TECHNICAL SPECIFICATIONS

NUFLO Scanner 2000 microEFM

Mounts directly to turbine meters,


orifice meters and cone meters

Cameron’s NUFLO™ Scanner® 2000 microEFM is among the most versatile


flow computers on the market. The device can operate alone to fulfill a Flow Computer
variety of measurement applications or be networked with other devices Data Logger
to provide a comprehensive flow management SCADA solution.
Multi-variable Transmitter

PID Controller
Key Features and Functions
The Scanner 2000 can operate autonomously with an integral battery for
• A
 utonomous operation for
one year or longer. Using only its integrated sensors, the Scanner 2000 can
One year (typical) via integral
measure differential pressure, pressure, temperature and flow meter pulses.
lithium battery pack*
The device can scale and calculate flow as well as indicate and record data,
• Measures
which can be downloaded to a user’s PC via a USB connection. Alternatively,
Industrial and
the integral keypad can be used to configure basic parameters and access
hydrocarbon gases
historical data.
Liquids
Saturated steam The instrument can be factory-installed on Cameron's gas and liquid turbine
• Senses meters, orifice meters and cone meters or shipped separately for connection
Differential pressure to other primary flow sensors. The Scanner 2000 can measure the standard
Pressure volume, mass and energy flows of saturated steam and many types
Temperature of gasses and liquids with custody transfer precision.
Flow meter pulses
• Computes In its most basic form, the Scanner 2000 replicates the BARTON® 202 flow
Standard volume recorder, the BARTON 242 pressure and temperature recorder, and the
Mass BARTON 200 and 227 differential pressure indicators.
Energy
With the addition of external connections, the Scanner 2000 can also act as a
• L ogs, indicates and
communicates any measured multi-variable transmitter, RTU and PID controller. This additional information
or computed variable can be transferred to and from the 2000 by analog or pulse (frequency),
• D
 ownloads historical data at Modbus or Foundation fieldbus serial communications.
high speeds for analysis and
data export using full-featured A single Scanner 2000 is powerful enough to measure the gas, oil and water
Windows-based software flow from a two- or three-phase separator or compute the flow from an
• C
 ertified internationally for ultrasonic gas flow meter. The Scanner 2000 is also versatile enough to act
measurement and electrical as a simple two-stream turbine totalizer or provide a Fieldbus connection to a
safety positive displacement or turbine meter.
ATEX / IECEx
CSA For more information about Scanner 2000 applications,
Measurement Canada see the following publications:
GOST • Scanner 2000 microEFM Solutions
• Supports a variety of protocols • Scanner 2200 EFM Solutions
RTU Modbus® • Scanner 2000 microEFM Well Testing Solution
Enron Modbus • Feature Profile on PID Control
Foundation Fieldbus

* Actual battery life is dependent on calculation,


sampling and display update frequency.

2
PID Control*

When purchased with the PID


control option, the Scanner 2000
can be used to control process
variables such as static pressure,
differential pressure, temperature
and flow rate. A 4-20 mA output
is configured to regulate a control
valve or adjustable speed drive
(ASD) and control parameters are
tuned with the easy-to-use tools
that are built into the standard
Scanner 2000 software platform,
ModWorX Pro. Users can configure
the Scanner 2000 to provide PID
control for a single parameter or opt
for PID control of flow rate with a
secondary pressure control.

See our feature profile on PID


control on the Cameron website for
more information.

* Not available with Foundation Fieldbus model

Foundation Fieldbus Communications

The Scanner 2000 for Foundation Fieldbus is a CSA explosion-proof and ATEX
intrinsically safe device that is approved by the Fieldbus Foundation. An integral
Fieldbus module converts Scanner 2000 Modbus data to fieldbus signals. Additional
inputs, flow volumes and calculations can be read by a fieldbus host and recorded.
Power and communications are supplied by a Fieldbus network and the integral
lithium battery provides backup power.

