WATER HEATING CALCULATION

Flamco
Calculation of water heating systems
Rules for determining the heating requirement for heating drinking water in
residential constructions according to the German standard DIN 4708 Part 2DIN
4708 Part 2 Page 1

CONTENTS
Page
1 Scope of validity 1
2 Other relevant standards 1
3 Terms 1
4 Determining the demand factor N 2
4.1 Calculation reference documents 2
4.2 Computation pass 3
5 Application 4
5.1 Choosing a water heater 4
5.2 Checking the rated power of the heat generator 4
6 Sample calculation 6

1 Scope 3 Terms
This standard is valid as the basis for the uniform For other terms refer to DIN 4708 Part 1 and Part 3.
determination of the heating requirement in central
drinking water heating systems in residential 3.1 Demand factor N
constructions whose water heaters are heated
directly or indirectly. They can be combined with The demand factor N is the result of the
heat generators for heat supply or can be intended determination process for the requirement for
exclusively for heating drinking water (see also DIN heated drinking water. It is identical to the number
4753 Part 1). of unit apartments in the construction project, but it
does not necessarily correspond to the number of
apartments.
This standard does not apply if an above-average
simultaneity in the utilization of the water heating 3.2 Occupation rate p
unit is to be expected according to the position and The occupation rate p is the number of persons per
purpose of the building to be supplied apartment.
(e.g. in factory apartments) or if the central water
heating system is intended only for supplying a self- 3.3 Unit apartment
contained apartment unit (apartment).
The unit apartment is a dwelling size determined
2 Relevant Standards from statistical values, for which the number of
rooms r, occupation rate p and requirement for
DIN 4471 Bath tub, cast iron, overview hydrants wv are agreed upon and whose demand
DIN 4701 Heating systems; rules for
calculating the heating requirement factor is N = 1. (Refer to DIN 4708 Part 1 Appendix
of buildings A.)
DIN 4708 Part 1 Central water heating systems,
terms and basis of calculation 3.4 Number of rooms r
DIN 4708 Part 3 Central water heating systems; The number of rooms r is the number of rooms of a
rules for testing the capacity of apartment which must be taken into consideration
water heaters for residential units when calculating the demand factor N .
DIN 4753 Part 1 Water heating systems for drinking
and process water; design, fitting
and testing 3.5 Number of apartments n
The number of apartments n is the number of
apartments of a construction project, in which the
number of rooms, the occupation rate and the
sanitary fittings are the same.

Standards Commission for Heating, Ventilation and Air Conditioning (NHR) at the DIN German Institute
for Standardization e.V

