
LOOSE ACCESSORIES
Remote control panel for advanced controllerRemote Display (for stand alone applications)Connection valve kit for CM
(12)Flow switchWater gaugesAutomatic water fillingRubber antivibration mountsSpring antivibration mountsRubber
antivibration mounts for hydraulic versionSpring antivibration mounts for hydraulic versionWater strainer Serial
communication card RS485 (for stand alone applications)
NOTES
Web App
ver1.0 5
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
(2) The power factor correction will apply on each unit electrical panel for unit in modular system.(3) The optional
includes the advanced controller. In case of selection of remote control panel, the ""Remote control display for advanced
controller"" must be choosen. For modular versions this optional is standard.(3a) For Total Recovery versions R or in
case the optional “Remote adjustable set point” is selected. (4) It includes variable fan speed control, additional
evaporator heater, double insulation for evaporator, control panel electric heater with thermostat(5) Not available for
units on stock.(6) It includes variable fan speed control, additional evaporator heater, double insulation for evaporator,
control panel electric heater with thermostat, oversized crankcase heater, compressors jackets, control system for
compressors oil temperature.(7) For modular applications only.(8) It includes advanced controller(9) Not compatible with
modular version(10) It includes only thermostatic expansion valve.(11) Not available with Heat pump version(12) The
connection kit includes: check valve, expansion valve and filter dryer.(13) The kv value is the flow of water in m3/h at a
pressure drop in the strainer of 1 bar.(14) 3 steps condensing control up to size 1200
4 steps condensing control from size 1220 up to size 1300.(15)Treatment on coils may increase the lead time (up to 3
weeks).(16)Thermosetting powder coating. Very good UV resistance. Not recommended for use in highly corrosive
environments.(17) Anti-corrosion protection suitable for marine ambients and industrial areas. Very good UV resistance.
Limited heat transmission losses.
Web App
ver1.0 6
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
ACCORDING TO EN14511
Unit
Model 1300
Refrigerant fluid R410A
Minimum partialization of the unit % 66
Compressors
Type Scroll
Number 3
Refrigerant ciruits 1
Capacity steps 2
Total oil charge kg 20.1
Total refrigerant charge kg 61.4
Fans
Type SRC
Number 6
Rated absorbed power kW 1.50
Rated absorbed current A 3.00
Heat exchanger - User side
Type PL
Number 1
Water content l 0.0
Dimensions
Lenght mm 3530
Width mm 2260
Height mm 2400
Weight
Net weight kg 2351.0
Hydraulic module - User side
Number of pumps 1
Rated absobed power kW 7.50
Rated absobed current A 15.0
Cooling conditions
Fluid - User side Water
Fouling factor - User side m² °C/kW 0.0430000
Inlet water temperature - User side °C 12.0
Outlet water temperature - User side °C 7.0
External air temperature °C 32.0
Height asl m 0
Cooling performances
Cooling capacity kW 310.3
Web App
ver1.0 7
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
Web App
ver1.0 8
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
Sound
63 [Hz] 125 [Hz] 250 [Hz] 500 [Hz] 1000 [Hz] 2000 [Hz] 4000 [Hz] 8000 [Hz]
Level
Lp [dB] 96 92 88 84 81 79 73 68 Lp_tot dB(A) 87
Lw [dB] 64 60 56 51 49 47 40 36 Lw_tot dB(A) 55
Technical data and dimensions are not binding. Thermocold reserves the right to make necessary changes without notice.
Technical data are referred to clean coils without fouling and do not consider the defrost cycles duty.
The minimum and maximum water flow admitted to the heat exchanger can be checked in the technical literature on Thermocold website.
The declared performance refers to basic units at an altitude of 0 meter above sea level; some options may affect the performance of the unit.
The use of appropriate correction factors is required to calculate performance if the following options are selected:
- hydraulic kits;
- special coils and/or special coating on coils;
- condensing/evaporating control devices;
- EC fans;
- Low ambient temperature kit;
- Low water temperature kit;
- Additional refrigerant circuit components (e.g. compressor suction service valve);
- High leaving hot water temperature module.
Standard hydraulic versions can operate with a maximum glycol percentage of 25%. Please contact the Thermocold sales support for the
quotation of hydraulic kits suitable for operation with a glycol percentage higher than 25%. If the hydraulic versions are selected, the following
additional water pressure values of the water circuit shall be considered, calculated in accordance to the water flow at nominal conditions (in
chiller mode with Tw in/out 12/7°C – Tair +35°C for the air cooled units; Tevap in/out 12/7°C – Tcond in/out 30/35°C for the water cooled unit).
Double pump --> 70kPa
Single pump + water tank --> 30kPa
Double pump + watr tank --> 90kPa
Performance tolerances at other conditions from the full load test conditions, as defined in EN Standard 14511-3:2013, are different and need to
be checked. Please contact Thermocold, also in case a performance test is needed at different conditions than those defined in EN Standard
14511-3:2013 (valid for chillers, heat pumps and multi-pipe units).
Hydraulic and electrical data shown are calculated in cooling only mode.
FLI = Full load power input at the conditions of the selection
FLA = Full load current at the conditions of the selection
SA = Inrush current (sum of LRA of the largest compressor, current of the other compressors, total current of the fans)
LRA = Locked rotor amperes for the largest compressor
FLImax= Full load power input at the worst conditions for compressors and fans (at the limit of the unit operating envelope)
FLAmax= Full load current at the worst conditions for compressors and fans (at the limit of the unit operating envelope)
Samax= Inrush current (sum of LRA of the largest compressor, current of the other compressors calculated at the worst conditions, total current
of the fans).
Acoustic data referred to the following operating conditions: evaporator water temp. In/out 12°/7°C - outdoor temp. 35°C.
Acoustic data refer to basic unit without hydraulic version and EC fans. Correction factors of sound power and sound pressure levels are
available on the technical bulletin.
The sound pressure levels are average values calculated in free field with a reflective surface and are indicative.
The sound power and sound pressure values are weighted (dBa).
The values shown in each octave band are indicative and represent sound pressure levels at 10 m unweighted (dB).
The water flows refers to the delta T shown in the datasheet.
FOR HEAT PUMPS: the selection of the fixed speed water pump shall be made in accordance to the water flow in cooling mode. In heating
mode the unit will work with the same water flow as in cooling but with consequent variation of the delta T respect to the one of the datasheet.
FOR MULTI-PIPE UNITS:
The selection of the fixed speed water pump on the cooling side shall be made in accordance to the water flow in cooling only mode. In chiller +
total recovery mode (cooling + heating) the unit will work with the same water flow as in cooling only mode but with consequent variation of the
delta T respect to the one of the datasheet. Unit controls on the entering cold water temperature.
The selection of the fixed speed water pump on the heating side shall be made in accordance to the water flow in heating only mode. In chiller +
total recovery mode (cooling + heating) the unit will work with the same water flow as in heating only mode but with consequent variation of the
delta T respect to the one of the datasheet. Unit controls on the entering hot water temperature.
Web App
ver1.0 9
Printing date:10/09/2018
T.C.M. S.r.l. - Via dei Ciclamini 25 - 70026 Modugno - Bari - Italy
Web App
ver1.0 10
Printing date:10/09/2018