3
Approvals Calculations
Explosion-proof Package • Flow rate (natural gas, steam, liquid) • T urbine Input 2 cannot be used
AGA-3 simultaneously with a pulse input
• CE approved
AGA-7 Pulse Input
• C
 omplies with EMC Directive
Compensated liquid turbine (Expansion Board Required*)
2004/108/EC
ISO 5167
• A
 TEX and IECEx certified, • A
 ccepts a signal from a turbine meter
Cone
II 2 GD Ex d IIC T6 IP68 or PD meter
Averaging pitot tube (Annubar®)
40º F to 158º F (-40° C to 70° C) • Optically isolated
• Fluid properties
• C
 SA certified for US and Canada • Input: 3 to 30 VDC or contact closure
AGA-8-92 (detail and gross)
Class I, Div. 1, Groups B, C, D, IF-97 (steam) • C
 annot be used simultaneously
Class I, Div. 2, Groups A,B,C,D Generic liquid with Turbine Input 2
(non-sparking), Type 4 enclosure, (water or emulsions) Analog Inputs 1 and 2
ANSI 12.27.01 single seal API-2540 liquid (crude oil, jet (Expansion Board Required*)
(0 to 3000 psi) fuel, gasoline, fuel oils, lube oil) • Three-wire sensor interface
• M
 easurement Canada certified • Wet correction (steam) • S ensor power same as external
for custody transfer, Approval James (orifice) power supply for main board
No. AG-0557C Chisholm (orifice) (6 to 30 VDC)
• GOST-R/GOST-K certified Steven (cone) • Accuracy: 0.1% of full scale
• A
 SME pressure vessel code compliant
• T emperature effect: 0.25% of full
(0 to 3000 psi); CRN 0F10472.5C Communications/ scale over operating temperature
• Fieldbus Foundation approved Archive Retrieval range of -40° F to 158° F
Intrinsically Safe Package • M
 odbus (RTU) with two on-board (-40° C to 70° C)
• CE approved RS-485 communications slave ports • Resolution: 20 bits
• A
 TEX certified, II 2G Ex ia IIB T4 IP66 COM 1 and COM 2 baud rates:
• U
 ser-adjustable sample time
40º F to 172º F (-40° C to 78° C) 300 to 38.4K
and damping
• Fieldbus Foundation approved • F oundation Fieldbus with one
Process Temperature Input
on-board RS-485 communications
slave port • 1
 00 ohm platinum RTD with
Display two-wire, three-wire or four-wire
COM 1 baud rate: 300 to 38.4K
• T wo-line LCD with easy-to-read interface
• U
 SB communications with
alphanumeric characters • S ensing Range: -40° F to 800° F
optional adapter
8 -digit display of values (top line) (-40° C to 427° C)
6 -digit display identifies each • Enron Modbus compliant downloads
• A
 ccuracy: 0.2° C (0.36° F) over
scrolling parameter and its • U
 ser-definable block allows the
sensing range at calibrated
engineering unit (bottom line) grouping of up to 25 floating point
temperature
• V
 iew up to 12 user-defined values for faster data transfer when
used with a SCADA system • T emperature effect (Fahrenheit):
parameters
0.54° F over operating range of
• View daily log data (99 days) • F ull archive download in
-40° F to 158° F
approximately three minutes with
• User-selectable units of measurement • T emperature effect (Celsius):
main board only (six minutes with
• Character height is 0.3” expansion board option) 0.3° C over operating range of
• A
 djustable contrast and -40° C to 70° C
update period Inputs • Resolution: 24-bits
• U
 ser-adjustable sample time
Turbine Meter Inputs 1 and 2
Power and damping
(expansion board required for
• L ithium battery for autonomous
turbine input 2*)
operation * Not available with Foundation Fieldbus model
• C
 onfigurable sensitivity adjustment
• E xternal power supply (6 to 30 VDC)
(20 mV to 200 mV, peak to peak)
optional with internal battery backup
• Frequency range: 0 to 3500 Hz
• F ieldbus network power
• Input amplitude: 20 mV to 3000 mV,
(Scanner 2000 Foundation Fieldbus
peak to peak
model only)

4
Outputs
Digital Output • Alarm output • Represents any measured variable
• C
 onfigurable as pulse output Low/high (e.g., differential pressure) or
or alarm output Out-of-range calculated parameter (e.g., flow rate)
• Solid-state relay Status/diagnostic • Regulates control valve in PID
• O
 utput rating: 60 mA max Latched/unlatched control applications
at 30 VDC Normally open/normally closed • Optically isolated
• Pulse output Analog Output • Resolution: 16-bits
Configurable pulse duration (Expansion Board Required*)
Maximum frequency: 50 Hz • 4 -20 mA
* Not available with Foundation Fieldbus model
Configurable pulse • A
 ccuracy: 0.1% of full scale at 25° C
representation (1 pulse = 1 MCF) (77° F), 50 PPM/° C (27.8 PPM/° F
 ased on any accumulator
B temperature drift
(flow run or turbine inputs)

Keypad Configuration

With the three-button keypad,


changes to basic parameters can be
made quickly and easily simply by
removing the enclosure lid (computer
software is not required). The slave
address, baud rate, date and time and
orifice plate size can all be configured
from the keypad.