VEN1139 © Flamco, Edition: 2005 / EXP Page 1


WATER HEATING CALCULATION

Flamco
3.6 Number of hydrants v Table 1
The number of hydrants v is the number of hydrants
for heated water per residence, which must be taken Number of rooms Number of occupants
into consideration when calculating the demand r p
factor N . 1 2,02)
1 1/2 2,02)
3.7 Hydrant rate wv 2 2,02)
The hydrant rate wv is the quantity of heat needed to 2 1/2 2,3
draw heated water from a hydrant. 3 2,7
3 1/2 3,1
4 Determining the demand factor N 4 3,5
4.1 Calculation reference documents 4 1/2 3,9
4.1.1 Information on the construction 5 4,3
project 5 1/2 4,6
6 5,0
Determining the demand factor N requires the
6 1/2 5,4
following documents and information from the
building owner or architects: 7 5,6
a) Floor plans of all floors in the building which are 2) If the residential building to be provided has mainly
to be supplied centrally with heated water, at
least on a scale of 1 : 100, showing all hydrants. 1- and/or 2-room dwellings, the occupany number p for
b) Information on the type, number and size of these dwellings is to be raised by 0.5.
sanitary devices in order to determine the
number of hydrants v and hydrant rate wv.
c) Information on the number of persons per
4.1.5 Number of hydrants v
apartment. As a minimum, the statistical values When determining the hydrants to be included in the
given in Table 1 are to be used as the basis of calculation v for heated water, it is assumed that
calculation. only the hydrants within a apartment are to be taken
d) If the occupier is to influence fittings in the into consideration. According to the sanitary fittings
construction project individually in respect of the of the apartment, a distinction is made between
number and type of hydrants, the building residences with standard fittings (see Table 2) and
owner must supply corresponding information. residences with comfort fittings (see Table 3).
If the calculation results in a demand factor N of
about 1, but it is known or suspected that more than 4.1.6. Features for assessing sanitary
one bath will be needed in the near future for fittings in residences and their
reasons of sanitary fittings (e.g., the physical inclusion in determining the
separation of bath and shower), the selected power
of the heater must be greater than calculated. requirements
When deteriming the requirement, a distinction is
4.1.2 Number of apartments n made between:
The respective number of identical apartments ni can - Residences with normal fittings
- Residences with comfort fittings.
be seen from the drawings. Normal fittings are deemed to exist, if the devices
mentioned in Table 2 are present.
4.1.3 Number of rooms r
The number of rooms r of each apartment group ni Table 2. Normal fittings
can be seen from the drawings. It refers to the
to be used for
number of living rooms of a apartment. Secondary Sr. Existing
rooms such as the kitchen (not kitchen-living area!), demand deter-
No. fitment
entrance hall, corridor, bath and storage room are mination according
per dwelling
not taken into consideration. to section 4.2:

4.1.4 Number of occupants p 1 Bath:


1.1 1 Tub bath 1600
The data regarding the actual occupation of the
individual apartments, but at least the values of conforming to DIN
statistical occupation, must be used as given in 4471 (acc
Table 1. to table 4 Sr. No. 1)
Or: 1 Tub bath 1600
The data on the statistical number of occupants p of
each apartment is arrived at from the number of 1 shower stall with/ conforming to DIN
rooms used in the calculation r1). without mixer unitand 4471 (accto table 4
normal shower (acc. to Sr. No. 1 or No. 2)
Tab. 4 Sr. No. 5)
1.2 1 Washing counter (acc.
to Table 4 Sr. is not considered
No. 9)

2 Kitchen:
1 Kitchen washing
1) >From current information of the Federal Statistics place (acc. to Table 4 is not considered
Office on the occupation density of apartments. Sr. No. 12)

Comfort fittings are deemed to exist, if other or more


comprehensive fittings than those indicated in Table
2 for normal fittings are present in every apartment.

Page 2
WATER HEATING CALCULATION

Flamco
Table 3. Comfort fittings

Existing amenities per apartment To be taken into account for calculating requirements

Room Amenities

Bath: Bath*1 As existing acc. to table 6, no. 2 to 4


Shower cubicle*1 As existing, incl. any additional facilities acc. to
table 6, no. 6 or 7, if arranged to permit
simultaneous use*2
Wash basin*1 Not to be taken into account
Bidet Not to be taken into account
Kitchen: 1 Kitchen sink Not to be taken into account
Guest Bath per guestroom:
room: As existing acc. to table 6, no. 1 to 4 wiht 50% of
draw-off demand "wv"

or As existing acc. to table 6, no. 5 to 7 with 100%


Shower of draw-off demand "wv"
Washbasin At 100% of draw-off demand "wv" table 6*3
Bidet At 100% of draw-off demand "wv" table 6*3
1* Size different from standard specification.
2* If no bath is installed, a bath is assumed instead of a shower cubicle as with standard specification (see table 6, no. 1)
unless draw-off rate of shower cubicle exceeds that of bath (e.g. deluxe shower). If several different shower cubicles
are installed, at least one bath is assumed for the shower cubicle with the highest draw-off rate.
3* If no bath or shower cubicle is assigned to guestroom.

4.1.7 Hydrant rate wv


The hydrant rate wv of the heated water
hydrants used in the calculation can be obtained
from Table 4. Table 5 should also be taken into
consideration.