CONFIGURATION: CONFIGURATION:
Move between menus Save configuration
and menu selections settings
TEST ACCESS
OPERATION: OPERATION:
View next parameter Save totals

CONFIGURATION:
PRESS + PRESS +
Change digits and
other menu selections
Simultaneously to view Simultaneously to access
time/date, temperature OPERATION: configuration menu
and battery voltage View daily logs

5
Memory MVT Accuracy
• Non-volatile memory for • Stability: Long-term drift is less than • Field calibration
configuration and log data ±0.05% of URL per year over a 1 to 12 calibration points
• 256 KB (512 KB with expansion five-year period for each parameter
board option) • Differential pressure: ±0.05% of span Three methods: multipoint,
Data stored up to 10 years Effect on differential pressure for set zero point and verify
without power a 1000 psi change in pressure Inputs are automatically locked
Zero shift: ±0.05% of URL during calibration
MVT Span shift: ±0.01% of reading • Maintenance
• Provides linearized digital data • Static pressure: ±0.05% of span Change plate
Static pressure Change cone
• Temperature performance: 0.25%
Differential pressure (linearization: 1 to 12 points)
of full scale over full operating
• Available with bottom ports Change averaging pitot tube
temperature range
(gas measurement) or side ports Change gas composition
• Resolution: 24 bits
(liquid or steam measurement) Change steam properties

• NACE compliant units also available Environmental Change liquid parameters


Change flow coefficients
• User-adjustable sample time and Operating Temperature Range
Change K-factor
damping • -40° F to 158° F (-40° C to 70° C)
(linearization: 1 to 12 points)
• LCD contrast is reduced below Change turbine flow meter
MVT Pressure Ranges -22° F (-30° C)
• Archive data downloads
Configurable downloads of
Static
Differential
Maximum Audit Trail
Pressure/ Overrange all or new records
Pressure • Daily records: 768 (more than
SWP Pressure Download types: daily, interval
(in. H20)
(PSIA) (PSIA) two years)
and event/alarm records
100 30 150 • Interval records: 2304 (greater than
Downloads are automatically
300 200 (1) 450 3 months of one-hour intervals);
saved in uneditable binary
840 450 6392 (greater than 8 months of
(SDF) files
500 30 (2) 750 one-hour intervals) with expansion
Exports to .xls, .csv, .rtf, .html,
200 (1) 750 board option
Flow-Cal® and PGAS® formats
1500 200 (1) 2250 Adjustable from five seconds
• Reporting
300 2250 to 12 hours
Daily logs (table or trend graph)
400 (1) 2250 • Event/alarm records: 1152
Interval logs
840 2250
• Records up to 16 user-defined (table or trend graph)
3000 (3) 200 (1) 4500
parameters Event/alarm logs
300 4500
Configuration settings
400 (1) 4500 Interface Software
Calibration settings
840 4500
• Provided at no charge Snapshot of current status data
5300 (3) 200 (1) 7420
• Easy to use and calculated parameters
300 7420
• Real-time data polling • Online documentation
400 7420
840 7420
• Complete configuration Quick start guides
Configuration upload tool for Hardware manual
(1)
T hese ranges are stocked for quicker delivery configuring multiple units Software manual
(2)
Available on request
(3)
• Multi-level security
Not evaluated for Measurement Canada approval

6
Dedicated button for quick and easy downloads

Four menus
simplify
navigation

The ModWorX Pro


software interface
offers easy access to
the most commonly
used functions from
one main display
screen.

Documentation for quick reference

Calibrate Inputs: Maintain Flow Run: Maintain Turbine: Configure:


Differential Pressure Change Orifice Plate Change Turbine SYSTEM PARAMETERS
Static Pressure Change Cone Flow Meter Device ID
Process Temperature Change Gas Composition Change K-factors Date and Time
Change Steam Properties Communications
Change Flow Coefficients Security
Calibrate, verify and Change Avg. Pitot Tube Display
set zero offset selections Archive
available for each parameter.
Alarm
Modbus Registers
FLOW RUN SETUP
Task-based menus help operators TURBINE SETUP
perform their jobs quickly and easily. INPUTS
Differential Pressure
Static Pressure
Process Temperature
OUTPUTS
Digital

7
North and South America
14450 JFK Blvd.
Houston, TX 77032
USA
Tel 1 281 582 9500
ms-us@c-a-m.com

Europe, Africa, Caspian and Russia


3 Steyning Way
Southern Cross Trading Estate
Bognor Regis
West Sussex PO22 9TT
England, UK
Tel 44 1243 826741
ms-uk@c-a-m.com

Asia Pacific
Suite 16.02 Menara AmFirst
No. 1 Jalan 19/3
46300 Petaling Jaya
Selangor Darul Ehsan
Malaysia
Tel 603 7954 0145
ms-kl@c-a-m.com

Middle East
Level 9, Al Jazira Club Tower A
P.O. Box 47280, Muroor Road
Abu Dhabi
United Arab Emirates
Tel 971 2 596 8400
ms-uk@c-a-m.com

For more information on the NUFLO Scanner 2000 Flow Computer,


Contact us
contact our sales team at 580 470 9600.

A L G E R I A • C A N A DA • C H I N A • I N D I A • M A L AYS I A • R U SS I A • UA E • U K • U S A www.c-a-m.com/measurement
© 2013 Cameron | NUFLO is a trademark of Cameron. BARTON, Modbus and SCANNER are registered trademarks of Cameron.
Other are trademarks of their respective corporations. | SWP 1M 06/13 AD00681M