4.1.8 Unit apartment


The total heat requirement of all apartments to be
supplied is converted into unit apartments.
The following features are agreed-upon for the unit
apartment:
Number of rooms r =4
Number of occupants p = 3.5 (3 to 4)
Hydrant rate wv = 5820 Wh/ water drawn
to fill a bath tub.

4.2 Calculation procedure


The demand factor N is determined from the
information given in section 3.1 according to the
formula:

where

Σ (n • p • v • wv) Σ (n • p • v • wv)
N= = (1)
p • wv 3.5 • 5820
where
p • wv = 3.5 • 5820 as values for one unit
apartment.
The pre-printed form is used for the calculation
(Table 5).
The apartments to be provided with heated water
are to be entered in the columns 1, 2 and 3 of the
form (Table 5).

Page 3
WATER HEATING CALCULATION

Flamco
Table 4. Hydrant rate wv (Heat quantity in Wh for heated water for one draw)

No. of sanitary facilities or draw-off point DIN code Draw-off Draw-off


volume per rate "wv"
use or useful per use in
capacity in Wh
litres
1 Bath NB 1 140 5820

2 Bath NB 2 160 6510

3 Small and step-type bath KB 120 4890

4 Large bath (1800 mm x 750 mm) GB 200 8720

5 Shower cubicle*4) with mixer tap and economy shower head BRS 40*5) 1630

6 Shower cubicle*4) with mixer tap and standard shower head*6 BRN 90*5) 3660

7 Shower cubicle*4) with mixer tap and deluxe shower head*7 BRL 180*5) 7320

8 Washbasin WT 17 700

9 Bidet BD 20 810

10 Washbasin HT 9 350

11 Kitchen sink SP 30 1160


For baths whose usefull capacities vary considarably, draw-off rate "wv" should be calculated in Wh acc. to the formula
wv = c x V x ∆T and be used in the calculation (∆T = 35 K)
*4 To be included in calculation only if bathroom and shower cubicle are in sperate rooms, i.e. simultaeous use is possible.
*5 Based on 6 minutes’ use.
*6 Fitting flow class A to DIN EN 200.
*7 Fitting flow class C to DIN EN 200.

5 Application or calculated and indicated in the technical


5.1 Choosing the water heater documents and obtained from there. In the case of
combined boilers, it must be clear which proportion
According to the demand characteristic N of the indicated nominal heating power is available
determined in section 2, the water heater is to be for heat supply.
chosen according to the power characteristics The apartments that are identical with respect to the
shown in the manufacturer's documentation, NL . number of rooms and scope of sanitary equipment
The power characteristic must be greater than or at are summarized with a serial number (Column 1).
least equal to the demand characteristic N (see also The following are to be entered:
section 4.1.1, last paragraph). Column 2: the number of rooms r
Column 3: the number of apartments n
5.2 Checking the power rating of the heat Column 4: the occupancy number p, either from
generator Table 1 or according to the information
obtained from the building owner
5.2.1 General Column 5: the result of multiplying column 3 by
Heat generators that are used for central heating as column 4
well as for water heating must - depending on the Column 6: the number of hydrants v, which is to
ratio of the two heat consumers - have an be taken into consideration when
allowance over and above the boiler power calculating the demand characteristic
determined according to DIN 4701 ZK according to N.
the formula: Column 7: the short designation (see Table 2) of
QN=QK+ZK in kW (2) the number of hydrants used in
column 6
Here, Column 8: the hydrant rate wv, (see Table 2) of
QN is the rated heating output of the boiler in kW the number of hydrants entered in
column 6 and column 7
QK is the boiler power for the heat requirement Qh Column 9: the result of multiplying column 6 by
according to DIN 4701 including the allowance column 8
for pipeline losses in kW Column 10: the result of multiplying column 5 by
ZK is the boiler allowance for the heating of column 9.
drinking water in kW. The values entered in column 10 are to be added
Depending on the circumstances of the building, the and the result as the numerator in equation (1) for
boiler allowance ZK can be reduced by the calculating the demand characteristic N .
allowances applied in the heat requirement The numbers of apartments entered in column 3 are
calculation based on DIN 4701, edition January to be added and the result entered after Σn . By
1959, section 2.2.21, if this can be substantiated by comparing this with the calculated demand
the usage characteristics. characteristic N the standard of sanitary fittings for
the construction project can be identified. In the
5.2.2 Boiler allowance ZK case of exclusively normal sanitary fittings, the
The magnitude of the boiler allowance ZK depends demand characteristic N is greater than or equal to
on the construction type of the water heater Σn. In construction projects whose sanitary fittings
(storage or throughflow heater) and is determined place higher demands on the heated water supply,
for each device by the manufacturer within the the demand factor is N greater than Σn.
framework of the power testing according to DIN
4708 part 3, edition October 1979, section 7.5.

Page 4
WATER HEATING CALCULATION

Flamco
Table 5. Form

Project No:
Requirement for heated water in centrally supplied dwellings
Sheet No:

Determination of the demand characteristic N for size determination of the water heater .

Project

Number of occupants p: according to statistical values according to section 4.1.4

1 2 3 4 5 6 7 8 9 10 11
Hydrants (per dwelling)

Sr. No. of Number Number No. of Number Symbol Hydrants


the of of occu- of require-
dwelling rooms dwellings pants hydrants ment in Remarks
groups Wh in Wh in Wh
r n p n.p v wv v . wv n . p . v . wv
1 1,5 4 2,0 8,0 1 BRN 1630 1630 13 040

2 3,0 10 2,7 27,0 1 NB 1 5820 5820 157 140

3 4,0 2 3,5 7,0 2 BRK 4070 8140 56 980

1 NB 2 6510 6510 91 140

4 4,0 4 3,5 14,0 1 BRK 4070 4070 56 980

1 BD 810 810 11 340

1 NB 1 5820 5820 125 130


50 % acc.
5 5,0 5 4,3 21,5 1 NB 1 5820 2910 62 565 to Table 3

1 BD 810 810 17 415

Σ ni = 25 Σ (n . p . v . wv) = 591 730 Wh

N = Σ (n p v wv)
. . . 591 730 Wh
= = 29,0
3,5 . 5820 20 370

Page 5
WATER HEATING CALCULATION

Flamco
6 Sample calculation
The demand characteristic N is used to determine the size of the water heater for the central water heating
system of a apartment construction project with the following apartments and equipment:

Number of Number of occupancy Amenities of the apartment to allow for in calcu-


apartments rooms rate lating requirements
n r p Quantity/description No. of draw-off
points/description

1 shower cubicle with standard shower head acc. to table 4 on page 31


4 1,5 2,0 1 washbasin in bathroom 1 shower cubicle (BRN)
1 sink in kitchen

1 bath 140 litres acc. to table 4 on page 31


10 3 2,7 1 washbasin in bathroom 1 bath (NB1)
1 sink in kitchen

1 shower cubicle with mixer tap and deluxe acc. to table 5 on page 32
shower 1 shower cubicle (BRL)
3,5 1 shower cubicle with standard shower head
2 4
(physically separated)
1 washbasin in bathroom
1 sink in kitchen

1 bath 160 litres acc. to table 5 on page 32


1 shower cubicle with mixer tap and 1 bath (NB2)
4 4 3,5 deluxe shower head in a separate room 1 shower cubicle (BRL)
1 washbasin in bathroom
1 bidet
1 sink in kitchen

1 bath 160 litres acc. to table 5 on page 32


1 washbasin in bathroom 1 bath (NB2)
5 5 4,3 1 bidet 1 bath (NB1) at 50% of
1 bath 140 litres in guest bathroom draw-off rate "wv"
1 washbasin in guestroom 1 washbasin (WT)
1 sink in kitchen 1 bidet (BD)

Page 6